Product Details:
Payment & Shipping Terms:
|
The 1756-HSC (also written 1756HSC) is the ControlLogix high-speed counter: two counters, three inputs per counter (A, B and Z for gate or reset), four outputs in two groups, and 1 MHz counting on the A input.
Published figures are 300 mA at 5.1 V DC and 3 mA at 24 V DC from the backplane, 1.6 W total backplane power, 5.6 W maximum dissipation and 19.1 BTU/hr on series A and B, 3.5 W and 12 BTU/hr on series C and D. Isolation is 125 V continuous basic (input group to backplane) and 30 V basic (group to group) on series A/B, 250 V and 125 V on series C/D. Inputs accept 4.5…5.5 V DC at 5 V operation or 10…26.4 V DC at 12/24 V operation, with 4 mA minimum and 15 mA nominal on-state current, on the 1756-TBCH terminal block for series A/B and 1756-TBS6H for series C/D (1756-TD002N).
1756-HSC/A, 1756-HSC/B |
2 counters, 4 outputs, 300 mA at 5.1 V DC, 5.6 W, 1756-TBCH |
In stock |
1756-HSC/C, 1756-HSC/D |
2 counters, 4 outputs, 300 mA at 5.1 V DC, 3.5 W, 1756-TBS6H |
In stock |
1756-CFM/A |
Flowmeter module, 2 channels, 300 mA at 5.1 V DC, 6 W |
In stock |
1756-CFM/B |
Flowmeter module, 2 channels, 300 mA at 5.1 V DC, 3.12 W |
In stock |
1756-TBCH |
16-point removable terminal block, HSC series A/B |
In stock |
1756-TBS6H |
Spring-clamp terminal block, HSC series C/D |
In stock |
Application |
High-speed counter |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-HSC |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-HSC |
Mounting |
Chassis |
Number Of Channels |
1756-HSC |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The HSC is bought for one of three jobs: totalising a fast pulse train, measuring rate for a speed loop, or reading a quadrature encoder for position. Each has its own frequency ceiling and its own use of the A, B and Z inputs, which is why the same module appears in very different applications.
On a packaging line it usually counts product or reads the line encoder; in a converting section it measures rate; on a test stand it captures a burst of pulses far faster than the I/O scan could sample. The common thread is that the count has to be accurate at pulse rates the standard digital input modules cannot follow.
The four outputs let the module act on its own count without waiting for the controller scan, which is the practical reason to use an HSC rather than a fast digital input and a software counter.
A counter or flowmeter module has no indicator that explains a bad reading; its limits are the numbers that decide whether the pulse train can be captured at all. Every row below is quoted from the module specification 1756-TD002N.
| Indicator | State | Meaning and first action |
| Inputs per counter | 3 (A, B, Z) | A and B for pulse or quadrature, Z for gate or reset depending on the mode. |
| Outputs | 4 (2 points per group) | Current-sourcing outputs, grouped in pairs; group-to-group isolation is published separately from group-to-backplane. |
| Maximum input frequency | 1 MHz counter mode, 500 kHz rate mode, 250 kHz encoder mode | The frequency ceiling depends on the mode selected; 70 Hz applies when the input filter is enabled. |
| Count range | 0…16,777,214 | 24-bit range per counter. |
| Input threshold | 5 V: 4.5…5.5 V DC; 12/24 V: 10…26.4 V DC | Minimum on-state current 4 mA, nominal 15 mA. |
| Backplane current | 300 mA at 5.1 V DC, 3 mA at 24 V DC | Total backplane power 1.6 W. |
| Dissipation | 5.6 W (A/B), 3.5 W (C/D) | 19.1 BTU/hr against 12 BTU/hr; both add to the enclosure thermal load. |
| Terminal block | 1756-TBCH (A/B), 1756-TBS6H (C/D) | The series also changes the isolation rating, so the block and the rating are one decision. |
Inputs, frequency limits, current draw, dissipation and isolation per Rockwell publication 1756-TD002N-EN-E (1756 ControlLogix I/O Modules Specifications) and 1756-IN050.
Series matters more than catalogue number here. A 1756-HSC/A or /B uses the 1756-TBCH terminal block and publishes 125 V group-to-backplane isolation; a /C or /D uses the 1756-TBS6H and publishes 250 V. Replacing one series with the other changes both the wiring hardware and the isolation rating of the circuit.
Where the pulse rate is slow enough for a standard input, the 1756-IB16ISOE or a DC input module with a software counter removes the cost of the HSC slot; where the count is flow rather than pulses, the 1756-CFM is the correct module and the HSC is the wrong one.
How many counters does the 1756-HSC have?
Two counters with three inputs each (A, B, Z for gate or reset) and four outputs in two groups (1756-TD002N).
What is the maximum input frequency?
1 MHz in counter mode on the A input, 500 kHz in rate measurement mode, 250 kHz in encoder mode with A/B inputs, and 70 Hz with the input filter enabled.
What is the count range?
0…16,777,214, a 24-bit range.
What input voltages are accepted?
4.5…5.5 V DC at 5 V operation and 10…26.4 V DC at 12/24 V operation, with 4 mA minimum and 15 mA nominal on-state current.
How much backplane current does it draw?
300 mA at 5.1 V DC and 3 mA at 24 V DC, 1.6 W total backplane power.
What is the dissipation and what terminal block is used?
5.6 W and 19.1 BTU/hr on series A/B with the 1756-TBCH; 3.5 W and 12 BTU/hr on series C/D with the 1756-TBS6H.
What isolation is published?
125 V continuous basic input group to backplane and 30 V group to group on series A/B; 250 V and 125 V respectively on series C/D.
Is it a substitute for a flowmeter module?
No. The HSC counts pulses; the 1756-CFM adds gate inputs and current outputs for proving and totalising flow.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002 (1756 ControlLogix I/O Modules Specifications) and the manufacturer's product page for 1756-HSC. Values re-checked 16 November 2026.