Product Details:
Payment & Shipping Terms:
|
The 1756-OB32 (also written 1756OB32) is the 32-point DC output module: 10...31.2 V DC, 500 mA per channel at 50 °C and 350 mA at 60 °C, 1 A inrush per channel, 16 A maximum per module at 50 °C and 10 A at 60 °C, backplane 300 mA at 5.1 V DC and 2 mA at 24 V DC, isolation 250 V basic outputs-to-backplane, 125 V basic group-to-group (1756-IN062).
Two ceilings apply at once, and they are usually confused. Per channel 500 mA at 50 °C, but the module as a whole caps at 16 A at 50 °C — so 32 channels at 500 mA each, which would be 16 A, fills the module exactly with no headroom, and any real load profile needs the arithmetic done.
The inrush figure, 1 A per channel, is the other limit. A solenoid valve that draws 700 mA continuously and 1.4 A at pick-up is outside the published inrush allowance even though its running current fits.
Group isolation is 125 V between the two groups of sixteen, with none inside a group. That is a shared-return design: two 24 V sources can be used, and each group's sixteen outputs share their return.
1756-IB16 | 16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 | In stock |
1756-IB16D | 16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA | In stock |
1756-IB16I | 16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA | In stock |
1756-IB16IF | 16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA | In stock |
1756-IB16ISOE | 16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA | In stock |
1756-IB32 | 32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 | In stock |
1756-IC16 | 16 inputs, 30...60 V DC, backplane per 1756-IN062 | In stock |
1756-IG16 | 16 TTL inputs, backplane per 1756-IN062 | In stock |
1756-IV16 | 16 inputs, 48 V DC, backplane per 1756-IN062 | In stock |
Application | Discrete output |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-OB32 |
Communication | Backplane (producer/consumer) |
Display | — |
Enclosure | None (open-style) |
Interface | Removable terminal block |
Mounting | Chassis slot |
Number Of Channels | 32 |
Standard | CE, UL, CSA, RCM |
Sub Brand | ControlLogix |
Type | Digital Output Module |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The OB32 is the density choice for panels with a large, mostly uniform 24 V DC output list: dozens of solenoid valves and indicator lamps on one card, with the module total worked out at 50 °C and again at 60 °C.
Because inrush is capped at 1 A per channel, it suits valves and lamps rather than contactors; a contractor with a high pick-up current belongs on a 2 A pilot duty module.
Two groups of sixteen allow a split supply — one group from the machine's 24 V supply, the second from a separate source — inside the 125 V group barrier.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | 10 A at 60 °C | The module ceiling drops by 6 A between 50 and 60 °C. |
| Check 3 | 1 A inrush per channel | Running current can fit while inrush does not. Check the coil's pick-up current. |
| Check 4 | 125 V group-to-group | Two groups of sixteen with shared returns inside each group. |
| Check 5 | 300 mA backplane | Nearly double a 16-point card's draw on the 5.1 V rail for twice the channels — still the better density. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
For 2 A per point with 250 V reinforced isolation, 1756-OB16I halves the channel count.
For 16 points at 1 A with 2 A inrush, 1756-OB16E is the standard 16-channel card.
For diagnostic outputs, 1756-OB16D publishes per-point load monitoring.
What is the 1756-OB32?
A 32-point DC output module, 10...31.2 V DC, 500 mA per channel at 50 °C and 350 mA at 60 °C.
What is the module maximum current?
16 A at 50 °C and 10 A at 60 °C.
What is the inrush rating?
1 A per channel.
How is it isolated?
250 V continuous basic outputs-to-backplane and 125 V basic between the two groups of sixteen.
How much backplane current does it draw?
300 mA at 5.1 V DC and 2 mA at 24 V DC.
Can all 32 channels run at 500 mA?
Only if the module total allows it: 32 x 500 mA is exactly the 16 A rating at 50 °C, with no margin.
What is the temperature code?
T4A, with 60 °C maximum surrounding air.
Which document publishes these figures?
1756-IN062, the ControlLogix DC digital I/O installation instructions.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-OB32. Values re-checked 15 November 2026.