Product Details:
Payment & Shipping Terms:
|
The 1756-L63S (also written 1756L63S) is the largest GuardLogix 5560 controller: 8 MB of user memory and 3.75 MB of safety memory, used as a pair with the 1756-LSP safety partner in the slot immediately to its right. Together the pair reaches SIL CL 3 / PL e / Category 4, with the safety and standard logic in one project and one tag database (1756-TD001I Tables 14 and 18).
Current draw is 1200 mA at 5.1 V DC and 14 mA at 24 V DC per module, 3.5 W and 11.9 BTU/hr; isolation is 30 V continuous basic insulation from the RS-232 port to the system, type tested at 720 V DC for 60 s. Digital I/O is limited to 128,000 points and analogue to 4,000. Controller redundancy is not supported on any GuardLogix controller.
| 1756-L61S | GuardLogix 5560 safety controller, 2 MB user / 1 MB safety | IN STOCK |
| 1756-L62S | GuardLogix 5560 safety controller, 4 MB user / 1 MB safety | IN STOCK |
| 1756-L63S | GuardLogix 5560 safety controller, 8 MB user / 3.75 MB safety | IN STOCK |
| 1756-L61 | ControlLogix 5560 standard controller, 2 MB | IN STOCK |
| 1756-L63 | ControlLogix 5560 standard controller, 8 MB | IN STOCK |
| 1756-L65 | ControlLogix 5560 standard controller, 32 MB | IN STOCK |
Application | Safety Control (SIL 3 / PL e) |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-L63S |
Communication | Backplane (EtherNet/IP, ControlNet, DeviceNet) |
Display | Indicators (OK, RUN, I/O, FORCE, BATTERY, RS-232) |
Enclosure | None (open-style) |
Interface | 1 RS-232 serial port |
Mounting | Chassis |
Number Of Channels | 1 |
Standard | CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand | ControlLogix |
Type | Safety Controller |
UNSPSC | 32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-RM093 (GuardLogix safety reference manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
3.75 MB of safety memory is the reason this part exists: a multi-station line where the safety program covers several zones of guarding, muting and safe-speed logic and no longer fits the 1 MB the smaller pairs offer, while the 8 MB standard side carries the cell's own sequencing and recipe data.
The pair is the safety unit — two slots, primary plus partner — and the networks are EtherNet/IP, ControlNet and DeviceNet for both standard and safety traffic. Because redundancy is not supported, availability has to come from the machine design rather than from a second controller.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Red | Major fault or self-test failure; check the safety task status before any restart. |
| RUN | Green solid | Program running, standard and safety tasks executing. |
| RUN | Red | Major fault latched; the program is stopped. |
| I/O | Green solid | All configured I/O modules are communicating. |
| I/O | Flashing green | One or more configured modules are not responding. |
| FORCE | Amber | Forces enabled in the standard task — a live wiring check is not valid while this is lit. |
| BATTERY | Red | Battery low or missing; the project in RAM is not protected across a power cycle. |
| Partner status | Per project | The safety partner is reported in the project: a missing or mismatched partner stops the safety task from validating. |
| RS-232 | Green flashing | Serial activity on the programming port. |
Indicator behaviour per Rockwell publication 1756-UM020 (GuardLogix Controllers User Manual) and 1756-IN050.
The 5560 family is discontinued; the successor pairs are 1756-L73S + 1756-L7SP in the GuardLogix 5570 range, or the 5580 safety controllers. The pair, not the primary alone, is what gets replaced, because the partner part number changes with the family.
With 3.75 MB of safety memory in use, the migration is a genuine program re-work: safety routine organisation is re-checked against the new controller's memory, the safety signature is regenerated, and the validated functional test is repeated.
How much safety memory does the 1756-L63S have?
3.75 MB of safety memory against 1 MB on the 1756-L61S and L62S, with 8 MB of user memory for the standard side and 478 KB of I/O memory (1756-TD001I Table 18). This is the largest safety memory published for the GuardLogix 5560 range.
What rating does the pair achieve?
SIL CL 3 per IEC 61508/EN 62061 and Category 4 / PL e per EN ISO 13849-1 when used as described in 1756-RM093; TÜV certifies the functional safety and UL certifies SIL CL 3 under file E256621 (Table 20).
Does the safety partner have its own memory?
It carries the same safety memory as its corresponding primary controller, and the table lists it as a dash for user memory — the 1756-LSP is a partner, not a controller in its own right, and cannot be used alone.
How is the pair installed in a chassis?
Primary controller plus 1756-LSP in the slot immediately to the right, two slots total, in any slot of a 1756-A4, A7, A10, A13 or A17 chassis. Moving the partner away from that position breaks the configuration.
What is the power budget?
1200 mA at 5.1 V DC and 14 mA at 24 V DC per module, 3.5 W and 11.9 BTU/hr per module (Table 18) — counted twice for a pair. Published supplies for the L6xS pair are 1756-PA72, PA75, PB72 and PB75.
Can the safety program be edited after validation?
Not while the safety memory is locked and protected. Locking follows the functional test; after that the safety logic cannot be modified and the SIL 3 claim holds. Before locking, online editing and forcing are allowed in the standard task.
What are the environmental limits and certifications?
Operating 0…60 °C, storage -40…85 °C, 5…95% RH non-condensing, 2 g vibration at 10…500 Hz, 30 g and 50 g shock, CISPR 11 Class A, ESD 6 kV contact and 8 kV air, radiated RF 10 V/m 80…2000 MHz and 3 V/m 2000…2700 MHz, EFT ±4 kV at 5 kHz and surge ±2 kV line-earth (Table 19). Certifications: c-UL-us UL E65584/E194810, CSA LR54689C/LR69960C, CE 2004/108/EC and 2006/42/EC, C-Tick/RCM, FM Class I Division 2 and KC (Table 20).
What is the difference from the standard 1756-L63?
The safety task, the safety memory and the second slot. The standard 1756-L63 is a single-slot controller with no safety rating, 8 MB of user memory and 0.32 kg; the L63S pair adds 3.75 MB of safety memory plus the partner module, and the safety certifications that follow from it.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-RM093 (GuardLogix Controller Systems Safety Reference Manual) and the manufacturer's product page for 1756-L63S. Values re-checked 15 November 2026.