The 1756-TBNH (also written 1756TBNH) is the screw-clamp terminal block with the heaviest published torque and the only double-connection option in the family: one conductor 0.33…2.1 mm² (22…14 AWG), or two conductors at 0.33…1.3 mm² (22…16 AWG), terminated at 1.36 N·m (12 lb·in).
It is the block for 8-channel analog modules, and the one to specify when a point must carry a second conductor — a jumper, a shield drain or a second device on the same signal.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Removable terminal block for 8-channel modules |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-TBNH |
Type |
Screw clamp terminal block |
Sub Brand |
ControlLogix |
Mounting |
Module front, keyed |
Wire Size, Single |
0.33…2.1 mm² (22…14 AWG) |
Wire Size, Double |
0.33…1.3 mm² (22…16 AWG) |
Connections Per Terminal |
One or two, never more than two |
Wire Insulation |
105 °C (221 °F) or greater |
Insulation Strip |
1.2 mm (3/64 in) maximum |
Terminal Torque |
1.36 N·m (12 lb·in) |
Keying |
User-defined mechanical |
Conformal Version |
1756-TBNHS |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The double connection is the reason this block exists in a panel design. Up to two conductors may share a terminal, and the second conductor is limited to 0.33…1.3 mm² (22…16 AWG) — a 14 AWG wire cannot be doubled. The rule is explicit in the module tables: do not wire more than two conductors on any terminal.
Torque is 1.36 N·m (12 lb·in), nearly three times the 0.5 N·m of the TBCH. Where a panel mixes both blocks — common on a chassis with digital and analog modules — two torque settings apply on the same row of terminals, and a single setting used across all of them will either under-tighten the TBNH or distort the TBCH.
Wire grading is 105 °C with 1.2 mm maximum strip, and solid and stranded conductors may not be intermixed in a double connection; both must also be the same size.
Module pairing follows the channel count: 8-channel analog modules such as 1756-OF6CI and 1756-IF8 list TBNH and TBSH, while 16/32-point digital modules and the HART eight-channel output list TBCH and TBS6H. The TBNH is not a general-purpose substitute for the TBCH.
Keying is user-defined mechanical. On an analog module the keying pair distinguishes voltage and current wiring variants only at the module level, so a block moved between two analog slots carries the other slot's keying.
The conformal-coated version is 1756-TBNHS, with the same 1.36 N·m torque, the same double-connection limits, and the added requirement that only same-size wires are used with no intermixing of solid and stranded types.
A terminal block has no diagnostics of its own; the evidence is wire strip length, conductor count per terminal, the torque figure for this block and the keying pair with the module.
| Indicator | State | Meaning and first action |
| Two wires will not fit | — | Only TBNH accepts a second conductor, and only 0.33…1.3 mm² (22…16 AWG) as a double connection. |
| Spring terminal will not accept a second wire | — | TBSH and TBS6H are published single-connection only; do not wire multiple conductors on any terminal. |
| Fault appears after a module swap | — | RTB keying is user-defined mechanical; a block keyed for another module is not interchangeable. |
| Agency mark questioned on a retrofit | — | The ControlLogix system is certified using only TBCH, TBNH, TBSH and TBS6H; other terminations can need agency approval. |
Wire, torque and connection limits per Rockwell publication 1756-TD002N-EN-E and 1756-IN050.
Check the torque before blaming the module: a TBNH under-torqued to the TBCH figure of 0.5 N·m is the classic cause of a drifting analog channel.
If a doubled terminal was used, confirm the second wire is 22…16 AWG; a 14 AWG second conductor is outside the published double-connection range.
Re-key and re-terminate to 1.36 N·m; do not reuse a block that has been over-torqued.
What is the 1756-TBNH?
A screw-clamp removable terminal block for ControlLogix 8-channel modules, with a double-connection option.
What is the terminal torque?
1.36 N·m (12 lb·in).
Can two wires share a terminal?
Yes, up to two conductors, with the second at 0.33…1.3 mm² (22…16 AWG).
What single wire size does it accept?
0.33…2.1 mm² (22…14 AWG).
Can solid and stranded wire be mixed?
No — the two conductors in a double connection must be the same size and type.
Which modules use it?
8-channel analog modules such as the 1756-OF6CI and 1756-IF8.
What insulation rating is required?
105 °C (221 °F) or greater, 1.2 mm maximum strip.
Is there a conformal-coated version?
Yes, 1756-TBNHS, with the same torque and connection limits.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002N (1756 ControlLogix I/O Modules Specifications, November 2021) - removable terminal block rows: wire size, conductor count, torque and keying for 1756-TBNH and the manufacturer's product page for 1756-TBNH. Values re-checked 16 November 2026.