Product Details:
Payment & Shipping Terms:
|
The 1756-PB75 (also written 1756PB75) is the 24 V DC input supply at the top of the standard range: 18…32 V DC in, 75 W out, 13 A at 5.1 V DC and 2.8 A at 24 V DC.
It is the DC counterpart of the PA75, for panels whose control voltage is a battery-backed 24 V bus rather than a mains feed.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Chassis power supply, DC input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-PB75 |
Type |
ControlLogix standard power supply |
Sub Brand |
ControlLogix |
Mounting |
Left end of 1756 chassis |
Input Voltage |
18…32 V DC, nominal 24 V DC |
Input Power |
95 W maximum |
Output Power |
75 W at 0…60 °C |
Current At 5.1 V |
13 A |
Current At 24 V |
2.8 A |
Current At 3.3 V |
4 A |
Current At 1.2 V |
1.5 A |
Inrush Current |
30 A maximum |
Hold-Up |
35 ms at 18 V; 40 ms at 24 V; 40 ms at 32 V |
Isolation |
250 V reinforced, tested 3500 V DC for 60 s |
Chassis |
1756-A4, A7, A10, A13, A17; series B, C |
Wire Size |
2.5 mm² (14 AWG), 90 °C minimum |
Terminal Torque |
0.565 N·m (5 lb·in) |
Weight |
0.95 kg (2.10 lb) |
Dimensions |
14.0 x 11.2 x 14.5 cm |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
A 24 V DC panel has one issue an AC panel does not: the input window is only 18…32 V, and a battery bus moves across that band every day. Float sits near 27 V, end of discharge approaches 21 V, and an equalise charge can push past 28 V. All three are inside the window, but the supply must be checked at the worst of the three, not at the nominal 24 V on the drawing.
The 13 A figure at 5.1 V is what separates the PB75 from the PB72. Analog and communication-heavy chassis draw their backplane current at 5.1 V, and a chassis that is comfortable on 75 W total can still exceed the 10 A rail of the smaller unit.
Hold-up is published in milliseconds for the DC units — 35 ms at 18 V, 40 ms at 24 V, 40 ms at 32 V — because a DC system measures ride-through in time rather than in supply cycles. On a battery bus the supply itself is rarely the limiting element; the battery is.
Inrush is 30 A maximum, and on a shared battery bus with one disconnect feeding several chassis this is the number that sizes the breaker and the busbar, not the 75 W steady-state load.
Isolation is 250 V continuous, reinforced, type tested at 3500 V DC for 60 seconds, which keeps the field DC bus and the backplane reference separate. That is the engineering reason a PB75 is used instead of feeding the chassis from the same 24 V supply that powers field devices.
Mechanically it mounts at the left end of a 1756-A4, A7, A10, A13 or A17 chassis, series B or C only, and takes 2.5 mm² (14 AWG) input wire at 90 °C minimum, torqued to 0.565 N·m.
A power supply carries no diagnostic display of its own; the useful evidence is the input voltage under load, the total chassis wattage and the published hold-up at the site voltage.
| Indicator | State | Meaning and first action |
| Chassis browns out on a load step | Voltage dip | The 75 W output budget is shared by all rails; an added 24 V load can exhaust it before the 5.1 V current limit is reached. |
| Supply restarts on a short | Inrush | Inrush is 20 A on the AC unit and 30 A on the DC unit; confirm the upstream breaker tolerates repeated energisation. |
| Hold-up shorter than expected | — | Hold-up is published in cycles at a stated input and load, not as a fixed millisecond figure. |
Input, output and hold-up figures per Rockwell publication 1756-TD005-EN-E and 1756-IN050.
Measure the DC bus at the supply terminals while the chassis is loaded. A bus that reads 24 V open and 19 V loaded is in the last volt of the window.
Confirm the chassis series. The PB75 does not fit series A, and neither does the PB72.
Check the 5.1 V total before replacing a tripping PB75 with a like-for-like unit; if the 13 A rail is at its limit, the fix is load distribution, not a new supply.
What is the 1756-PB75?
A standard ControlLogix DC power supply, 24 V DC input, 75 W output, 13 A at 5.1 V DC.
What input voltage range does it accept?
18…32 V DC, nominal 24 V DC.
How does it differ from the 1756-PB72?
13 A at 5.1 V instead of 10 A, for the same 75 W total output.
What is the hold-up time?
35 ms at 18 V DC, 40 ms at 24 V DC and 40 ms at 32 V DC.
What is the maximum inrush current?
30 A.
Which chassis series does it fit?
Series B or C, in 1756-A4, A7, A10, A13 and A17 chassis.
What is the isolation rating?
250 V continuous, reinforced, power input to backplane, tested at 3500 V DC for 60 s.
What current is available at 24 V DC?
2.8 A, counted against the same 75 W total.
Data sources. Technical values on this page come from Rockwell publications 1756-TD005 (ControlLogix Power Supplies Specifications) - input, output, hold-up, isolation and environmental data for 1756-PB75; 1756-SG001 (ControlLogix System Selection Guide) - chassis and supply selection and the manufacturer's product page for 1756-PB75. Values re-checked 16 November 2026.