Product Details:
Payment & Shipping Terms:
|
The 1756-L73 (also written 1756L73) is the 8 MB controller of the ControlLogix 5570 range and the size most 5570 racks are built around: one chassis slot, a 1 GB SD card installed, the 1756-ESMCAP energy storage module in place of a battery, and a four-character display that reports the firmware revision at power-up.
Its published specification is 8 MB of user memory, 0.98 MB of I/O memory, maximums of 128,000 digital, 4,000 analogue and 128,000 total I/O points, 800 mA at 5.1 V DC plus 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr, and 30 V continuous basic isolation from the USB port to the system (1756-TD001). The energy storage module is listed as interchangeable between the standard and conformal-coated (K) versions of the controller.
| 1756-L71 | ControlLogix 5570 controller, 2 MB user memory | IN STOCK |
| 1756-L72 | ControlLogix 5570 controller, 4 MB user memory | IN STOCK |
| 1756-L73 | ControlLogix 5570 controller, 8 MB user memory | IN STOCK |
| 1756-L71S | GuardLogix 5570 safety controller, 2 MB / 1 MB safety | IN STOCK |
| 1756-L72S | GuardLogix 5570 safety controller, 4 MB / 2 MB safety | IN STOCK |
| 1756-L73S | GuardLogix 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SP | GuardLogix 5570 safety partner, pairs with L71S / L72S / L73S | IN STOCK |
| 1756-L73XT | ControlLogix-XT 5570 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L73SXT | GuardLogix-XT 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SPXT | GuardLogix-XT 5570 safety partner, pairs with L73SXT | IN STOCK |
Application |
Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L73 |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-L73 |
Mounting |
Chassis |
Number Of Channels |
1756-L73 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
8 MB is the memory size that carries a whole line without splitting it: station programs, the safety-adjacent interlocks, integrated motion over EtherNet/IP, recipe and product data held in the controller, plus the edit headroom that every commissioning consumes.
Because the electrical figures are unchanged across the 5570 family, an L73 upgrade from an L71 or L72 is a controller swap and a download — the chassis supply, the slot width and the isolation rating stay exactly where they were.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| RUN | Steady green | Controller is in Run mode. |
| FORCE | Off | No tags contain I/O force values, or forces are disabled. |
| FORCE | Steady yellow | I/O forces are enabled. A field wiring check made now is not valid. |
| FORCE | Flashing yellow | Forced addresses exist but forces are not enabled; enabling them applies every stored force at once. |
| OK | Off | No power applied to the controller. |
| OK | Flashing red | New controller that needs a firmware update, or a major fault on a controller in service. |
| OK | Steady red | Power-up diagnostics, ESM discharge at power-down, project transfer to nonvolatile memory, or a controller that is powered but inoperable. |
| OK | Steady green | Controller operating normally. |
| Status display | TEST / PASS | Power-up tests running, then completed. |
| Status display | CHRG | Capacitor energy storage module charging; do not remove the ESM. |
| Status display | BUSY | I/O modules in the project are not yet fully powered. |
| Status display | No Project | Controller memory is empty; download the project or load it from the SD card. |
| Status display | Rev XX.xxx | Firmware major and minor revision currently installed. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
For a 5560 rack, the L73 is the functional replacement at the memory size of an L63, with the 5570 programming path, the SD card and the status display. The I/O modules and the chassis do not change.
Above it the 5580 controllers add embedded Ethernet, CIP Security and packet rates measured in tens of thousands per second; within the 5570 range the L74 and L75 cover 16 MB and 32 MB with the same electrical specification.
What memory does the 1756-L73 have?
8 MB of user memory and 0.98 MB of I/O memory, with maximums of 128,000 digital, 4,000 analogue and 128,000 total I/O points (1756-TD001).
Is the 1756-L73 the same electrically as the L71?
Yes. 800 mA at 5.1 V DC, 5 mA at 1.2 V DC, 2.5 W, 8.5 BTU/hr and 30 V continuous basic isolation from the USB port to the system are printed identically for L71, L72, L73, L74 and L75.
What is the 1756-ESMCAP and why does it ship installed?
It is the removable capacitor energy storage module that replaces the lithium battery in the 5570 controllers; it ships with every standard and conformal-coated 1756-L7 controller. It holds wall-clock time across a power cycle and its charge is shown as CHRG on the status display.
Can the SD card be removed while the controller is running?
Only when no card activity is shown. SAVE, LOAD and UPDT on the status display mean the card is being written or read; the manual requires the save or load to finish before the card is removed or power is disconnected (1756-UM001).
How many tasks and programs can it run?
The 5570 controllers run the Logix task model with a continuous task plus periodic and event tasks, each holding up to 100 programs; the exact count and the instruction execution times are listed in the 5570 controller user manual and the Logix 5000 programming manuals.
What replaces a 1756-L63?
The 1756-L73 is the memory-equivalent move in the 5570 family: 8 MB against 8 MB, one slot, same chassis. What changes is the programming port, the nonvolatile storage and the firmware revision the project is rebuilt at.
Which indicators does it carry?
Four: RUN, FORCE, SD and OK, plus the four-character status display (1756-UM001). A steady red OK during power-up or ESM discharge is normal; a flashing red OK on a used controller is a major fault.
What surrounds it in the cabinet?
Any 1756 chassis slot, one slot wide, 0…60 °C surrounding air, open-style enclosure, with the 800 mA at 5.1 V DC counted against the chassis supply together with every I/O module in the rack.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L73. Values re-checked 16 November 2026.