Product Details:
Payment & Shipping Terms:
|
The 1756-PC75 (also written 1756PC75) is the standard ControlLogix supply with a 48 V DC input — 30…60 V DC, nominal 48 V — and the same 75 W output, 13 A at 5.1 V DC and 2.8 A at 24 V DC as the other large standard units.
It exists for plants whose DC distribution is 48 V rather than 24 V: telecom-style cabinets, centralised DC systems and installations where a 48 V battery bank already exists.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Chassis power supply, DC input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-PC75 |
Type |
ControlLogix standard power supply |
Sub Brand |
ControlLogix |
Mounting |
Left end of 1756 chassis |
Input Voltage |
30…60 V DC, nominal 48 V DC |
Input Power |
95 W maximum |
Output Power |
75 W at 0…60 °C |
Current At 5.1 V |
13 A |
Current At 24 V |
2.8 A |
Current At 3.3 V |
4 A |
Current At 1.2 V |
1.5 A |
Inrush Current |
30 A maximum |
Hold-Up |
50 ms at 30…60 V DC |
Isolation |
250 V reinforced, tested 3500 V DC for 60 s |
Chassis |
1756-A4, A7, A10, A13, A17; series B, C |
Wire Size |
2.5 mm² (14 AWG), 90 °C minimum |
Terminal Torque |
0.565 N·m (5 lb·in) |
Weight |
0.95 kg (2.10 lb) |
Dimensions |
14.0 x 11.2 x 14.5 cm |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The input class decides the catalog number, not the wattage. The three DC supplies here have three different, non-overlapping input windows — 18…32 V, 30…60 V and 90…143 V — so a 48 V bus cannot feed a PB75 and a 24 V bus cannot feed a PC75.
The 48 V input buys two things on a long DC feed: lower current for the same power, so thinner cable and smaller fusing, and a wider margin above the battery's end-of-discharge point. A 48 V string that sags to 42 V under a discharge test is still well inside 30…60 V.
Output remains 75 W total with 13 A at 5.1 V. The higher input voltage does not change the backplane budget, only the input side — a common misreading when a 48 V panel is expected to carry more modules than a 24 V one.
Hold-up is 50 ms at 30…60 V nominal input, longer than the 35–40 ms of the 24 V unit because the stored energy at the higher input voltage is larger for the same output. It is published in milliseconds, consistent with the DC units.
Inrush is 30 A maximum, and isolation is 250 V continuous, reinforced, type tested at 3500 V DC for 60 seconds.
Mounting is at the left end of a 1756-A4, A7, A10, A13 or A17 chassis in series B or C, with 2.5 mm² (14 AWG) 90 °C input wire at 0.565 N·m. Compatibility notes for the chassis are the same letter-grade question as every large standard supply.
A power supply carries no diagnostic display of its own; the useful evidence is the input voltage under load, the total chassis wattage and the published hold-up at the site voltage.
| Indicator | State | Meaning and first action |
| Chassis browns out on a load step | Voltage dip | The 75 W output budget is shared by all rails; an added 24 V load can exhaust it before the 5.1 V current limit is reached. |
| Supply restarts on a short | Inrush | Inrush is 20 A on the AC unit and 30 A on the DC unit; confirm the upstream breaker tolerates repeated energisation. |
| Hold-up shorter than expected | — | Hold-up is published in cycles at a stated input and load, not as a fixed millisecond figure. |
Input, output and hold-up figures per Rockwell publication 1756-TD005-EN-E and 1756-IN050.
Confirm the bus voltage class before ordering. A panel documented as 'DC supplied' can be 24 V, 48 V or 125 V, and the three supplies are not interchangeable.
Check the input under load. A 48 V string at 42 V is fine, at 29 V it is not, and the supply will simply not start rather than fail visibly.
Reuse the input wiring only if the insulation rating and gauge match the 2.5 mm², 90 °C requirement.
What is the 1756-PC75?
A standard ControlLogix DC power supply with a 48 V DC nominal input and 75 W output.
What input voltage range does it accept?
30…60 V DC, nominal 48 V DC.
What current is available at 5.1 V DC?
13 A.
What is the total output power?
75 W at 0…60 °C, shared across the backplane rails.
What is the hold-up time?
50 ms at 30…60 V DC nominal input.
What is the maximum inrush current?
30 A.
Which chassis can it be used with?
1756-A4, A7, A10, A13 and A17 chassis in series B or C.
Can a 24 V bus feed a PC75?
No — the input window starts at 30 V DC, so a 24 V bus needs the 1756-PB72 or PB75.
Data sources. Technical values on this page come from Rockwell publications 1756-TD005 (ControlLogix Power Supplies Specifications) - input, output, hold-up, isolation and environmental data for 1756-PC75; 1756-SG001 (ControlLogix System Selection Guide) - chassis and supply selection and the manufacturer's product page for 1756-PC75. Values re-checked 16 November 2026.