The 1756-PBXT (also written 1756PBXT) is the DC input supply of the ControlLogix-XT family: 24 V DC nominal input, 52 W output, rated from -25 to +70 °C for XT chassis. Rockwell lists it as active with a 70 W maximum input power and a 30 A inrush current, and pairs it with the same four XT chassis as the AC version (1756-IN619, 1756-TD005).
The published current figures differ by source, and it is worth knowing which one you are quoting. 1756-TD005 lists 10.0 A at 5.1 V DC, 2.1 A at 24 V DC, 4.0 A at 3.3 V DC and 1.5 A at 1.2 V DC for the 52 W ceiling; Rockwell's product page for 1756-PBXT lists 8 A at 5 V DC, 1.75 A at 24 V DC, 4 A at 3.3 V and 1.5 A at 1.2 V for the same 52 W. Both agree on 52 W, so the ceiling that actually binds a design is the wattage, not the per-rail current.
Electrical and mechanical detail: 18…32 V DC input range with 18 V minimum (the product page states 19.2 V DC as the low end), 250 V continuous reinforced insulation from power input to backplane type tested at 3260 V DC for 60 s, wire category 1 on the power ports, 2.5 mm² (14 AWG) 90 °C copper at 0.565 N·m, 0.95 kg, 140 x 112 x 145 mm. Operating shock is 30 G and vibration 2 G at 10…500 Hz, with 5…95 % non-condensing humidity.
| 1756-PA75R | AC redundant supply, 120/240 V AC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PB75R | DC redundant supply, 24 V DC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PAXT | XT AC supply, 8 A at 5.1 V DC, 42 W at -25 to +70 C | IN STOCK |
| 1756-PBXT | XT DC supply, 10 A at 5.1 V DC, 52 W at -25 to +70 C | IN STOCK |
| 1756-PAXTR | XT AC redundant supply, 42 W, 0-60 C in a non-XT chassis | IN STOCK |
| 1756-PA75 | Non-redundant AC supply, single, 13 A at 5.1 V DC, 75 W | IN STOCK |
Application | Chassis Power |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-PBXT |
Communication | — |
Display | — |
Enclosure | None (open-style) |
Interface | Backplane, via 1756-PSCA2 |
Mounting | Remote, cable-connected |
Number Of Channels | — |
Standard | CE, UL, RCM, EAC, Morocco DOC |
Sub Brand | ControlLogix |
Type | Redundant Power Supply |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN620 (redundant power supply instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The DC XT supply is the choice when the panel already runs on 24 V DC — a battery bank, a DC bus, a solar or telecom-derived rail — and the enclosure sits outside the 0…60 °C window. Input inrush of 30 A and a 18 V floor are the two numbers that decide whether the existing DC distribution can feed it.
Because 52 W is the whole budget, the module list is settled early. Typical XT DC panels carry a controller, one or two communication modules and a small I/O count; above that the design splits across chassis rather than adding modules to one supply.
The 5.1 V rail carries the backplane logic and the bulk of the load. At 8 A the rail is already 40.8 W, which leaves roughly 11 W for everything else — the reason the design discussion should start from the wattage and work backwards.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Power ceiling | 52 W at -25…+70 °C. Sum the 5.1 V, 3.3 V, 24 V and 1.2 V loads; the per-rail currents (8 A or 10 A at 5.1 V depending on the document) cannot all be drawn at once inside 52 W. |
| Check 3 | Input source | 18…32 V DC, 24 V nominal, 70 W maximum input power, 30 A inrush. The 24 V feed has to carry the inrush without dropping below 18 V at the supply terminals during start-up. |
| Check 4 | Terminals | 2.5 mm² (14 AWG) 90 °C copper, 1.2 mm maximum insulation, 0.565 N·m torque, wire category 1 on the power ports, one conductor per terminal. |
| Check 5 | Transient immunity | IEC 61000-4-29 applies on the DC input: 10 ms interruption, 60 % dips for 100 ms, 100 % dips for 50 ms, ±20 % fluctuation for 15 min and 5 s interruptions. A weak 24 V rail shows up here first. |
| Check 6 | Certification scope | The product page lists ATEX, IECEx, CE, UKCA, RCM, EAC, CCC and UL/c-UL-us safety for this catalogue number. The protection type itself is quoted from the certificate on the unit, not assumed from the family name. |
Installation checks per Rockwell publication 1756-IN620, which covers adapter mounting, cable seating, load sharing, fusing and the chassis compatibility table and 1756-IN050.
The AC counterpart is the 1756-PAXT: 85…265 V AC input, 42 W output, 8 A at 5.1 V DC, same XT chassis list. Moving between the two is an input-wiring change — terminals, branch protection and inrush (20 A against 30 A) all differ.
For redundancy the published parts are 1756-PAXTR and 1756-PBXTR with the 1756-PSCA2XT adapter and 1756-CPR2 cables; the redundant versions are rated 0…60 °C, so the XT window and redundancy do not stack in one part number.
A single-supply XT chassis has no second supply behind it. Keeping a spare 1756-PBXT on the shelf costs less downtime than a spare module, because a supply failure stops the entire rack.
What is the input rating of the 1756-PBXT?
18…32 V DC range, 24 V DC nominal, 70 W maximum input power, 30 A maximum inrush. Rockwell's product page states 19.2 V DC as the low limit where 1756-TD005 says 18 V, so the design margin should be taken from the lower of the two.
How much current can it deliver?
The 52 W output ceiling is common to both sources. 1756-TD005 lists 10 A at 5.1 V DC and 2.1 A at 24 V DC; the product page lists 8 A at 5 V DC and 1.75 A at 24 V DC, with 4 A at 3.3 V and 1.5 A at 1.2 V in both. Design to 52 W and to the lower current figure.
What is the temperature rating?
-25…+70 °C (-13…+158 °F) ambient, the XT window, against 0…60 °C for standard ControlLogix supplies.
Which chassis can it be used in?
1756-A4LXT/B, 1756-A5XT/B, 1756-A7LXT/B and 1756-A7XT/B, the same list published for the 1756-PAXT (1756-IN619).
How does it behave on a noisy 24 V rail?
IEC 61000-4-29 requirements apply on the DC input: 10 ms interruptions, 60 % dips for 100 ms, 100 % dips for 50 ms, ±20 % fluctuation for 15 min, and 5 s interruptions. A supply that drops out under these is usually a distribution problem, not a supply fault.
What certifications does it carry?
Rockwell lists ATEX, IECEx, CE, UKCA, RCM, EAC, China CCC and UL/c-UL-us safety certification for 1756-PBXT, with the certification date recorded as 2026-11-10. Previous production may differ — check the label.
What is the isolation and wiring detail?
250 V continuous reinforced insulation, power input to backplane, type tested at 3260 V DC for 60 s; wire category 1 on the power ports, 2.5 mm² (14 AWG) 90 °C copper, 0.565 N·m torque.
What are the physical and environmental figures?
0.95 kg, 140 x 112 x 145 mm (H x W x D), open-style enclosure, 5…95 % non-condensing humidity, 30 G operating shock, 2 G vibration at 10…500 Hz, country of origin Mexico.
Is there a redundant version?
Not in this catalogue number — the product page states redundancy capable: false. Redundant XT supplies are the 1756-PAXTR and 1756-PBXTR, rated 0…60 °C in a non-XT chassis.
Data sources. Technical values on this page come from Rockwell publications 1756-IN620 (ControlLogix Redundant Power Supply, installation instructions), 1756-IN619 (ControlLogix Power Supply installation instructions) and 1756-TD005 (ControlLogix power supply technical data) and the manufacturer's product page for 1756-PBXT. Values re-checked 15 November 2026.