The 1756-SYNCH (also written 1756SYNCH) is the SynchLink fibre module for the ControlLogix 1756 platform: two fibre-optic ports, 5 Mbps synchronous data rate at 650 nm, a 50 µs frame period, chassis mounted and one slot wide. It coordinates Coordinated System Time across several ControlLogix chassis, moves a small amount of data between them at high speed, and lets one controller consume motion axis data from a controller in another chassis.
A frame carries 3 flags of 3 bytes, a 1-byte control field and a 24-byte data field. Current draw is 1200 mA at 5.1 V DC plus 3 mA at 24 V DC, dissipating 6.2 W and 21.2 BTU/hr. Cabling is 200/230 µm HCS (hard clad silica) fibre terminated with the Versalink V-System, 1…300 m; the temperature code is T4 and operating temperature is 0…60 °C (1756-TD003 Tables 19 and 20).
| 1756-DHRIO | DH+ or remote I/O bridge, two selectable ports, 32 connections | IN STOCK |
| 1756-RIO | Remote I/O module, scanner or adapter, 32 physical racks | IN STOCK |
| 1756-DH485 | DH-485 network communication module | IN STOCK |
| 1756-SYNCH | SynchLink fibre module, 5 Mbps, 50 us frame, 2 ports | IN STOCK |
Application | SynchLink |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-SYNCH |
Communication | SynchLink |
Display | Digital |
Enclosure | None (open-style) |
Interface | 2 fibre-optic ports, 650 nm, 200/230 um HCS |
Mounting | Chassis |
Number Of Channels | 2 |
Standard | CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand | ControlLogix |
Type | Communication Module |
UNSPSC | 32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix system user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module is used where two chassis have to share time and motion data: a coordinated drive line split across two ControlLogix racks, or a motion controller that has to consume axis data produced in another chassis. SynchLink carries the Coordinated System Time that makes those axes agree.
The published envelope is small and deliberate — a 24-byte data field in a 50 µs frame at 5 Mbps, over 1…300 m of HCS fibre. It is a time-and-data synchronisation link, not a general-purpose network; I/O and messaging stay on EtherNet/IP or ControlNet.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for the solid state. |
| OK | Off | No chassis power at the slot, or the module failed its self-test. |
| Link 1 / Link 2 | Green solid | Fibre link synchronised and the frame is being received. |
| Link 1 / Link 2 | Flashing green | Light detected, synchronisation not established — check the node role and the peer chassis. |
| Link 1 / Link 2 | Off | No light received: fibre polarity, connector contamination, or a break in the run. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix System User Manual) and 1756-IN050.
No successor catalogue number is published for the 1756-SYNCH. Where a design is being rebuilt, synchronisation across chassis is normally carried by EtherNet/IP with the time-synchronisation features of the controller family, and the SynchLink-specific data exchange is re-engineered rather than copied.
For maintenance, the checks that matter are the fibre itself and the node roles: HCS 200/230 µm cable with Versalink V-System termination, runs inside 1…300 m, and one module designated per role in the Studio 5000 project.
What does the 1756-SYNCH actually synchronise?
Coordinated System Time across ControlLogix chassis. It also moves a limited amount of data between chassis at 5 Mbps and lets one controller consume motion axis data from a controller in another chassis (1756-TD003 Table 19).
What is the data capacity of one frame?
Three flags of 3 bytes, a 1-byte control field and a 24-byte data field, in a 50 µs frame period at 5 Mbps, 650 nm (Table 19). That is the whole published payload — it is a synchronisation link, not a general data network.
What fibre and distance does it support?
200/230 µm HCS (hard clad silica) fibre with Versalink V-System termination, 1…300 m (Table 19). Two fibre-optic ports are on the module; a dark port on a known-good peer is usually polarity or connector contamination.
How much backplane current does it draw?
1200 mA at 5.1 V DC and 3 mA at 24 V DC, dissipating 6.2 W and 21.2 BTU/hr (Table 19). At 1.2 A it is one of the heavier communication modules, so the chassis supply budget is checked before the slot is committed.
What are its environmental limits?
Operating 0…60 °C, storage -40…85 °C, 5…95% RH non-condensing, 2 g vibration at 10…500 Hz, 30 g operating and 50 g non-operating shock, CISPR 11 Class A, ESD 6 kV contact and 8 kV air, radiated RF immunity 10 V/m from 80…2000 MHz and 1 V/m from 2000…2700 MHz (Table 20). Temperature code T4.
Which chassis and supplies are approved?
1756-A4, A7, A10, A13 and A17 with the 1756-PA72, PA75, PB72, PB75, PC75 or PH75 supply, in any slot, one slot wide (Table 19).
Which certifications does the module carry?
The module certification list in 1756-TD003 gives c-UL-us UL E65584 and Class I Division 2 UL E194810, CE to 2014/30/EU, RCM, ATEX II 3 G Ex ec IIC T4 Gc, UKEX UL22UKEX2604X, UKCA, IECEx UL 22.0063X, KC, Morocco and CCC 2020122309111998. Where a classified location is involved, confirm the marking on the module against the panel documentation.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications) and 1756-UM001 (ControlLogix System User Manual) and the manufacturer's product page for 1756-SYNCH. Values re-checked 15 November 2026.