Product Details:
Payment & Shipping Terms:
|
2080-IQ4OV4 is a 8-point combo plug-in in the Bulletin 2080 Micro800 plug-in family. One slot gives four inputs and four outputs, which doubles the usable I/O of a small controller without a second plug-in.
A plug-in module snaps into a slot on the controller itself, so the I/O count grows without adding a DIN rail footprint or an expansion bus module.
| 2080-IF2 | 2-channel analog input plug-in | IN STOCK |
| 2080-IF4 | 4-channel analog input plug-in | IN STOCK |
| 2080-OF2 | 2-channel analog output plug-in | IN STOCK |
| 2080-TC2 | 2-channel thermocouple plug-in | IN STOCK |
| 2080-RTD2 | 2-channel RTD plug-in | IN STOCK |
| 2080-TRIMPOT6 | 6-channel trimpot analog input | IN STOCK |
| 2080-OB4 | 4-point DC source output plug-in | IN STOCK |
| 2080-OV4 | 4-point DC sink output plug-in | IN STOCK |
| 2080-OW4I | 4-point relay output plug-in | IN STOCK |
| 2080-IQ4OV4 | 8-point combo, 4 in / 4 out sink | IN STOCK |
| 2080-IQ4OB4 | 8-point combo, 4 in / 4 out source | IN STOCK |
| 2080-SERIALISOL | isolated RS-232/RS-485 serial plug-in | IN STOCK |
| 2080-MOT-HSC | high-speed counter plug-in | IN STOCK |
| 2080-MEMBAK-RTC | memory backup with real-time clock | IN STOCK |
| 2080-USBADAPTER | Micro810 USB adapter | IN STOCK |
| 2080-LCD | Micro810 LCD display with keypad | IN STOCK |
| 2080-REMLCD | Micro820 remote LCD display | IN STOCK |
| 2080-PS120-240VAC | 120/240 V AC to 24 V DC power supply | IN STOCK |
Catalog number |
2080-IQ4OV4 |
Product type |
8-point combo plug-in |
Channels / points |
4 inputs, 4 outputs |
Signal |
12/24 V DC sink/source input, 12/24 V DC sink output |
Isolation |
Non-isolated |
Resolution |
Not published |
Controller compatibility |
Micro820, Micro830 and Micro850 plug-in slots; not supported on Micro810 |
Dimensions, H x W x D |
12-pin terminal block |
Temperature rating |
Per 2080-UM004 |
Lifecycle status |
Active |
UPC |
Not published |
Country of origin |
Not published |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-UM004 (module specifications) and Rockwell literature library (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
2080-IQ4OV4 is a 8-point combo plug-in in the Bulletin 2080 Micro800 plug-in family. One slot gives four inputs and four outputs, which doubles the usable I/O of a small controller without a second plug-in.
A plug-in module snaps into a slot on the controller itself, so the I/O count grows without adding a DIN rail footprint or an expansion bus module.
Channel count and signal type are fixed by the catalog number: 4 inputs, 4 outputs, 12/24 V DC sink/source input, 12/24 V DC sink output.
Micro820, Micro830 and Micro850 plug-in slots; not supported on Micro810
The module is configured in Connected Components Workbench, not by a hardware switch, so the project file has to match the module that is physically fitted.
Micro810 controllers have no plug-in slots at all; the Micro810 accessories take the USB or display port instead.
Rockwell prints the input side as 12/24 V DC sink/source, IEC Type 3, and the output side as 12/24 V DC sink.
Every plug-in in this family is rated for the same panel environment, and the terminal block is the part that decides whether a swap is quick or not.
Isolation is Non-isolated. Where that matters, it is stated per model rather than assumed for the whole family.
Rockwell lists this catalog number as Active.
Dimensions are 12-pin terminal block, rated ambient Per 2080-UM004.
UPC is Not published, country of origin Not published.
A used plug-in is only worth fitting if the terminal block and the retaining clips are intact; the clips are what holds the module against vibration.
Match the catalog number exactly. The family contains pairs that differ only in sink versus source output or isolation, and the front label is the only reliable identifier once the box is gone.
It is the sink version: the source version is 2080-IQ4OB4, and the part numbers differ by two letters.
What does 2080-IQ4OV4 do?
8-point combo plug-in: 4 inputs, 4 outputs, 12/24 V DC sink/source input, 12/24 V DC sink output.
Which controllers accept 2080-IQ4OV4?
Micro820, Micro830 and Micro850 plug-in slots; not supported on Micro810
What is the resolution of 2080-IQ4OV4?
Not published.
What are the dimensions of 2080-IQ4OV4?
12-pin terminal block, rated Per 2080-UM004.
Is 2080-IQ4OV4 still available from Rockwell?
Rockwell lists it as Active.
2080-IQ4OV4 is a 4 input plus 4 sinking output combination plug-in module for the Micro800 controllers, and the specification rows below are the published values for this catalog number together with the two or three rows an engineer actually checks before ordering.
| Specification | Value |
|---|---|
| Catalog number | 2080-IQ4OV4, 8 point plug-in module, 4 DC sink/source inputs and 4 DC sink outputs |
| Inputs | 4, 12/24V DC sink or source |
| Outputs | 4, 12/24V DC sinking |
| Input on-state voltage | 9 to 30V DC |
| Input on-state current | 2 mA at 9V DC minimum, 5 mA maximum |
| Input off-state voltage | 5V DC maximum, leakage 1.5 mA maximum |
| Output on-state voltage | 10 to 30V DC, nominal 24V DC |
| Output current | 0.5 A steady state; 2 A surge for 2 s minimum |
| IEC compatibility, inputs | Type 3 |
| Slot count | One plug-in slot for the whole module |
| Source | 2080-TD001 Micro800 technical data, digital plug-in module specifications |
The output half sinks, which means the load is wired to the positive supply and the module closes the return path. This is the version for a panel that already distributes positive to every field device and switches the common.
Slot economy is the whole argument again: eight channels in one slot, at the cost of a fixed output polarity that cannot be changed in the field.
Every row on this page is a published value for the catalog number named in the heading. Where the source prints a range, the range is reproduced; where the source is internally inconsistent, the inconsistency is described rather than resolved.
Eight to ten milliseconds of filter time on a plug-in input is a deliberate compromise. It rejects contact bounce on a pushbutton and it also rejects a two millisecond cam pulse, so a machine that needs to catch a short pulse needs the high speed counter module rather than a faster filter setting.
Common mode and normal mode rejection of one hundred and seventy decibels are the numbers that make a temperature reading stable next to a drive. Without them the channel reads the switching frequency rather than the process, and the filter in the program cannot recover it.
Sink and source is a wiring decision that has to be made against the sensor type rather than against the controller. A sourcing input expects the field device to switch the positive side, and a sinking output pulls the load to common, so a mixed panel needs the combination module and not two separate ones.
Combination modules exist because a two slot controller runs out of slots before it runs out of I/O. Four inputs and four outputs in one module is the same channel count as two separate modules, and it costs one slot instead of two, which is the entire argument.
Twelve bits of resolution on an analog output with one percent accuracy means the step size is finer than the accuracy by a factor of four or five. The commanded value can be set precisely and the delivered value cannot be certified to the same precision, and the loop has to be tuned to the second.
Input impedance between three and twelve volts is the lowest of the three bands, which is where a two wire sensor with a series resistor has to work. Above twelve volts the impedance rises again, and that non-monotonic curve is the reason a marginal sensor works at twenty four volts and fails at ten.
The RTD type list is long and the accuracy figure is a single number for the whole list. A ten ohm copper sensor and a thousand ohm platinum sensor do not behave alike, and the resolution in degrees follows the sensor rather than the module.
A plug-in module is bought for the slot, not for the function. Two slots on a Micro820 either take two analog inputs or two relay outputs or one of each, and that allocation is decided once at the panel design stage and then lives for the life of the machine.
A four point module rated at half an amp steady and two amps for two seconds is quoting an inrush allowance, not a continuous load. A solenoid valve that draws two amps for one hundred milliseconds is inside the specification, and the same valve held energised is not.
A real time clock backed by a battery is a maintenance item with a date on it. Three and a half years from the date of manufacture at normal temperature and two and a half years at freezing is the shelf life statement, and a panel commissioned two years after delivery starts with half of it gone.
The on-state window is what the sensor has to deliver. Nine volts at two milliamps at the low end and thirty volts at five milliamps at the high end defines a band, and a sensor whose off-state leakage sits above one and a half milliamps will read as permanently on.
Temperature modules are specified by accuracy at twenty five degrees and by a cold junction error, and the second number is usually the larger of the two on a thermocouple channel. A one degree accuracy with a one point two degree cold junction error is not a one degree measurement.
A non-isolated module shares the controller reference, which is the cheapest way to add a channel and also the way that a ground loop enters the panel. Isolation is bought at the expansion module level and it is the reason those modules cost more per channel.
One slot for eight channels, with a fixed sinking output half.
Related models, options and spare parts for this range are listed in the Allen-Bradley Micro and Nano systems category.