Product Details:
Payment & Shipping Terms:
|
2085-OA8 is a 8-point AC output module in the Micro800 expansion line. Triac outputs switch AC loads without a relay, so an AC solenoid or a small contactor coil can be driven straight from the module with no interposing relay.
Field wiring lands on the removable terminal block (RTB). The RTB can be unplugged with the wiring in place, which is the reason a failed module can be swapped without re-terminating a panel.
| 2085-IA8 | 8-point 120 V AC input | IN STOCK |
| 2085-IM8 | 8-point 240 V AC input | IN STOCK |
| 2085-OA8 | 8-point 120/240 V AC triac output | IN STOCK |
| 2085-IQ32T | 32-point 12/24 V DC sink/source input | IN STOCK |
| 2085-OV16 | 16-point 12/24 V DC sink transistor output | IN STOCK |
| 2085-OB16 | 16-point 12/24 V DC source transistor output | IN STOCK |
| 2085-OW8 | 8-point AC/DC relay output | IN STOCK |
| 2085-OW16 | 16-point AC/DC relay output, 2 A | IN STOCK |
| 2085-IF4 | 4-channel 14-bit isolated analog input | IN STOCK |
| 2085-IF8 | 8-channel 14-bit isolated analog input | IN STOCK |
| 2085-OF4 | 4-channel 12-bit isolated analog output | IN STOCK |
| 2085-IRT4 | 4-channel 16-bit RTD and thermocouple input | IN STOCK |
| 2085-ECR | 2085 expansion bus terminator | IN STOCK |
Catalog number |
2085-OA8 |
Product type |
8-point AC output module |
Points / channels |
8 outputs |
Signal |
120/240 V AC, triac |
Isolation |
Field wiring to controller |
Backplane current, 5 V DC |
180 mA |
Dimensions, H x W x D |
28 x 90 x 87 mm |
Temperature rating |
Per 2085-IN005 |
Lifecycle status |
Active |
UPC |
Not published |
Country of origin |
Not published |
Terminal block |
Removable terminal block (RTB) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2085-IN005 (module specifications) and 2080-UM003 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
2085-OA8 is a 8-point AC output module in the Micro800 expansion line. Triac outputs switch AC loads without a relay, so an AC solenoid or a small contactor coil can be driven straight from the module with no interposing relay.
It mounts to the right of a Micro810, Micro820, Micro830, Micro850 or Micro870 controller and is addressed by its position in the expansion chain, so the slot order in the project has to match the physical order.
Signal and channel count are fixed by the catalog number: 8 outputs, 120/240 V AC, triac.
Field wiring lands on the removable terminal block (RTB). The RTB can be unplugged with the wiring in place, which is the reason a failed module can be swapped without re-terminating a panel.
Triac outputs are solid state: they have a leakage current in the off state and they do not like being switched into a capacitive load without a snubber.
Size the conductors and the torque to the module data sheet; the RTB screws are hand-tightened, not driven with a power tool.
Module order matters: the expansion chain is scanned in physical order, and the bus is ended with a terminator. It draws the same 180 mA bus current as the 240 V input card.
Backplane draw is 180 mA. Add every module in the chain before deciding on the controller power budget.
Rockwell lists this catalog number as Active.
Dimensions are 28 x 90 x 87 mm and the rated ambient is Per 2085-IN005.
UPC is Not published, country of origin Not published.
Check that the module comes with its RTB. A module sold without the terminal block is not a drop-in swap, whatever the price difference.
Confirm the catalog number against the project: the 2085 line separates sink from source transistor outputs and AC input from DC input by catalog number only.
Where the load is inductive or the switching duty is high, the relay output modules are the safer choice.
What does 2085-OA8 do?
8-point AC output module: 8 outputs, 120/240 V AC, triac.
Where does 2085-OA8 mount?
To the right of a Micro800 controller, in the expansion chain, connected through the 2085 bus.
How much backplane current does 2085-OA8 draw?
180 mA.
What are the dimensions of 2085-OA8?
28 x 90 x 87 mm, rated Per 2085-IN005.
Is 2085-OA8 a current Rockwell product?
Rockwell lists it as Active.
2085-OA8 is a 8 point AC triac output module in the 2085 expansion family for Micro850 controllers, and the specification rows below are the published values for this catalog number rather than a family average.
| Specification | Value |
|---|---|
| Catalog number | 2085-OA8, 8 point 120/240V AC triac output expansion module |
| Number of outputs | 8 |
| Voltage category | 120V/230V AC |
| Operating voltage range | 120 to 240V AC; output 85V AC minimum, 240V AC maximum |
| Off-state leakage current | 2.5 mA maximum |
| Source | 2080-TD001 Micro800 technical data, discrete AC output expansion I/O specification |
Two and a half milliamps of off-state leakage is what a triac output does, and it is enough to hold a small relay or a neon indicator faintly on. A load below the minimum holding current will glow or buzz, and that is a property of the switching device, not a fault.
Eighty five to two hundred and forty volts AC on one module covers both the North American and the European line voltages, which is why the catalog describes it as a 120/230 volt device rather than a dual voltage one.
The figures on this page are published for this catalog number in the Micro800 technical data, including the isolation and temperature code rows. Where the source gives a range rather than a single value, the range is reproduced instead of a midpoint.
The Type 1 input designation is a real classification, not marketing. IEC Type 1 inputs are the slow, tolerant sensors, and a module published against that standard is the right choice for a limit switch and the wrong one for a registration mark.
Channel update time on a temperature module is measured per enabled channel, not per module. Twelve to five hundred milliseconds per channel means a module with all channels enabled updates slowly, and a control loop that assumes a fast scan will be wrong about when the value arrived.
An expansion module is a separate DIN rail device with its own terminal block, and that changes the wiring effort compared with a plug-in module. The 2085 family is what a Micro850 chassis accepts, up to four of them, and each one carries its own field terminals rather than borrowing the controller row.
Relay and transistor outputs on the same family look interchangeable on a drawing and are not interchangeable on a load. A relay at eight amps per module handles an inrush that a transistor output rated half an amp per point will not survive, and the load type decides which module is ordered.
Two hundred and twenty grams of shipping weight and an open style enclosure are the practical statements about these modules. They are panel mounted inside an enclosure, they are not field mounted, and the enclosure rating is the panel rating rather than the module rating.
Isolation on these modules is fifty volts continuous, reinforced insulation, channel to system, with a type test at seven hundred and fifteen volts DC for sixty seconds. That is a working isolation for a panel with a common reference, not a barrier for a hazardous area, and the two should not be confused.
Analog temperature modules carry an accuracy that depends on the sensor type. A thermocouple input specified within half a degree to three degrees and an RTD input within two tenths to six tenths of a degree are two very different measurement systems sharing one module.
Expansion modules share the controller supply and add to its consumption, so the power budget is cumulative. A controller published at eleven watts with no expansion and thirty three watts with plug-ins and expansion is telling the designer that the difference belongs to the modules that were added.
Forty four and a half millimetres of width is the physical unit of expansion planning. Five modules fit in a fraction of the rail space that five separate controllers would take, and the depth of eighty seven millimetres is what decides whether the panel is deep enough for the terminal cover.
The bus terminator is the part that makes the serial expansion bus electrically correct. It terminates the end of the chain, it is listed in the same technical data as the modules, and a chain without it is a chain that may work on the bench and fail in the panel.
The point count on an expansion module is a bus load as well as a field count. Sixteen discrete inputs draw one hundred and seventy milliamps from the five volt bus and thirty two draw one hundred and ninety, which is the figure the controller power budget has to absorb for every module in the chain.
Derating curves are published for a reason, and they are the part of a data sheet that gets skipped. A sixteen point DC input module with a published curve will carry its full count at one ambient and a reduced count at another, and the cabinet temperature is the variable that decides which.
A green health indicator and no channel indicators is a deliberate diagnostic style on some analog modules. The module tells you it is alive and the channel value tells you the rest, which means the troubleshooting tool is the programming software rather than a lamp.
Check the load against the minimum holding current, because two and a half milliamps of leakage will hold a small load on.
Browse the Allen-Bradley Micro and Nano systems category for the other models, options and spare parts that share this range.