Product Details:
Payment & Shipping Terms:
|
The 1756-A7LXT (also written 1756A7LXT) is the seven-slot ControlLogix-XT chassis rated for -25…+60 °C: the low-profile seven-slot backplane that fits a 50.8 x 60.9 x 20.3 cm minimum cabinet, conformally coated for ISA G3 environments.
Published figures are 7 slots, 10 A chassis and 6 A per slot at 5.1 V DC, 2 A / 2 A at 24 V DC, 4 A / 4 A at 3.3 V DC, 4.1 W maximum chassis dissipation and 1.1 kg approximate weight (1756-TD006). The seven-slot count carries a controller, a communication module and five I/O modules without leaving a slot open.
1756-A4LXT/B |
4 slots, 50.8 x 50.8 x 20.3 cm, -25…+60 °C, 10 A at 5.1 V DC |
In stock |
1756-A5XT/B |
5 slots, 50.8 x 76.2 x 20.3 cm, -25…+70 °C, 10 A at 5.1 V DC |
In stock |
1756-A7LXT/B |
7 slots, 50.8 x 60.9 x 20.3 cm, -25…+60 °C, 10 A at 5.1 V DC |
In stock |
1756-A7XT/B |
7 slots, 50.8 x 60.9 x 20.3 cm, -25…+70 °C, 10 A at 5.1 V DC |
In stock |
1756-A7XT/C |
7 slots, -25…+70 °C, 15 A at 5.1 V DC, Series C |
In stock |
1756-A10XT/C |
10 slots, 50.8 x 85.75 x 20.3 cm, -25…+70 °C, 15 A at 5.1 V DC |
In stock |
Application |
Chassis / backplane |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-A7LXT |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
Open chassis, conformally coated (XT) |
Interface |
1756-A7LXT |
Mounting |
Horizontal only, panel located |
Number Of Channels |
1756-A7LXT |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Chassis |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN005 (chassis installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Seven slots is the common XT rack size: a controller, one or two communication modules, digital and analog I/O, and the spare slot that every commissioning seems to need. At -25…+60 °C it suits most unheated industrial cabinets that never see direct sun or process heat.
The chassis dissipation of 4.1 W is small against the modules, but it is part of the enclosure calculation, and the XT power supply on the left adds its own heat on top of it.
A chassis has no indicators; its limits are the numbers that decide whether the rack can carry the modules planned for it. Every row below is quoted from the chassis specification 1756-TD006.
| Indicator | State | Meaning and first action |
| Backplane current at 5.1 V DC | 10 A / 6 A | Chassis total / per-slot maximum. Sum the 5.1 V current of every module against this figure before the layout is fixed. |
| Backplane current at 24 V DC | 2 A / 2 A | Chassis total / per-slot maximum, for modules that take their 24 V from the backplane. |
| Backplane current at 3.3 V DC | 4 A / 4 A | Chassis total / per-slot maximum, common to the whole XT family. |
| Backplane current at 1.2 V DC | 1.5 A / – | Chassis total, with no per-slot limit published. |
| Power dissipation | See the specification table | The chassis itself dissipates 3.7 W to 5.0 W depending on size; it adds to the enclosure thermal load. |
| Operating temperature | -25…+60 °C (-13…+140 °F) | The surrounding-air rating of this chassis. Every module in the rack has to share it or the assembly drops to the lower figure. |
| Mounting | Horizontal only | Panel mount, minimum cabinet depth 20.3 cm; the XT chassis is conformally coated for ISA G3 environments. |
| Earth grounding | 8 AWG functional / 14 AWG protective | Copper wire rated 90 °C or greater; the coating does not replace the earth connection. |
Slot counts, backplane current, enclosure sizes and environmental ratings per Rockwell publication 1756-TD006F-EN-E (1756 ControlLogix Chassis Specifications) and 1756-IN050.
Where the cabinet reaches +70 °C, the same seven slots are available in the 1756-A7XT (Series B at 10 A, Series C at 15 A). Where the slot count is smaller, the 1756-A4LXT and 1756-A5XT cover four and five.
The -25 °C floor is the reason this chassis exists at all: the standard 1756-A7 stops at 0 °C, so a cold-store or outdoor panel cannot be built from it.
How many slots does the 1756-A7LXT have?
Seven slots at 10 A chassis / 6 A per slot on 5.1 V DC (1756-TD006).
What is the temperature rating?
-25…+60 °C surrounding air; the 1756-A7XT covers -25…+70 °C at the same slot count.
What cabinet size is needed?
Minimum 50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.), horizontal mounting only.
What does the chassis weigh and dissipate?
1.1 kg (2.4 lb) approximately and 4.1 W maximum dissipation.
What backplane current is published?
10 A at 5.1 V DC (6 A per slot), 2 A at 24 V DC (2 A per slot), 4 A at 3.3 V DC, 1.5 A at 1.2 V DC.
Which supply and adapter fit?
Xt supplies 1756-PAXT / PBXT / PA30XT / PB30XT on the left; redundant pair 1756-PAXTR / PBXTR with the 1756-PSCA2XT chassis adapter.
Does the conformal coating change the earth requirement?
No. 8.3 mm² (8 AWG) functional earth and 2.1 mm² (14 AWG) protective earth, both 90 °C copper, still apply.
Which certifications apply?
UL Listed (E65584), UL Class I Division 2 (E194810), FM Approved, CE, RCM, ATEX Ex nA IIC T4 Gc X, IECEx, KC, EAC, when marked.
Data sources. Technical values on this page come from Rockwell publications 1756-TD006 (1756 ControlLogix Chassis Specifications) and 1756-IN005 (ControlLogix chassis installation instructions) and the manufacturer's product page for 1756-A7LXT. Values re-checked 16 November 2026.