Product Details:
Payment & Shipping Terms:
|
The 1756-L72S / 1756L72S is the GuardLogix 5570 safety controller built on the 5570 hardware: 4 MB of standard user memory with a separate 2 MB safety memory, one chassis slot, the 1 GB SD card in the slot, and the paired safety partner that turns a standard controller into a SIL 3 / PLe pair.
Published figures for the GuardLogix 5570 controllers are 0.98 MB I/O memory, 128,000 digital I/O maximum, 1756-ESMCAP energy storage module shipped installed, 800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr, 30 V continuous basic isolation from the USB port to the system, and a shipping weight of 0.25 kg (0.55 lb) (1756-TD001). The safety partner uses its own energy storage module — 1756-SPESMNSE or 1756-SPESMNRM — which is a separate line on the same specification table.
| 1756-L71 | ControlLogix 5570 controller, 2 MB user memory | IN STOCK |
| 1756-L72 | ControlLogix 5570 controller, 4 MB user memory | IN STOCK |
| 1756-L73 | ControlLogix 5570 controller, 8 MB user memory | IN STOCK |
| 1756-L71S | GuardLogix 5570 safety controller, 2 MB / 1 MB safety | IN STOCK |
| 1756-L72S | GuardLogix 5570 safety controller, 4 MB / 2 MB safety | IN STOCK |
| 1756-L73S | GuardLogix 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SP | GuardLogix 5570 safety partner, pairs with L71S / L72S / L73S | IN STOCK |
| 1756-L73XT | ControlLogix-XT 5570 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L73SXT | GuardLogix-XT 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SPXT | GuardLogix-XT 5570 safety partner, pairs with L73SXT | IN STOCK |
Application |
Safety Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L72S |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-L72S |
Mounting |
Chassis |
Number Of Channels |
1756-L72S |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
2 MB of safety memory covers a multi-zone line where the safety logic is distributed across cells rather than concentrated in one interlock block. The standard side of the controller carries the line program, the HMI faceplates and the recipe data.
The pairing rule does not change with memory: controller plus 1756-L7SP, safety I/O on the same network, and a safety signature that is re-generated whenever the safety task is edited.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| RUN | Steady green | Controller is in Run mode. |
| FORCE | Off | No tags contain I/O force values, or forces are disabled. |
| FORCE | Steady yellow | I/O forces are enabled. A field wiring check made now is not valid. |
| FORCE | Flashing yellow | Forced addresses exist but forces are not enabled; enabling them applies every stored force at once. |
| OK | Off | No power applied to the controller. |
| OK | Flashing red | New controller that needs a firmware update, or a major fault on a controller in service. |
| OK | Steady red | Power-up diagnostics, ESM discharge at power-down, project transfer to nonvolatile memory, or a controller that is powered but inoperable. |
| OK | Steady green | Controller operating normally. |
| Status display | TEST / PASS | Power-up tests running, then completed. |
| Status display | CHRG | Capacitor energy storage module charging; do not remove the ESM. |
| Status display | BUSY | I/O modules in the project are not yet fully powered. |
| Status display | No Project | Controller memory is empty; download the project or load it from the SD card. |
| Status display | Rev XX.xxx | Firmware major and minor revision currently installed. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
Moving a 5560 GuardLogix rack to this controller keeps the chassis and the safety I/O and replaces the controller pair; the functional replacement path is the 5570 controller plus L7SP.
Within the range the step up is the 1756-L73S at 8 MB / 4 MB, with the same partner, the same energy storage modules and the same electrical figures.
How is the 1756-L72S memory split?
4 MB of standard memory and 2 MB of safety memory, with 0.98 MB of I/O memory and a 128,000 digital I/O maximum (1756-TD001).
Which partner pairs with it?
1756-L7SP, in its own chassis slot, with its own 1756-SPESMNSE or SPESMNRM energy storage module.
Does the safety memory change the scan?
The safety task runs at its own configured rate inside the controller; the published specification gives memory and current draw, not instruction times, so safety reaction time is measured in the project.
What is the current draw?
800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr — identical across the GuardLogix 5570 range, so a memory upgrade inside the family does not change the chassis supply calculation.
Can the same SD card be used in both controller and partner?
Each device has its own card slot and its own project image; the pair is restored together, in the order the manual gives.
What isolation does the USB port provide?
30 V continuous, basic insulation, USB port to system, tested to IEC/UL 61010-1. The port is for temporary programming, not a permanent connection.
Is 2 MB of safety memory enough for a line?
It is the middle size of the range: 1 MB in the L71S, 2 MB here, 4 MB in the L73S. The safety program is usually small compared with the standard program, so 2 MB is the common choice for a multi-zone line.
What is the shipping weight?
0.25 kg (0.55 lb) per controller, as printed for the GuardLogix 5570 table (1756-TD001).
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L72S. Values re-checked 16 November 2026.