Product Details:
Payment & Shipping Terms:
|
The 1756-BATA (also written 1756BATA) is the replacement battery assembly for the 1756-BATM ControlLogix battery module — Rockwell describes it in exactly those terms: Replacement Battery Assembly For 1756-BATM.
It is a two-part arrangement that catches people out. The module (1756-BATM) is the part that mounts and connects; the battery inside it (1756-BATA) is the consumable. Replacing the battery means ordering the assembly, not the module, once the module is already installed.
Lifecycle is published as End of Life: discontinued 31 December 2027, no planned Rockwell replacement. The module it serves was discontinued earlier, on 18 July 2017, which makes the assembly a support part for an installed base rather than a current design choice.
Published attributes: Series A, UPC 612598284757, function replacement battery backup, temperature rating 0...60 °C (32...140 °F), country of origin Korea (Republic of), one year standard warranty, cutsheet 1756-TD002 and selection guide 1756-SG001.
1756-BA2 | Lithium battery assembly, Series B 1756-L6x only, end of life 2027-12-31, UPC 612598322152 | Limited stock |
1756-BATA | Replacement battery assembly for 1756-BATM, end of life 2027-12-31, UPC 612598284757 | Limited stock |
1756-BATM | Battery module, 20 mA max at 3.6 V DC, discontinued 2017-07-18, UPC 612598284764 | Limited stock |
Application | Controller battery backup |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-BATA |
Communication | — |
Display | — |
Enclosure | — |
Interface | Controller battery connector |
Mounting | Inside controller / module |
Number Of Channels | — |
Standard | CE, UL |
Sub Brand | ControlLogix |
Type | Battery |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN576 (battery module installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
For a plant running a 1756-BATM module, the assembly is the only consumable in the backup chain, so its availability is the practical limit on how long the controller keeps its backup through an outage.
Because both the module and the assembly are discontinued, the useful question is not 'where can I buy one' but 'how many outages will this installed base see before the controllers are replaced'. That quantity is the last buy.
Holding one assembly per rack with a BATM module is cheap relative to the consequence: a controller that loses backup during an extended outage is a restart and a program reload, not a battery change.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Both halves are discontinued | The module ended on 18 July 2017; the assembly ends on 31 December 2027, with no planned replacement for either. Stock position, not catalogue listing, decides delivery. |
| Check 3 | Consumable behaviour | The battery is the wear item. Long outages, high cabinet temperature and long storage all shorten usable life, and the temperature rating of 0...60 °C is an operating limit, not a life guarantee. |
| Check 4 | Origin | Country of origin Korea (Republic of) as published — relevant where a customs document has to state it. |
| Check 5 | Disposal | A lithium assembly. It goes through the battery waste route, not general electronic waste. |
Lifecycle dates and attributes per the Rockwell product record for this catalogue number; battery data per 1756-TD001 / 1756-TD002 and installation instructions 1756-IN576 and 1756-IN050.
No planned Rockwell replacement exists for this assembly, and none for the 1756-BATM module it fits. Migration goes through the controller and its backup arrangement, which is a project decision.
The assembly is not interchangeable with 1756-BA2, which is the Series B 1756-L6x battery — different module, different part.
If the module is still healthy but the assembly is not available, the honest options are a last buy from channel stock or a controller migration; substituting another family's battery is not one of them.
What is the 1756-BATA?
The replacement battery assembly for the 1756-BATM ControlLogix battery module, as titled by Rockwell.
Does it replace the module?
No. It is the battery assembly that fits into the module; the module itself is a separate catalogue number, 1756-BATM.
Is it still available?
Published as End of Life with a discontinued date of 31 December 2027 and no planned replacement. Availability before then depends on channel stock.
What is the temperature rating?
0...60 °C (32...140 °F) as published.
Where is it made?
Country of origin Korea (Republic of), UPC 612598284757.
Can I use 1756-BA2 instead?
No — 1756-BA2 is the Series B 1756-L6x battery assembly. The two serve different modules and are not interchangeable.
What should I hold in spares?
One assembly per rail with a BATM module, sized against the number of outages the installed controllers will still see.
How is it disposed of?
As a lithium battery through the battery waste route; it is not general electronic waste.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-BATA. Values re-checked 15 November 2026.