logo
Home ProductsAB ControlLogix I/O 1756

Allen Bradley PLC 1756-OF8 / 1756OF8

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1756-OF8 / 1756OF8

China Allen Bradley PLC 1756-OF8 / 1756OF8 supplier
Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier Allen Bradley PLC 1756-OF8 / 1756OF8 supplier

Large Image :  Allen Bradley PLC 1756-OF8 / 1756OF8

Product Details:

Place of Origin: Made in USA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1756-OF8 / 1756OF8

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $1088.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1756-OF8 technical data PDF download 1756-OF8 / 1756OF8 ControlLogix 8-Channel Analog Output

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC Automation

The 1756-OF8 (also written 1756OF8) is the 8-channel ControlLogix analog output module: eight voltage or current outputs, 15-bit across 10.5 V (320 µV/bit) in voltage mode and 16-bit across 21 mA (325 nA/bit) in current mode.

Like the 4-channel module it replaced in most new builds, it exists in two hardware series with different backplane demand: series A at 150 mA / 210 mA (5.1 V / 24 V) and series B at 200 mA / 300 mA.

1756-EN2F CLX HI CAP EIP MOD - FBR IN STOCK
1756-EN2T ControlLogix Hi Capacity ENET/IP IN STOCK
1756-EN2TR 2-PORT CLX HI-CAP ENET/IP MODULE - TP IN STOCK
1756-EN2TRXT CLX ENET/IP Module - 2TP -X Envt IN STOCK
1756-EN2TSC EtherNet/IP Hi Prof Sngl Port VPN Bridge IN STOCK
1756-EN2TXT CLX ENET/IP MODULE - TP, X-ENVT IN STOCK
1756-EN3TR ControlLogix Ethernet Motion Module IN STOCK
1756-ENBT ControlLogix Communication Module IN STOCK
1756-EWEB ControlLogix Web Server Module IN STOCK
1756-EXT ControlLogix Backplane Extender IN STOCK
1756-HIST1G Historian ME 1 Gig in ControlLogix Rack IN STOCK
1756-HIST2G Historian ME 2 Gig in ControlLogix Rack IN STOCK
1756-HSC ControlLogix High-Speed Counter Module IN STOCK
1756-HYD02 ControlLogix Analog Combination Module IN STOCK

 Application
 Analog output module
 Brand Name
 Rockwell (Rockwell)
 Cat Num
 1756-OF8
 Outputs
 8 voltage or current
 Output Range
 ±10 V DC; 0…20 mA
 Resolution
 15 bits across 10.5 V = 320 µV/bit; 16 bits across 21 mA = 325 nA/bit
 Backplane Current, Series A
 150 mA @ 5.1 V; 210 mA @ 24 V
 Backplane Current, Series B
 200 mA @ 5.1 V; 300 mA @ 24 V
 Backplane Power
 5.8 W (series A); 8.22 W (series B)
 Power Dissipation
 5.8 W at 0…750 Ω (series A); 8.22…2 W (series B)
 Thermal Dissipation
 16.78 BTU/hr (series A); 28.03 BTU/hr (series B)
 Isolation
 None between channels (single-ended)
 Drive Capability
 Current 0…750 Ω; voltage mode load dependent
 Open Circuit Detection
 Current mode only, output above 0.1 mA
 Terminal Block
 1756-TBNH or 1756-TBSH, 20-position
 Slot Width
 1

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1756-OF8 analog output module product photograph 1756-OF8, second view product photograph 1756-OF8, third view product photograph

Where the module sits on an analog loop

The series difference is material at this channel count. Series A total backplane power is 5.8 W with 16.78 BTU/hr dissipation; series B is 8.22 W with 28.03 BTU/hr. Two series B modules in one chassis can consume more than a 10 A supply allows once the controller and communications are counted.

There is no isolation between channels. Eight loops share a reference, so a grounded transmitter or a grounded shield on one loop shows up as an offset on the others. Where loop-to-loop separation is required, the 1756-OF8I (eight isolated channels, 16-bit, any voltage or current mix) or the OF8H (eight outputs with a HART modem) are the correct parts.

Open circuit detection is restricted to current mode and needs the output above 0.1 mA. This matters at commissioning: a channel parked at 0 mA reports nothing when the loop opens, and the fault surfaces only when the process is started.

Power dissipation is load-dependent: the published figures are 5.8 W for series A at 0…750 Ω, and 8.22 W falling to 2 W across the same load range for series B. A panel with eight 500 Ω loops runs hotter than the headline number suggests.

Field wiring is a 20-position removable terminal block, 1756-TBNH or 1756-TBSH, ordered separately. RTB keying is user defined, so a block taken from a 16-point digital module does not key correctly here.

Slot width is one, and the module can go in any slot of a standard ControlLogix chassis, which makes it the usual choice when a project outgrows the 4-channel module without wanting to add a second chassis.

Commissioning in five checks

  1. Confirm the series before ordering; A and B differ by 50 mA at 5.1 V and 90 mA at 24 V, which changes the chassis budget.
  2. Do not expect channel separation. This module has no isolation between channels, so grounded transducers must be handled at the field side.
  3. Use a 20-position RTB, 1756-TBNH or TBSH, ordered separately.
  4. Size the load against drive capability; the dissipation figures assume 0…750 Ω.
  5. Rely on open circuit detection only in current mode and only above 0.1 mA.

Loop faults and what the module reports

This module reports module health and calibration state only. There is no isolation between channels, so a grounded component on one loop appears as an offset on the others.

 Indicator  State  Meaning and first action
 Output drifts when one channel is loaded  —  This module has no isolation between channels; the channels share a reference and a common return.
 Output cannot reach the top of the range  —  Drive capability is finite: the load resistance decides the achievable current, and the published power figures assume a 0…750 Ω load.
 New module draws more than the old one  —  Series A and B differ: 150 mA versus 200 mA at 5.1 V and 210 mA versus 300 mA at 24 V.

Backplane current, dissipation, derating and isolation per Rockwell publication 1756-TD002-EN-E and 1756-IN050.

Replacing a 1756-OF8

Record the series letter from the old module; A and B are not interchangeable on a tight chassis supply.

Carry over or re-order the 20-position RTB and re-key it.

Re-check current-mode channels for the 0.1 mA open-circuit threshold.

Which module to specify

  • 1756-OF8 — 8 outputs, no channel isolation, series A or B.
  • 1756-OF8I — 8 isolated channels, any voltage or current mix, 16-bit.
  • 1756-OF8H — 8 outputs plus a HART modem for smart-valve diagnostics.
  • 1756-OF4 — the 4-channel equivalent when only four loops are needed.
  • 1756-IF8 / IF16 — the input-side counterparts.

FAQ — 1756-OF8 / 1756OF8 ControlLogix 8-Channel Analog Output

What is the 1756-OF8?

A ControlLogix 8-channel analog output module with voltage or current outputs.

What resolution does it have?

15 bits across 10.5 V (320 µV/bit) and 16 bits across 21 mA (325 nA/bit).

How much current does series A draw?

150 mA at 5.1 V and 210 mA at 24 V, 5.8 W total backplane power.

How much current does series B draw?

200 mA at 5.1 V and 300 mA at 24 V, 8.22 W total backplane power.

Are the channels isolated?

No, there is no isolation between channels.

What does it dissipate?

16.78 BTU/hr for series A; 28.03 BTU/hr for series B.

Which terminal block does it need?

A 20-position 1756-TBNH or 1756-TBSH, ordered separately.

When does open circuit detection work?

Current mode only, with the output above 0.1 mA.

Is there an isolated 8-channel version?

Yes, 1756-OF8I with eight isolated channels.


Data sources. Technical values on this page come from Rockwell publications 1756-TD002 (ControlLogix I/O Modules Specifications) - the table for 1756-OF8, including backplane current, dissipation and per-point derating and the manufacturer's product page for 1756-OF8. Values re-checked 16 November 2026.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)