The 1756-OB16E (also written 1756OB16E) is the 16-point DC output module: 10...31.2 V DC, 1 A per point with 2 A inrush, backplane 250 mA at 5.1 V DC and 2 mA at 24 V DC, isolation 250 V continuous basic outputs-to-backplane and 125 V basic output-to-output, maximum module current 8 A at 60 °C (1756-IN062).
One amp per point with a 2 A inrush ceiling is the honest shape of this module. It drives lamps, small solenoids and relay coils comfortably; a contactor whose inrush exceeds 2 A needs a different output, and the OB16I at 2 A pilot duty is the next step up.
The isolation is split: 250 V to the backplane, but only 125 V between outputs. Two separate 24 V supplies can be used, and they must share a reference within that 125 V window — the OB16I publishes 250 V for the same arrangement.
Its temperature code is T4 rather than the T4A carried by most of the DC output table, and its backplane draw at 5.1 V DC is 250 mA, which is modest for sixteen channels and leaves room for input cards in the same chassis.
1756-IB16 | 16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 | In stock |
1756-IB16D | 16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA | In stock |
1756-IB16I | 16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA | In stock |
1756-IB16IF | 16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA | In stock |
1756-IB16ISOE | 16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA | In stock |
1756-IB32 | 32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 | In stock |
1756-IC16 | 16 inputs, 30...60 V DC, backplane per 1756-IN062 | In stock |
1756-IG16 | 16 TTL inputs, backplane per 1756-IN062 | In stock |
1756-IV16 | 16 inputs, 48 V DC, backplane per 1756-IN062 | In stock |
Application | Discrete output |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-OB16E |
Communication | Backplane (producer/consumer) |
Display | — |
Enclosure | None (open-style) |
Interface | Removable terminal block |
Mounting | Chassis slot |
Number Of Channels | 16 |
Standard | CE, UL, CSA, RCM |
Sub Brand | ControlLogix |
Type | Digital Output Module |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The OB16E is the economical 16-point card for a panel full of indicator lamps, small solenoid valves and interposing relay coils, where 1 A per point is the real load and inrush stays under 2 A.
Its 250 mA backplane draw makes it the lighter choice when a chassis already carries several input modules and the 5.1 V budget is tight.
Where a point must drive a contactor at 2 A continuous, the OB16I or the OB16D is the module that publishes that rating; the OB16E does not.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | 125 V output-to-output | Half the barrier of the OB16I. Mixed supplies are allowed within that window, not beyond it. |
| Check 3 | 8 A module maximum | At 60 °C. Eight points at 1 A fills the module; the rest must be left off or moved to another card. |
| Check 4 | Inrush 2 A | A contactor coil that pulls more than 2 A at pick-up will not be driven reliably by this output. |
| Check 5 | T4 temperature code | 135 °C maximum surface temperature — a less restrictive code than the T4A modules. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
For 2 A per point, 1756-OB16I publishes 24 V DC at 2 A pilot duty with 250 V output-to-output isolation.
For diagnostics with electronic fusing, 1756-OB16D publishes 2 A at 30 °C and 1 A at 60 °C across 19.2...30 V DC.
For 8 points with 250 V output-to-output isolation, 1756-OB8EI is the short version of this module.
What is the 1756-OB16E?
A 16-point DC output module, 10...31.2 V DC, 1 A per point with 2 A inrush, backplane 250 mA at 5.1 V DC.
What is the maximum current per point?
1 A continuous, with a 2 A inrush allowance.
What is the module maximum?
8 A at 60 °C.
How is it isolated?
250 V continuous basic outputs-to-backplane and 125 V basic output-to-output.
Can I use two separate 24 V supplies?
Within the 125 V output-to-output barrier. For 250 V between outputs, use the OB16I.
Does it fuse each output electronically?
No — the electronically fused, load-diagnostic module is the OB16D. This is the standard 1 A card.
What is its temperature code?
T4, with 60 °C maximum surrounding air.
Which document quotes these figures?
1756-IN062, the ControlLogix DC digital I/O installation instructions.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-OB16E. Values re-checked 15 November 2026.