The 1756-SPESMNSE (also written 1756SPESMNSE) is the capacitor energy storage module for the 1756-L7SP safety partner in a GuardLogix 5570 system. It is removable, carries no residual WallClockTime backup, and draws 300 mA at 5.1 V DC.
The NSE variant exists for one specific compliance need: a controller that must be transported with its residual stored energy reduced to 40 µJ or less.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Energy storage module for safety partner |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-SPESMNSE |
Current Draw |
300 mA at 5.1 V DC |
Removable |
Yes |
WallClockTime Backup |
No |
Memory Limit |
1756-L73 (8 MB) or smaller |
Type |
Capacitor energy storage module |
Sub Brand |
GuardLogix |
Enclosure |
None (open-style) |
Temperature Code |
T4 |
Operating Temperature |
0…60 °C (32…140 °F) |
Non-Operating Temperature |
-40…85 °C (-40…185 °F) |
Relative Humidity |
5…95%, non-condensing |
Vibration |
2 g @ 10…500 Hz |
Shock, Operating |
30 g |
Shock, Non-Operating |
50 g |
Certification |
c-UL-us, CE, RCM, ATEX/IECEx zone 2, UKEx, UKCA, KC, CCC |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 40 µJ threshold is the whole point of this part. Rockwell publishes that you wait at least 20 minutes after removing power for the residual stored energy to fall to that level before taking the ESM, or the controller, out of the application. The companion 1756-ESMNSE carries the same rule on the standard side.
It is also memory-limited: the publication restricts this ESM to a 1756-L73 (8 MB) or smaller memory-sized controller. A larger controller does not take it, regardless of what the slot accepts mechanically.
The module is removable, and that is what separates it from the 1756-SPESMNRM. Removable means serviceable in the field; the NRM version trades that for a permanent block on USB and SD access.
Current draw is 300 mA at 5.1 V, counted against the chassis supply like any other module. On a GuardLogix 5570 pair the safety partner and its ESM both draw from the same backplane budget.
There is no WallClockTime backup in this part. If the application relies on the controller clock surviving a power cycle, the capacitor ESM shipped with the controller (1756-ESMCAP) is the one that provides it, not this module.
Environmental ratings are the standard ControlLogix set: 0…60 °C operating, -40…85 °C non-operating, 5…95% relative humidity non-condensing, 2 g vibration at 10…500 Hz, 30 g operating shock and 50 g non-operating. Certification covers c-UL-us with Class I Division 2, CE, RCM, ATEX/IECEx zone 2 (Ex ec IIC T4 Gc), UKEx, UKCA, KC and CCC.
An energy storage module has no status display; the relevant facts are the depletion wait before transport, whether the part is removable, and whether USB and SD access are blocked.
| Indicator | State | Meaning and first action |
| Safety partner reports no partner after a swap | — | The ESM belongs to the L7SP safety partner, not to the standard controller; a standard 1756-ESM in that slot is the wrong part. |
| USB port dead after maintenance | — | 1756-SPESMNRM and SPESMNRMXT permanently disable the USB connection and SD card use by design. |
| SD card will not come out | — | An SD card installed before the NRM ESM was fitted remains functional but is no longer removable. |
Description, current draw and environmental figures per Rockwell publication 1756-TD001-EN-P and 1756-IN050.
Replace with the same catalogue number, not the standard-side ESM. The safety partner takes the SP series.
Observe the 20 minute wait before removal whenever the ESM is being taken out of the application rather than swapped on a bench.
Check the controller memory size before ordering; the L73 8 MB limit is published.
What is the 1756-SPESMNSE?
A removable capacitor energy storage module for the 1756-L7SP safety partner in a GuardLogix 5570 system.
Does it provide WallClockTime backup?
No — the publication states no residual WallClockTime power backup.
What current does it draw?
300 mA at 5.1 V DC.
How long before it can be removed?
Wait at least 20 minutes for residual stored energy to fall to 40 µJ or less.
Which controllers accept it?
A 1756-L73 (8 MB) or smaller memory-sized controller.
Is it interchangeable with 1756-SPESMNRM?
No — the NRM version is non-removable and blocks USB and SD card use.
What is its operating temperature?
0…60 °C, with -40…85 °C non-operating.
Is there an extreme-temperature version?
Yes, 1756-SPESMNSEXT.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) - GuardLogix 5570 safety partner energy storage modules, current draw, environmental and certification data for 1756-SPESMNSE and the manufacturer's product page for 1756-SPESMNSE. Values re-checked 16 November 2026.