logo
Home ProductsAB ControlLogix I/O 1756

Allen Bradley PLC 1756-DMD30 / 1756DMD30

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1756-DMD30 / 1756DMD30

China Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier
Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier Allen Bradley PLC 1756-DMD30 / 1756DMD30 supplier

Large Image :  Allen Bradley PLC 1756-DMD30 / 1756DMD30

Product Details:

Place of Origin: Made in USA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1756-DMD30 / 1756DMD30

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $3429.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

1756-DMD30 technical data PDF download 1756-DMD30 / 1756DMD30 ControlLogix Drive Module (SD3000)

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC Automation

The 1756-DMD30 (also written 1756DMD30) is the ControlLogix drive module for the SD3000 one-axis drive system. It mounts in a ControlLogix chassis and connects to an individual Power Module Interface (PMI) chassis and to SynchLink devices over fibre optic cable.

Rockwell's installation instructions publish the numbers that decide whether the module fits the panel: 1.35 A at 5.1 V DC and 3.0 mA at 24 V DC from the backplane, 6.96 W maximum power dissipation and 23.7 BTU/hr thermal, an operating range of 0…60 °C, and two different fibre links that are easy to confuse — drive comm at 62.5/125 µm glass, 820 nm, 10 Mbps, and SynchLink at 200/230 µm hard-clad silica, 650 nm, 5 Mbps, each capped at 300 m with no more than one splice or adapter.

1756-DMD30
Drive module, SD3000 system, 1.35 A at 5.1 V DC
In stock
1756-DMF30
Drive module, SF3000 system, 1.35 A at 5.1 V DC
In stock
1756-DMCF003
Drive comm fibre cable, 3 m, pre-configured
In stock
1756-DMAF
Adapter for existing UDC/PMI fibre cables
In stock
1756-SYNCH
SynchLink module, the fibre network companion
In stock

 Application
 Drive control and synchronisation (SD3000)
 Brand Name
 Rockwell (Rockwell)
 Cat Num
 1756-DMD30
 Type
 Drive module
 Sub Brand
 ControlLogix
 Mounting
 1756 ControlLogix chassis
 Interface
 Fibre, drive comm and SynchLink
 Backplane Current
 1.35 A at 5.1 V DC, 3.0 mA at 24 V DC
 Power Dissipation
 6.96 W maximum, 23.7 BTU/hr thermal
 Operating Temperature
 0…60 °C (32…140 °F)
 Storage Temperature
 -40…85 °C (-40…185 °F)
 Relative Humidity
 5…95% non-condensing
 Shock
 30 g operating, 50 g non-operating (11 ms)
 Vibration
 2 g at 10…500 Hz, IEC 68-2-6
 Certification
 UL Listed, SF Certified, Class I Div 2, FM, CE, N223
 SynchLink Link
 200/230 µm HCS, 650 nm, 5 Mbps, 300 m max
 Drive Comm Link
 62.5/125 µm glass, 820 nm, 10 Mbps, 300 m max
 UNSPSC
 32151705

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1756-DMD30 drive module product photograph 1756-DMD30, second view product photograph 1756-DMD30, third view product photograph

Where the drive module sits in a typical system

A DC drive system is not remote I/O. The SD3000 loop needs its control and synchronisation data at drive rates, and the 1756-DMD30 puts that interface in the controller's own chassis, with the power stage living in the PMI chassis and the link carried on fibre.

That is why the module has almost no field wiring of its own. What arrives is two fibre pairs and the backplane; what leaves is the synchronisation stream. Commissioning effort therefore sits in cable type, cable length, node count and drive-system identity, not in terminal torque.

The two-link split is the part worth memorising. Drive comm carries PMI traffic at 820 nm infrared; SynchLink carries time synchronisation at 650 nm red. A star topology allows 256 SynchLink nodes while a daisy chain allows 10, and the drive comm link serves exactly one PMI chassis.

Commissioning in five checks

  1. Budget the backplane before the slot is chosen: 1.35 A at 5.1 V DC and 3.0 mA at 24 V DC per module, 6.96 W maximum dissipation, added to every other module in the chassis.
  2. Mount the chassis in a suitable enclosure; the equipment is rated Pollution Degree 2, overvoltage Category II, 2000 m altitude, with an operating range of 0…60 °C.
  3. Separate the two fibre runs by type. Drive comm is 62.5/125 µm glass at 820 nm and 10 Mbps; SynchLink is 200/230 µm hard-clad silica at 650 nm and 5 Mbps. They are not the same cable.
  4. Respect the published limits: 300 m maximum on either link with no more than one splice or adapter, 1 m minimum, 10 nodes in a daisy chain or 256 in a star on SynchLink, one PMI chassis on drive comm.
  5. Treat insertion under power as live work. RIUP is supported, and the instructions still warn that an arc can send an erroneous signal to field devices.

Indicators, limits and the two fibre links

The module carries the OK LED plus six indicators per interface panel, and every row below is quoted from the drive module installation instructions.

 Indicator  State  Meaning and first action
 OK  Flashing green  Inhibited I/O connection; no action.
 OK  Red  Non-recoverable fault; remove the module from service.
 OK  Off  Module is powered down.
 DRIVE FAULT  Red  Module is faulted; read the fault status parameters.
 LINK SYNC  Flashing red  Two CST time masters detected; leave exactly one on the SynchLink.
 OS OK  Off  Checksum failure; reflash the module.
 DRIVE COMM OK  Off  DPS communication is inactive or unsynchronised; verify the cable connections.
 LINK COMM  Off  Configured but not receiving valid SynchLink data; verify cabling, or enable the module transmitter.
 Interface panel  SD3000  The module carries an SD3000 interface label; the drive system behind the PMI chassis must match it.

Power, fibre, environmental, certification and indicator figures per Rockwell publication 1756-IN577-EN-P and 1756-IN050.

Replacing a drive module inside an installed chassis

There is no catalogue successor: the SD3000 system is the constraint, so a failed module is a drive-system problem answered with a tested spare from the installed base.

Where the drive system itself is being replaced, a PowerFlex drive with an EtherNet/IP interface removes the drive module and the SynchLink network from the chassis, which changes the power budget, the fibre drawing and the controller's I/O configuration together.

Never substitute the 1756-DMF30 for a DMD30. The published electrical specification is identical, but the module belongs to the SF3000 system and will not synchronise an SD3000 drive.

Which drive module to specify

  • 1756-DMD30 — the one-axis drive module for the SD3000 drive system, fibre-linked to the PMI chassis and SynchLink.
  • 1756-DMF30 — the same module for the SF3000 drive system; electrically identical, functionally not interchangeable.
  • 1756-DMCF001 / 003 / 010 / 030 — pre-configured drive comm cables at 1, 3, 10 and 30 m.
  • 1756-DMAF — the adapter for existing UDC/PMI fibre cables.
  • 1403-CF0xx — pre-configured SynchLink cables, 1 m to 250 m.

FAQ — 1756-DMD30 / 1756DMD30 ControlLogix Drive Module (SD3000)

What is the 1756-DMD30?

The ControlLogix drive module for the SD3000 one-axis drive system, fibre-linked to the PMI chassis and SynchLink.

What backplane load does it add?

1.35 A at 5.1 V DC and 3.0 mA at 24 V DC, with 6.96 W maximum power dissipation and 23.7 BTU/hr thermal dissipation.

What fibre does the drive comm link use?

62.5/125 µm glass at 820 nm infrared, 10 Mbps, SC and ST breakout pairs, 1 m minimum and 300 m maximum.

What fibre does SynchLink use?

200/230 µm hard-clad silica at 650 nm red, 5 Mbps, 10 nodes in a daisy chain or 256 in a star.

What are the temperature limits?

0…60 °C operating and -40…85 °C storage, at 5…95% relative humidity non-condensing.

Which certifications are marked?

UL Listed Industrial Control Equipment, SF Certified Process Control Equipment, Class I Division 2 Groups A, B, C, D (certified and FM approved), CE and N223.

How do I know the module passed self-test?

At power-up the OK indicator turns red for five seconds, then flashing green if the self-test passed.

Does it support removal under power?

Yes, RIUP is supported — but an arc can send an erroneous signal to field devices, so the drive must be in a safe state.


Data sources. Technical values on this page come from Rockwell publications 1756-IN577 (ControlLogix Drive Module, catalog numbers 1756-DMD30 and 1756-DMF30, installation instructions) and the manufacturer's product page for 1756-DMD30. Values re-checked 16 November 2026.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)