Product Details:
Payment & Shipping Terms:
|
The 1756-TBSH (also written 1756TBSH) is the spring-clamp block for the 8-channel module family — the analog modules that list TBNH as their screw alternative. One conductor of 0.33…2.1 mm² (22…14 AWG), 105 °C insulation, 1.2 mm maximum strip.
Its published wording is unambiguous: a single wire connection, and no multiple conductors on any terminal.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Removable terminal block for 8-channel modules |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-TBSH |
Type |
Spring clamp terminal block |
Sub Brand |
ControlLogix |
Mounting |
Module front, keyed |
Wire Size, Single |
0.33…2.1 mm² (22…14 AWG) |
Connections Per Terminal |
One, no multiple conductors |
Wire Insulation |
105 °C (221 °F) or greater |
Insulation Strip |
1.2 mm (3/64 in) maximum |
Torque |
Not applicable, spring clamp |
Keying |
User-defined mechanical |
Conformal Version |
1756-TBSHS |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
This block deliberately does not offer the double connection that its screw-clamp twin, the 1756-TBNH, provides. A point that needs a jumper or a shield drain has to be wired as a single conductor here or moved to the TBNH.
The wire range is the same as the TBNH for a single conductor — 0.33…2.1 mm² (22…14 AWG) at 105 °C with 1.2 mm strip — so a schedule can be carried across when a panel changes termination style, as long as no point was doubled up.
Torque does not apply. The 1.36 N·m figure in the module tables belongs to the TBNH screw clamp; on this block the verification is a conductor pull test.
It pairs with the 8-channel analog modules, the same family the TBNH serves. The module row lists both blocks as alternatives, so choosing spring termination does not change the module, the slot or the wiring diagram.
Keying is user-defined mechanical, and the block and module pair is keyed together; a spring block taken from a 16-point module will not be keyed for an analog slot.
The conformal-coated version is 1756-TBSHS, published as single connection only with the same wire range.
A terminal block has no diagnostics of its own; the evidence is wire strip length, conductor count per terminal, the torque figure for this block and the keying pair with the module.
| Indicator | State | Meaning and first action |
| Two wires will not fit | — | Only TBNH accepts a second conductor, and only 0.33…1.3 mm² (22…16 AWG) as a double connection. |
| Spring terminal will not accept a second wire | — | TBSH and TBS6H are published single-connection only; do not wire multiple conductors on any terminal. |
| Fault appears after a module swap | — | RTB keying is user-defined mechanical; a block keyed for another module is not interchangeable. |
| Agency mark questioned on a retrofit | — | The ControlLogix system is certified using only TBCH, TBNH, TBSH and TBS6H; other terminations can need agency approval. |
Wire, torque and connection limits per Rockwell publication 1756-TD002N-EN-E and 1756-IN050.
A conductor that releases under vibration is usually strip length; check the 1.2 mm maximum before replacing the block.
Spring blocks accept one conductor only — a doubled point has to be split or moved to the 1756-TBNH.
Keep the 105 °C insulation grade; a 90 °C wire in a 60 °C ambient panel is close to its limit at the terminal.
What is the 1756-TBSH?
A spring-clamp removable terminal block for ControlLogix 8-channel modules.
What wire size does it accept?
0.33…2.1 mm² (22…14 AWG), single connection only.
Can two conductors share a terminal?
No — the block is published as single connection only.
How does it differ from the 1756-TBNH?
Same module family and same single-wire range; spring clamp instead of screw clamp, and no double connection.
Which modules use it?
8-channel analog modules such as the 1756-OF6CI and 1756-IF8.
Does it need to be torqued?
No — the 1.36 N·m figure applies to the 1756-TBNH screw clamp.
What insulation rating is required?
105 °C (221 °F) or greater, 1.2 mm maximum strip.
Is there a conformal-coated version?
Yes, 1756-TBSHS.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002N (1756 ControlLogix I/O Modules Specifications, November 2021) - removable terminal block rows: wire size, conductor count, torque and keying for 1756-TBSH and the manufacturer's product page for 1756-TBSH. Values re-checked 16 November 2026.