The 1756-OF6CI (also written 1756OF6CI) is the ControlLogix six-channel isolated current output module: 0…20 mA and 4…20 mA ranges, channel-to-channel isolation at 250 V, and a drive capability of 0…1000 Ω with separate field terminations for the 0…550 Ω and 551…1000 Ω ranges.
It is the module to specify when the loops must not share a common. Design accuracy is better than 0.1% of range from 4…21 mA at 25 °C, module error is 0.6% of range, and the output stage is an R-ladder DAC with monotonicity and no missing codes — the properties that matter when a valve positioner is being stepped rather than swung.
1756-OF6CI |
6 isolated current outputs, 0…1000 Ω |
In stock |
1756-OF6VI |
6 isolated voltage outputs |
In stock |
1756-OF8 |
8 analog outputs, group isolated |
In stock |
1756-OF8IH |
8 HART current outputs |
In stock |
1756-IF16 |
16 analog inputs where the loop is read rather than driven |
In stock |
Application |
Isolated current analog output |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-OF6CI |
Type |
Analog output module |
Sub Brand |
ControlLogix |
Mounting |
1756 ControlLogix chassis |
Number Of Channels |
6 current outputs, channel-to-channel isolated |
Output Range |
0…20 mA, 4…20 mA |
Drive Capability |
0…1000 Ω, separate terminations for 0…550 Ω and 551…1000 Ω |
Resolution / Accuracy |
Better than 0.1% of range from 4…21 mA at 25 °C |
Module Error |
0.6% of range |
Settling Time |
< 2 ms to 95% of final value, resistive load |
Scan Time |
25 ms maximum floating point, 10 ms integer |
Short Circuit |
Electronically limited to 21 mA or less |
Overvoltage Protection |
24 V DC |
Isolation Voltage |
250 V continuous, basic, channel-to-backplane and channel-to-channel |
Backplane Current |
225 mA at 24 V DC for 0…550 Ω loads, 300 mA for 551…1000 Ω |
Backplane Power |
6.7 W for 0…550 Ω, 8.5 W for 551…1000 Ω |
Power Dissipation |
5.5 W / 6.1 W maximum |
Thermal Dissipation |
18.76 / 20.80 BTU/hr |
Terminal Block |
1756-TBNH or 1756-TBSH |
Operating Temperature |
0…60 °C (32…140 °F) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Per-channel isolation is the reason this module exists alongside the cheaper eight-channel OF8. Six loops at 250 V channel-to-channel let one card drive positioners on equipment fed from different supplies, or on a skid whose field wiring is separately grounded, without a common-mode path between loops.
The drive range is split deliberately. Loads of 0…550 Ω terminate on OUT and RTN; loads of 551…1000 Ω terminate on OUT and ALT, and the backplane draw rises from 225 mA to 300 mA at 24 V, with total power from 6.7 W to 8.5 W. A 750 Ω loop is not just a heavier load, it is a different terminal pair and a different power budget.
Protection is published rather than implied: overvoltage protection at 24 V DC and short-circuit protection electronically limited to 21 mA or less. On a 4…20 mA loop that 21 mA ceiling is above the 20 mA span, so a shorted loop reads over-range instead of damaging the output stage.
Timing is the constraint on the control side. Module scan is 25 ms maximum in floating point and 10 ms in integer, with settling under 2 ms to 95% of a step into a resistive load. A loop that is retuned every 100 ms at the controller is unaffected; a fast hydraulic positioner is not.
Accuracy has a shelf life. Calibrated accuracy of 0.1% is stated at 25 °C, with offset drift of 1 µA/°C and gain drift of 60 ppm/°C typical, 100 ppm/°C maximum, on a six-month calibration interval. The honest way to carry those numbers into a specification is to state the interval alongside the accuracy.
The terminal block choice is 1756-TBNH or 1756-TBSH, and the module draws one slot. The TBNH accepts two conductors per terminal at 0.33…1.3 mm², the TBSH one conductor at 0.33…2.1 mm² — the difference decides whether a loop and its shield drain can be landed on the same terminal.
Two indicators cover the module itself; loop faults show up as a span error, a current pinned at 21 mA, or a slow drift that the calibration interval explains.
| Indicator | State | Meaning and first action |
| OK | Green | Module healthy and communicating on the backplane. |
| Loop reads low at span | — | Field resistance above 1000 Ω, or the loop terminated on the 0…550 Ω pair with a higher-resistance load. |
| Output stuck at 21 mA | — | Short circuit protection has engaged; the loop is electronically limited to 21 mA or less. |
| Drift over months | — | Offset 1 µA/°C typical, gain 60 ppm/°C typical; recalibrate on the published six-month interval. |
Loop, isolation and accuracy figures per Rockwell publication 1756-TD002N-EN-E; configuration per 1756-UM009 and 1756-IN050.
A loop that reads low at span is usually field resistance, not the module: check the total loop resistance against the 1000 Ω limit and the terminal pair against the 550 Ω boundary.
An output pinned at 21 mA has short-circuit protection engaged; find the field short before replacing the card, or the replacement will do the same thing.
A channel that drifts while its neighbours hold points at a failed calibration rather than a failed DAC, which is why the six-month interval is published. Recalibrate before condemning the module.
What is the 1756-OF6CI?
A ControlLogix analog output module with 6 isolated current outputs.
What ranges does it support?
0…20 mA and 4…20 mA.
What load can it drive?
0…1000 Ω, with separate terminations for 0…550 Ω and 551…1000 Ω loads.
Is it isolated channel to channel?
Yes — 250 V continuous, basic insulation, channel-to-backplane and channel-to-channel.
What is the accuracy?
Better than 0.1% of range from 4…21 mA at 25 °C; module error 0.6% of range.
What is the short-circuit behaviour?
The output is electronically current limited to 21 mA or less.
What does it draw from the backplane?
225 mA at 24 V DC for 0…550 Ω loads or 300 mA for 551…1000 Ω loads, 6.7 W or 8.5 W total.
What is the scan time?
25 ms maximum in floating point and 10 ms in integer mode, with settling under 2 ms to 95%.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002N (1756 ControlLogix I/O Modules Specifications, November 2021) - 1756-OF6CI output, isolation, power and environmental data; 1756-UM009 (ControlLogix Analog I/O Modules User Manual) and the manufacturer's product page for 1756-OF6CI. Values re-checked 16 November 2026.