logo
Home ProductsAB ControlLogix I/O 1756

Allen Bradley PLC 1756-A4 / 1756A4

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1756-A4 / 1756A4

China Allen Bradley PLC 1756-A4 / 1756A4 supplier
Allen Bradley PLC 1756-A4 / 1756A4 supplier Allen Bradley PLC 1756-A4 / 1756A4 supplier Allen Bradley PLC 1756-A4 / 1756A4 supplier Allen Bradley PLC 1756-A4 / 1756A4 supplier Allen Bradley PLC 1756-A4 / 1756A4 supplier Allen Bradley PLC 1756-A4 / 1756A4 supplier

Large Image :  Allen Bradley PLC 1756-A4 / 1756A4

Product Details:

Place of Origin: Made in USA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1756-A4 / 1756A4

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $181.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1756-A4 technical data PDF download 1756-A4 ControlLogix 4 Slot Chassis | Rockwell

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC Automation

The 1756-A4 (also written 1756A4) is the 4-slot ControlLogix chassis: a slot-type backplane with convection cooling whose published minimum enclosure is 50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.). It is the smallest rack in the family and the one used where a design needs a controller, one communication module and two I/O modules — and nothing more.

The chassis is a passive backplane. It carries no power supply and generates no logic; the modules in it are fed from a 1756-PA75, 1756-PB75 or a redundant supply pair installed in the leftmost position and wired to the backplane.

Series matters more on a 4-slot chassis than on a large one, because the slot budget leaves no room for a second rack later. A 1756-A4/B accepts the AC redundant pair (1756-PA75R x2 through a 1756-PSCA2 adapter with two 1756-CPR2 cables); a 1756-A4/C accepts the DC pair. The series is printed on the product label and listed in 1756-IN620.

Published record: UPC 612598129300, active lifecycle, country of origin multiple (depends on manufacturing location), one year standard warranty, drawings available as 2-D PDF, DXF and 3-D STEP, publications 1756-UM001, 1756-IN621, 1756-TD006 and 1756-SG001.

1756-A4
4 slots, minimum enclosure 50.8 x 50.8 x 20.3 cm, UPC 612598129300
In stock
1756-A7
7 slots, minimum enclosure 50.8 x 60.9 x 20.3 cm, UPC 612598129317
In stock
1756-A10
10 slots, minimum enclosure 50.8 x 76.2 x 20.3 cm, UPC 612598129270
In stock
1756-A13
13 slots, minimum enclosure 60.9 x 76.2 x 20.3 cm, UPC 612598129287
In stock
1756-A17
17 slots, minimum enclosure 76.2 x 91.4 x 20.3 cm, UPC 612598129294
In stock

 Application
 Chassis / backplane
 Brand Name
 Rockwell (Rockwell)
 Cat Num
 1756-A4
 Communication
 —
 Display
 —
 Enclosure
 Open chassis, convection cooled
 Interface
 Backplane
 Mounting
 Panel, bracket supplied
 Number Of Channels
 —
 Standard
 CE, UL, cUL
 Sub Brand
 ControlLogix
 Type
 Chassis
 UNSPSC
 —

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (chassis installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1756-A4 chassis view 1 product photograph 1756-A4 chassis view 2 product photograph 1756-A4 chassis view 3 product photograph

Where the module sits in a typical system

The 4-slot chassis suits remote cells: a small press, a packaging head, a skid with a handful of I/O where a 10-slot rack would be mostly air. It also makes a clean communication gateway rack — a controller and two network modules with no I/O at all.

Because the enclosure minimum is square (50.8 x 50.8 cm), the 4-slot rack is the family member that fits a deep but narrow panel. That geometry decision is usually made before the electrical one.

Where a redundancy requirement exists, the 4-slot /B or /C chassis carries the same redundant pair as a 17-slot rack — the redundant supplies are rated 75 W class and the adapter passes up to 15 A at 5.1 V DC, so a small rack simply uses less of that budget.

Commissioning in five steps

  1. Confirm the chassis series against the supply: a /B chassis takes the AC redundant pair, a /C chassis takes the DC pair, and a standard chassis takes one non-redundant supply. The compatibility table in 1756-IN620 is the authority for this.
  2. Mount the chassis on the panel using the bracket the chassis ships with, and leave the convection path open — the published minimum enclosure size is a volume requirement, not a clearance allowance.
  3. Install the power supply, then verify the backplane voltages at the supply terminals before any module is inserted. A wiring error found with an empty chassis costs a fuse; found with a loaded chassis it costs modules.
  4. Insert modules with the chassis de-energised, then check that every module seats flush. A module that stops half way leaves its backplane connector open.
  5. Record the slot assignment on the drawing. ControlLogix allows the controller and communication modules to be placed in the slots the design needs, so the drawing rather than convention is what a later technician will follow.

Diagnostics: status indicators

Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.

 Indicator  State  Meaning and first action
 Check 2  Series letter  Read /B or /C from the label before ordering a redundant supply. A /B chassis with a DC pair, or the reverse, is a build that will not connect.
 Check 3  Four slots is four modules  Count controller, communication and I/O honestly. A 4-slot rack with a controller, two comms and one I/O has no spare slot, and there is no way to extend it except a second chassis.
 Check 4  Enclosure volume  50.8 x 50.8 x 20.3 cm is the minimum enclosure, not the chassis size. Terminal blocks, breakers and cable ducts share that volume with the convection path.
 Check 5  Backplane seating  Modules must seat flush. On a short chassis a single unseated module is a quarter of the rack's capacity.

Slot and supply compatibility per Rockwell publication 1756-IN620 (ControlLogix Redundant Power Supply installation instructions) and 1756-UM001 (ControlLogix system user manual, chassis installation) and 1756-IN050.

Sizing the rack and upgrading the slot count

The step up in the family is 1756-A7, 7 slots, minimum enclosure 50.8 x 60.9 x 20.3 cm — the same height and depth, 10.1 cm wider.

A chassis is not field-expandable: moving from 4 to 7 slots means a new chassis, a re-terminated panel and a new slot drawing. Plan the slot count with the I/O schedule, not with the first release of the program.

Supplies and adapters are shared across the family, so a chassis upgrade keeps the 1756-PA75R pair and the 1756-PSCA2 adapter — only the rack and the cable runs change.

Which ControlLogix EtherNet/IP module to specify

  • 1756-A4 — 4 slots, minimum enclosure 50.8 x 50.8 x 20.3 cm; the smallest enclosure footprint of the family.
  • 1756-A7 — 7 slots, minimum enclosure 50.8 x 60.9 x 20.3 cm; the size most machine-level panels are built around.
  • 1756-A10 — 10 slots, minimum enclosure 50.8 x 76.2 x 20.3 cm.
  • 1756-A13 — 13 slots, minimum enclosure 60.9 x 76.2 x 20.3 cm, 0...60 °C published.
  • 1756-A17 — 17 slots, minimum enclosure 76.2 x 91.4 x 20.3 cm, 0...60 °C published.
  • Series suffix matters — /B chassis take the AC redundant pair (1756-PA75R x2 + 1756-PSCA2 + 1756-CPR2 x2); /C chassis take the DC redundant pair (1756-PB75R x2 + the same adapter and cables).
  • 1756-PA75 / 1756-PB75 — the single supplies used when redundancy is not required; ordered separately from the chassis.

FAQ — 1756-A4 ControlLogix 4 Slot Chassis | Rockwell

What is the 1756-A4?

A 4-slot ControlLogix chassis — a passive backplane, no power supply included, published minimum enclosure 50.8 x 50.8 x 20.3 cm.

Does it come with a power supply?

No. Supplies are ordered separately: 1756-PA75 or 1756-PB75 for a single supply, or a redundant pair with a 1756-PSCA2 adapter on a /B or /C chassis.

How do I know if it takes a redundant supply?

From the series letter on the label: /B takes the AC pair, /C takes the DC pair. 1756-IN620 lists the compatible combinations.

How many modules can I install?

Four, one of which is usually the controller. The power supply occupies the leftmost position and is not a slot.

What enclosure do I need?

At least 50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.) as published, with the convection path left open and space for terminals and wiring.

Is it convection cooled?

Yes — the chassis family is convection cooled, with no fan and no filter to maintain.

What drawings are available?

2-dimensional PDF, DXF and a 3-D STEP model, so the panel layout can be built from the actual model.

What is the UPC?

612598129300. Country of origin depends on manufacturing location and is marked on the packaging.


Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-A4. Values re-checked 15 November 2026.

Related numbers

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)