Product Details:
Payment & Shipping Terms:
|
The 1756-RM2 (also written 1756RM2) is the ControlLogix redundancy module that links a chassis pair. It draws 1.16 A at 5.1 V DC and 3.4 mA at 24 V DC, dissipates 6 W maximum (21 BTU/hr), and occupies one slot in any chassis slot.
Two modules of the same catalogue number are required: one in each of the two redundancy chassis. The pair monitors events in both chassis and initiates the system response.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Controller redundancy module |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-RM2 |
Current Draw |
1.16 A @ 5.1 V DC; 3.4 mA @ 24 V DC |
Power Dissipation |
6 W, max |
Thermal Dissipation |
21 BTU/hr |
Slot Width |
1 slot |
Module Location |
Chassis-based, any slot |
Chassis |
1756-A4, A7, A10, A13, A17 |
Controller Families |
ControlLogix 5570, ControlLogix 5580 |
Connector Cables |
1756-RMC1 (1 m), 1756-RMC3 (3 m), 1756-RMC10 (10 m) |
Power Supply, Standard |
1756-PA72, PA75, PB72, PB75 |
Power Supply, Redundant |
1756-PA75R, PB75R, PSCA2 |
Mounting |
Standard ControlLogix chassis, single-slot |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The pairing rule is absolute. Rockwell publishes that a pair of redundancy modules is required to link the redundancy chassis pair and that the modules must have the same catalogue number. Two RM2 modules qualify; one RM2 plus one RM3 does not.
Power is the first thing to check in a retrofit. At 1.16 A on the 5.1 V rail per module, a pair takes 2.32 A before any I/O is counted. That is nearly a quarter of the 10 A available on a 1756-PA72, which is why the redundant supply set for this family is 1756-PA75R, 1756-PB75R and 1756-PSCA2.
The 24 V figure is small but not zero: 3.4 mA at 24 V DC per module. On a chassis where the 24 V rail already carries field devices, this is still counted in the budget.
Cabling is ordered separately. The connector cables are 1756-RMC1 (1 m), 1756-RMC3 (3 m) and 1756-RMC10 (10 m). No cable ships with the module, and cable length is the physical limit on how far the two chassis can stand apart.
The module fits 1756-A4, A7, A10, A13 and A17 chassis in any slot, and is supported by ControlLogix 5570 and 5580 controllers. The standard supplies for the pair are 1756-PA72, PA75, PB72 and PB75.
Service behaviour is the practical argument for this part in brownfield plants. A single chassis can be powered down, worked on and returned while the partner keeps the process running, provided the module pair and the cable are intact.
A redundancy fault is almost always a pairing, fiber or supply problem; the module pair tolerates a failed chassis, not a mismatched cable.
| Indicator | State | Meaning and first action |
| Redundancy module shows a link fault | — | Check the LC connector and the fiber type against the SFP fitted; singlemode and multimode fiber are not interchangeable. |
| Module draws more than expected from the chassis supply | — | 1756-RM2 draws 1.16 A at 5.1 V plus 3.4 mA at 24 V, and 1756-RM3 draws 1 A at 5.1 V plus 5 mA at 1.2 V. |
| Swap of one chassis does not restore redundancy | — | The cable must be re-terminated on the replacement module; a loose LC ferrule reads as a link failure even when the module is healthy. |
Current draw, dissipation, connector and cable data per Rockwell publication 1756-TD001-EN-P and 1756-IN050.
Replace with the same catalogue number; a mixed pair does not achieve redundancy.
Re-terminate the LC connectors on the new module and confirm the fiber type matches the transceiver.
Recheck the 5.1 V budget after the swap, especially where more than one module pair shares a chassis.
What is the 1756-RM2?
A ControlLogix redundancy module that links a pair of redundancy chassis.
What current does it draw?
1.16 A at 5.1 V DC and 3.4 mA at 24 V DC.
How much does it dissipate?
6 W maximum, 21 BTU/hr.
How many modules do I need?
Two, one per chassis, and both with the same catalogue number.
Which cables does it use?
1756-RMC1 (1 m), 1756-RMC3 (3 m) or 1756-RMC10 (10 m), ordered separately.
Which chassis does it fit?
1756-A4, A7, A10, A13 and A17, in any slot.
Which power supplies suit a redundant pair?
1756-PA75R, 1756-PB75R and 1756-PSCA2.
Is there an XT version?
Yes, 1756-RM2XT for 1756-A7XT and 1756-A10XT chassis.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) - redundancy module current draw, dissipation, chassis and cable data for 1756-RM2 and the manufacturer's product page for 1756-RM2. Values re-checked 16 November 2026.