Product Details:
Payment & Shipping Terms:
|
The 1756-OB16IEF (also written 1756OB16IEF) is the 16-point fast DC output module: 10...30 V DC, 2 A per channel at 45 °C on four channels maximum, 1 A maximum at 60 °C, backplane 320 mA at 5.1 V DC and 3 mA at 24 V DC (1756-IN062).
The "four channels" limit is the constraint that decides whether this module fits. At 45 °C the 2 A rating applies to four channels only; at 60 °C the ceiling is 1 A per channel. A panel designed for sixteen channels at 2 A each in a 55 °C enclosure is not covered by the published table.
That trade is deliberate: the fast output stage switches faster than a standard DC output, and speed costs thermal headroom. The module publishes no separate module total in the IN062 table, so the per-channel figure and the four-channel note are the numbers to design against.
Backplane draw is 320 mA at 5.1 V DC and 3 mA at 24 V DC, the highest 24 V figure among the non-diagnostic DC outputs, which is a small but real addition to a full chassis budget.
1756-IB16 | 16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 | In stock |
1756-IB16D | 16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA | In stock |
1756-IB16I | 16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA | In stock |
1756-IB16IF | 16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA | In stock |
1756-IB16ISOE | 16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA | In stock |
1756-IB32 | 32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 | In stock |
1756-IC16 | 16 inputs, 30...60 V DC, backplane per 1756-IN062 | In stock |
1756-IG16 | 16 TTL inputs, backplane per 1756-IN062 | In stock |
1756-IV16 | 16 inputs, 48 V DC, backplane per 1756-IN062 | In stock |
Application | Discrete output |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-OB16IEF |
Communication | Backplane (producer/consumer) |
Display | — |
Enclosure | None (open-style) |
Interface | Removable terminal block |
Mounting | Chassis slot |
Number Of Channels | 16 |
Standard | CE, UL, CSA, RCM |
Sub Brand | ControlLogix |
Type | Digital Output Module |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The fast output is for loads that need quick, repeatable switching: high-cycle solenoid valves, fast pneumatic pilot valves, and the output side of a high-speed inspection or sorting station.
Design it for four high-current channels plus the rest at 1 A. That is how the published table reads, and a panel built to sixteen channels at 2 A will not meet the specification.
Where every point only needs 1 A and speed is not critical, the OB16E costs less and draws 250 mA instead of 320 mA on the 5.1 V rail.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | 1 A at 60 °C | Above 45 °C the published per-channel maximum falls to 1 A. |
| Check 3 | 10...30 V DC | The published output range; a 24 V supply sits comfortably inside it. |
| Check 4 | 320 mA on the 5.1 V rail | Plan the chassis power budget for the fast output stage, not for a standard card. |
| Check 5 | Inductive load suppression | The faster the output stage, the more a coil's back-EMF matters. Fit suppression at the load. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
For a 2 A rating without the four-channel limit, 1756-OB16I publishes 2 A pilot duty with a 350 mA backplane draw.
For 1 A per point with 2 A inrush across all sixteen channels, 1756-OB16E is the standard card.
For the scheduled-output variant of the same fast stage, 1756-OB16IEFS is the companion catalog number.
What is the 1756-OB16IEF?
A 16-point fast DC output module, 10...30 V DC, 2 A per channel at 45 °C on up to four channels and 1 A at 60 °C.
Why only four channels at 2 A?
That is the published limit — 2 A applies to four channels at 45 °C, with 1 A per channel as the 60 °C maximum.
What is its backplane current?
320 mA at 5.1 V DC and 3 mA at 24 V DC.
What output voltage range does it switch?
10...30 V DC.
Is there a module total in the published table?
The IN062 table publishes the per-channel ratings and the four-channel limit; there is no separate module total listed for this catalog number.
Does it have the same isolation as the OB16I?
The isolation row for this catalog number is not separately published in the IN062 table; the OB16IEFS row in the same table lists 250 V reinforced to the backplane.
What is the maximum ambient temperature?
60 °C, with the per-channel rating at that ambient published as 1 A.
Which publication should be quoted?
1756-IN062, the ControlLogix DC digital I/O installation instructions.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-OB16IEF. Values re-checked 15 November 2026.