The 1756-IH16I (also written 1756IH16I) is the isolated high-voltage DC input module: 90...146 V DC, 1 mA at 90 V and 3 mA at 146 V per input, backplane load 125 mA at 5.1 V DC and 3 mA at 24 V DC (1756-IN062).
The published rating is not a single number, and this is the module where that matters most. The same table states: 90...146 V DC with 12 channels on at 50 °C, 90...132 V DC with 14 channels on at 55 °C, 90...125 V DC with 16 channels on at 60 °C, and 90...146 V DC with 16 channels on at 30 °C. Both the top of the voltage range and the number of channels that may be on move with the ambient temperature.
In practice that means an enclosure running at 60 °C cannot present 140 V to all 16 inputs. A design that quotes '90...146 V DC, 16 points' and installs the panel in a hot cabinet is quoting the 30 °C row.
Isolation is 250 V continuous basic from inputs to backplane and 250 V basic input-to-input — the isolated variant, for 110 V DC control circuits where each channel may come from a different source.
1756-IB16 |
16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 |
In stock |
1756-IB16D |
16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA |
In stock |
1756-IB16I |
16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA |
In stock |
1756-IB16IF |
16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA |
In stock |
1756-IB16ISOE |
16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA |
In stock |
1756-IB32 |
32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 |
In stock |
1756-IC16 |
16 inputs, 30...60 V DC, backplane per 1756-IN062 |
In stock |
1756-IG16 |
16 TTL inputs, backplane per 1756-IN062 |
In stock |
1756-IV16 |
16 inputs, 48 V DC, backplane per 1756-IN062 |
In stock |
Application |
Discrete input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IH16I |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
16 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Digital Input Module |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module is for 110 V DC control circuits — older DC auxiliaries, trip and close circuits, and plant where 110 V DC is the station battery voltage. It reads those signals directly into the ControlLogix rack.
Because every channel is isolated, it suits circuits fed from different sources: several battery sections, or equipment from different suppliers each with its own 110 V DC supply.
The derating table makes it a documentation item as much as a hardware item: the panel schedule has to state which row applies, and the cabinet temperature has to be measured, not assumed.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Channels on derates too | 12 channels at 146 V/50 °C, 14 at 132 V/55 °C, 16 at 125 V/60 °C. Count how many inputs are actually energised continuously. |
| Check 3 | 1 mA at 90 V, 3 mA at 146 V | The input current is voltage-dependent, so the field burden rises with the applied voltage. |
| Check 4 | Input-to-input isolation | 250 V basic between inputs as well as to the backplane — the reason to choose this rather than a group-isolated module. |
| Check 5 | 125 mA backplane | Modest compared with the ISOE variants, but still counted per module in a full chassis. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
The group-isolated wide-window module is 1756-IB16ISOE: 10...55 V DC, 5.1 mA, 320 mA backplane.
The sequence-of-events high-voltage module is 1756-IH16ISOE: 90...140 V DC, 1.15...1.85 mA, 275 mA backplane.
For 30...60 V DC circuits the module is 1756-IC16, and for 24 V DC it is 1756-IB16.
What is the 1756-IH16I?
A 16-point isolated high-voltage DC input module, 90...146 V DC, with input current of 1 mA at 90 V and 3 mA at 146 V.
Why does the specification list several voltage ranges?
The published table derates both voltage and channels-on with ambient temperature: 90...146 V DC at 30 °C, 90...146 V DC with 12 channels at 50 °C, 90...132 V DC with 14 channels at 55 °C and 90...125 V DC with 16 channels at 60 °C.
What is the backplane current?
125 mA at 5.1 V DC and 3 mA at 24 V DC.
What isolation does it provide?
250 V continuous basic inputs-to-backplane and 250 V basic input-to-input.
Can all 16 inputs be on at 60 °C with 146 V?
No. At 60 °C the published top of the range is 125 V DC for 16 channels on.
What is the input current per point?
1 mA at 90 V DC and 3 mA at 146 V DC.
Is there a harsh-environment version?
Yes — 1756-IH16IK, the conformal-coated variant in the same publication.
What documents cover it?
1756-IN062 for installation and specifications, 1756-TD002 for technical data and 1756-UM058 for the user manual.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IH16I. Values re-checked 15 November 2026.