Product Details:
Payment & Shipping Terms:
|
The 1756-EN2TR (also written 1756EN2TR) is the dual-port EtherNet/IP communication module for the ControlLogix 1756 platform: two copper RJ45 ports rated Category 5E at 10/100 Mbps, chassis mounted, one slot wide. The second port is what separates it from the 1756-EN2T — both ports can carry a device-level ring (DLR) or a linear daisy chain, so the module itself is the point where the ring recovers.
Connection capacity is identical to the 1756-EN2T, so the EN2T/EN2TR choice is a topology decision, not a throughput decision: 128 TCP/IP connections, 256 CIP connections and 128 + 128 CIP unconnected messages (1756-TD003 Table 1). The second port costs 0.2 A — 1.2 A at 5.1 V DC, 6.12 W, 20.9 BTU/hr (Table 4) against 1 A on the single-port module — so the slot's 5.1 V budget is reopened on any swap. Firmware 2.x needs Studio 5000 / RSLogix 5000 17.01.02 or later and RSLinx 2.55 or later; from firmware 5.x the packet rate rises to 25,000 packets/s and up to eight integrated-motion axes are supported (Table 3).
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application | EtherNet/IP |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-EN2TR |
Communication | EtherNet/IP |
Display | Digital |
Enclosure | None (open-style) |
Interface | 2 Copper RJ45 (10/100 Mbps, Category 5E) |
Mounting | Chassis |
Number Of Channels | 2 |
Standard | CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand | ControlLogix |
Type | Communication Module |
UNSPSC | 32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module sits in one of two places. In a ring it is the controller-side node of a DLR loop that also holds the drives, remote I/O adapters and managed switches — port 1 goes to the upstream neighbour, port 2 to the downstream one, and the ring heals inside the module when a single cable or device is lost. In a star it is simply the uplink for the chassis, one port to the plant switch and the second port left free for a local service laptop or a passive tap.
Because it bridges the 1756 backplane, everything in the chassis — ControlNet, DeviceNet, DH+/RIO, serial, analogue and motion modules — becomes reachable over the same Ethernet drop, and the module routes messages between networks instead of a second bridge. The 128 CIP connections are shared between explicit and implicit use, so connection counting is per target device, not per port.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test or firmware update in progress; wait for the solid state. |
| OK | Off | No chassis power at the slot, or the module has failed its self-test; check the supply and reseat. |
| NET | Green solid | CIP connections established to at least one device. |
| NET | Flashing green | IP address present, no CIP connection — check the connection entry and the message path in Studio 5000. |
| NET | Off | No IP address; the module is not on the network yet. |
| LINK 1 / LINK 2 | Green solid | Port linked and running at 10 or 100 Mbps. |
| LINK 1 / LINK 2 | Off | No link on that port: cable, connector or partner port. |
Indicator behaviour per Rockwell publication 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and 1756-IN050.
The 1756-ENBT was discontinued by Rockwell on 1 November 2021 and the published replacement is the 1756-EN2T. The EN2TR is the right substitute when the failed node was part of a ring, because the ENBT had a single port and the ring had to be closed elsewhere.
The swap is mechanical and electrical, not programmatic: same slot, same chassis, and the 128 CIP connections of the EN2T replacement exceed the 64 of the ENBT, so an existing program keeps working. Recalculate the 5.1 V budget first — the ENBT draws 700 mA, the EN2TR 1.2 A, 500 mA more per substituted slot. Then confirm the ring: if the old node was closed by an external switch, the second port takes over and the switch can go.
How does the 1756-EN2TR differ from the 1756-EN2T?
Only in the ports and topology. Both carry 128 TCP/IP connections, 256 CIP connections and 128 + 128 CIP unconnected messages (1756-TD003 Table 1). The EN2TR adds a second RJ45 port rated Category 5E and can act as a device-level ring node or ring supervisor; the EN2T has one Category 5 port and needs an external switch to close a ring.
What is required to run a device-level ring on this module?
Both ports are in the ring, one module in the loop is configured as ring supervisor in Studio 5000, and every node supports DLR. Cable on both ports must meet Category 5E as listed in Table 4, each segment stays inside the 100 m channel limit, and a single break is healed without dropping the connections that pass through it.
Which cable category and connector does the module need?
Two RJ45 ports, Category 5E shielded or unshielded twisted pair, 802.3 compliant (Table 4). Category 5E is the published rating for the dual-port module — Category 5 is listed for the single-port 1756-EN2T — so a ring built on older Cat 5 patch leads is outside the specification even when the link negotiates at 100 Mbps.
Can the module be removed or inserted with power on?
Yes. The 1756 platform supports removal and insertion under power, and the module is one slot with no wiring other than the RJ45 plugs.
What are the environmental limits and certifications?
Operating 0…60 °C in a Series C chassis, 0…50 °C in a Series B chassis; storage -40…85 °C; 5…95% RH non-condensing; 2 g vibration at 10…500 Hz; 30 g operating shock; CISPR 11 Class A emissions; ESD 6 kV contact and 8 kV air; EFT ±3 kV at 5 kHz and surge ±2 kV line-earth on the Ethernet ports; temperature code T4; open-style enclosure (Tables 4 and 5). Certifications: c-UL-us UL E65584 and Class I Division 2 UL E194810, CE to 2014/30/EU, RCM, ATEX 2014/34/EU II 3 G Ex ec IIC T4 Gc under UL 22 ATEX 2818X, UKEX UL22UKEX2604X, UKCA, FM Class I Division 2, IECEx UL 22.0063X, KC, ODVA conformance, CCC 2020122309111998 (Table 6).
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-EN2TR. Values re-checked 15 November 2026.
How much current does the 1756-EN2TR draw from the backplane?
1.2 A at 5.1 V DC and 3 mA at 24 V DC, dissipating 6.12 W and 20.9 BTU/hr, with 30 V continuous basic isolation type tested at 860 V AC for 60 s (1756-TD003 Table 4).
Which firmware and software versions does the 1756-EN2TR need?
Firmware 2.x needs RSLogix 5000 17.01.02 with RSLinx 2.55 and runs at 10,000 packets/s. Firmware 5.x needs 18.02.00 with RSLinx 2.56, runs at 25,000 packets/s and supports up to eight integrated-motion axes (Table 3).
Which chassis and power supplies are approved for it?
Any slot of 1756-A4, A7, A10, A13 or A17 with the PA72, PA75, PB72, PB75, PC75 or PH75 supply, or the redundant PA75R, PB75R and PSCA2 pairing (Table 4).
Which certifications does the 1756-EN2TR carry?
c-UL-us UL E65584 and Class I Division 2 UL E194810, CE to 2014/30/EU, RCM, ATEX II 3 G Ex ec IIC T4 Gc under UL 22 ATEX 2818X, UKEX UL22UKEX2604X, UKCA, FM Class I Division 2, IECEx UL 22.0063X, KC, ODVA conformance, Morocco and CCC 2020122309111998. CSA is not listed against this module in Table 6.