Product Details:
Payment & Shipping Terms:
|
The 1756-EN2TXT (also written 1756EN2TXT) is the extended-environment version of the ControlLogix EtherNet/IP bridge: two RJ45 Category 5 ports at 10/100 Mbps, 256 Logix connections, 128 TCP connections, one slot wide. It runs the same EtherNet/IP stack as the 1756-EN2T; what changes is the conformal coating, the -25…+70 °C range and the G3/CX corrosion rating, and those are carried by the XT chassis it is installed in (1756-TD003 Table 7).
Current draw is 1 A at 5.1 V DC, dissipating 5.1 W and 17.4 BTU/hr — 200 mA less than the two-port standard model, which matters when an XT panel is sized around a small 1756-PAXT supply. Isolation is 30 V continuous basic insulation, compliant and tested to IEC/UL 61010-1; Table 7 publishes no type-test voltage for the XT family. The front USB port runs at 12 Mbps, the temperature code is T4 and the module is open-style.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application | EtherNet/IP |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-EN2TXT |
Communication | EtherNet/IP |
Display | Digital |
Enclosure | None (open-style) |
Interface | 2 Copper RJ45 (10/100 Mbps, Category 5) |
Mounting | Chassis |
Number Of Channels | 2 |
Standard | CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand | ControlLogix |
Type | Communication Module |
UNSPSC | 32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module is for panels that are not heated: an outdoor skid, a wash-down area, a plant where hydrogen sulphide or salt mist is present. The -25 °C start and the coating are the reason to pay for the XT part, and they only exist as long as the whole assembly is XT — module, chassis and supply.
On the network it does the ordinary bridge job: I/O, drives, HMI and programming traffic share the 128 TCP and 256 Logix connections, and the two ports can run a device-level ring or two separate segments.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for the solid state. |
| OK | Off | No chassis power at the slot, or the module failed its self-test. |
| NET | Green solid | CIP connections established to at least one device. |
| NET | Flashing green | IP address present, no CIP connection — check the connection entry in Studio 5000. |
| NET | Off | No IP address; the module is not on the network yet. |
| LINK 1 / LINK 2 | Green solid | Port linked at 10 or 100 Mbps. |
| LINK 1 / LINK 2 | Off | No link on that port: cable, connector or partner port. |
Indicator behaviour per Rockwell publication 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and 1756-IN050.
The 1756-ENBT reached End of Life on 1 November 2021 and the published replacement is the 1756-EN2T. In an XT panel the equivalent slot is this module: same connection capacity as the ENBT path in Table 7 at 128 TCP and 256 Logix, and 1 A draw against the ENBT's 700 mA.
The substitution does not end at the module. The XT chassis 1756-A7XT/C, A10XT/C, A7ZXT or A10ZXT and the PAXT, PBXT or PA75XT supply are part of the same assembly; fitting an XT module into a standard chassis gives back the standard 0…60 °C rating.
What does the XT suffix add over the standard 1756-EN2T?
Conformal coating, a -25…+70 °C operating range and a G3/CX corrosion rating, all carried by the XT chassis and supply. The network side is unchanged: two RJ45 Category 5 ports at 10/100 Mbps, 128 TCP and 256 Logix connections (Table 7).
What is its current draw and thermal load?
1 A at 5.1 V DC, 5.1 W and 17.4 BTU/hr, one slot wide (Table 7). That is 200 mA below the standard two-port EN2TR, which buys headroom on a small XT power supply.
Which chassis and power supplies is it approved with?
1756-A7XT/C, A10XT/C, A7ZXT or A10ZXT with the PAXT, PBXT or PA75XT supply, or the redundant PAXTR and PBXTR pairing (Tables 7 and 8). The XT chassis is what makes the extended rating real.
Do the XT ratings still apply if I fit it in a standard chassis?
No. The -25…+70 °C range, the coating and the G3/CX rating are properties of the complete XT assembly. In a 1756-A7 or A10 chassis the module is limited by that chassis rating.
What environmental limits are published?
Operating -25…+70 °C; storage -40…85 °C; conformal coated; corrosion resistance G3/CX; 2 g vibration; 30 g shock; CISPR 11 Class A; ESD 6 kV contact and 8 kV air; radiated RF immunity tested to 6000 MHz; EFT ±3 kV and surge ±2 kV line-earth on the Ethernet ports (Tables 7 and 9).
Which certifications does the XT module carry?
c-UL-us, CE, RCM, ATEX to EN 60079-7, UKEX, UKCA, IECEx UL 22.0063X, KC, ODVA conformance, Morocco and CCC (Table 9). FM approval is not listed for the XT family.
How many connections can it carry?
128 TCP connections and 256 Logix connections (Table 7), the same figures as the standard EN2T and EN2TR. I/O, drives, HMI sessions and programming traffic all draw from that same budget.
Is this the module that replaces the 1756-ENBT in cold panels?
Yes for XT installations. The ENBT reached End of Life on 1 November 2021 with the 1756-EN2T as its published replacement; in an unheated or corrosive enclosure the equivalent slot is the EN2TXT, at 1 A draw instead of 700 mA.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-EN2TXT. Values re-checked 15 November 2026.