Product Details:
Payment & Shipping Terms:
|
The 1756-PAR2 (also written 1756PAR2) is not a single power supply — Rockwell catalogues it as a ControlLogix Power Supply Bundle, described as an 85-265 V AC redundant power supply assembly with the connection cables included. It is the part number to order when the whole redundant AC feed is wanted as one item rather than as two supplies, an adapter and a pair of cables on four separate lines.
The assembled rating is the familiar redundant pair figure: 13 A at 5.1 V DC, 4 A at 3.3 V DC, 1.5 A at 1.2 V DC and 2.8 A at 24 V DC, with the redundant configuration flag published as true. That is the 1756-PA75R pair rating carried on the bundle part number, and it is capped in the chassis by the 15 A that the 1756-PSCA2 adapter passes to the backplane.
The detail that makes a bundle worth its own page is the cable line: Rockwell lists connection cables: included. In the component-by-component route the 1756-CPR2 cable is ordered separately, and an installation that arrives without one cannot be completed. The bundle removes that failure mode from the procurement chain.
Published attributes: Series A, active lifecycle, country of origin Mexico, UPC 612598313716, one year standard warranty. Documentation is 1756-TD005 for the technical data and 1756-SG001 for the selection guide; the certification entry recorded is China CCC as of 2026-08-11.
| 1756-PA75R | AC redundant supply, 120/240 V AC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PB75R | DC redundant supply, 24 V DC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PAXT | XT AC supply, 8 A at 5.1 V DC, 42 W at -25 to +70 C | IN STOCK |
| 1756-PBXT | XT DC supply, 10 A at 5.1 V DC, 52 W at -25 to +70 C | IN STOCK |
| 1756-PAXTR | XT AC redundant supply, 42 W, 0-60 C in a non-XT chassis | IN STOCK |
| 1756-PA75 | Non-redundant AC supply, single, 13 A at 5.1 V DC, 75 W | IN STOCK |
Application | Chassis Power |
Brand Name | Rockwell (Rockwell) |
Cat Num | 1756-PAR2 |
Communication | — |
Display | — |
Enclosure | None (open-style) |
Interface | Backplane, via 1756-PSCA2 |
Mounting | Remote, cable-connected |
Number Of Channels | — |
Standard | CE, UL, RCM, EAC, Morocco DOC |
Sub Brand | ControlLogix |
Type | Redundant Power Supply |
UNSPSC | — |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN620 (redundant power supply instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Bundles are specified for new builds and for renewals where the whole redundant feed is being replaced. One line on the bill of materials, one lead time, one warranty start — against four part numbers that each have their own availability and their own risk of arriving short.
In a critical rack the AC bundle is the default choice: 85-265 V AC input accepts 120 V and 240 V supplies on either side of the Atlantic without a transformer tap decision, and the two supplies share the rack current so a single failure is invisible to the process.
Because the supplies are remote, the bundle also decouples the power source from the chassis thermal design. Heat from the supplies stays out of the rack, which is what allows the 0…60 °C chassis rating to be reached in a dense panel.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Cables are in the box | Rockwell states connection cables included. Confirm what the supplier ships, because a bundle missing the cables behaves like a kit with a missing part — the chassis adapter has nothing to connect. |
| Check 3 | 13 A, capped at 15 A | The pair is rated 13 A at 5.1 V DC; the adapter passes at most 15 A to the backplane. Load budget is the lower of the two rules that applies to your chassis. |
| Check 4 | Chassis series | The AC redundant assembly is published against 1756-A4/B, A7/B, A10/B, A13/B and A17/B — the /B series. A /A or /C chassis needs a different supply pairing (1756-IN620). |
| Check 5 | Remote mounting | The supplies are mounted remotely in the enclosure and cabled to the adapter in the chassis. The enclosure layout, not the chassis slot, decides cable length, and 0.91 m is the standard length. |
| Check 6 | Adapter still excluded | The redundancy claim covers the supplies only; the adapter and cables are excluded. A bundle does not change that engineering statement, it only delivers the pieces together. |
Installation checks per Rockwell publication 1756-IN620, which covers adapter mounting, cable seating, load sharing, fusing and the chassis compatibility table and 1756-IN050.
The DC counterpart is 1756-PBR2: a 19-32 V DC redundant assembly with the same cable-included bundle structure and the same 13 A at 5.1 V DC pair rating. Choosing between them is a decision about the plant's DC or AC distribution, not about the rack.
A single failed supply inside an installed bundle is replaced with 1756-PA75R. The adapter is 1756-PSCA2 and the cable 1756-CPR2 (0.91 m), so the components remain individually available even though the assembly ships as a bundle.
For XT enclosures the redundant AC parts are 1756-PAXTR / 1756-PBXTR with the 1756-PSCA2XT adapter, rated 0…60 °C when used in a non-XT chassis. The PAR2 does not extend an XT rating.
What is included in a 1756-PAR2?
Rockwell describes it as a ControlLogix Power Supply Bundle — an 85-265 V AC redundant power supply assembly — and lists the connection cables as included. It is the complete redundant AC feed in one catalogue number.
How much current does the assembly deliver?
13 A at 5.1 V DC, 4 A at 3.3 V DC, 1.5 A at 1.2 V DC and 2.8 A at 24 V DC for the pair, carried on the bundle part number; the 1756-PSCA2 adapter passes up to 15 A at 5.1 V DC to the backplane.
Which chassis does it fit?
The 1756-A4/B, A7/B, A10/B, A13/B and A17/B series chassis, the same list published for the 1756-PA75R supply in 1756-IN620.
Why buy the bundle instead of two supplies and an adapter?
Because the cables ship with it. Ordered separately, the supplies, adapter and 1756-CPR2 cables are four lines with independent availability, and a missing cable blocks the installation.
Is the adapter covered by the redundancy?
No. The installation instructions exclude the chassis adapter and the power supply cables from the redundancy claim — a bundle delivers them together but does not change that statement.
What happens if one supply fails?
The remaining supply carries the whole chassis load without disruption. The failure is visible only through the annunciator contacts, which are user-wired up to 10 m (32.8 ft) and are the reason to wire them.
Can the two supplies be different?
AC and DC supplies can be mixed in tandem in the redundant system, but a bundle is supplied as a matched AC pair. A mixed arrangement is a site decision, and the adapter and cable rules apply unchanged.
What lifecycle and documentation data is published?
Active lifecycle, Series A, country of origin Mexico, UPC 612598313716, one year standard warranty; technical data in 1756-TD005 and selection guidance in 1756-SG001.
Is there a DC version?
Yes — 1756-PBR2, a 19-32 V DC redundant power supply assembly, again with the connection cables included and the same 13 A at 5.1 V DC pair rating.
Data sources. Technical values on this page come from Rockwell publications 1756-IN620 (ControlLogix Redundant Power Supply, installation instructions), 1756-IN619 (ControlLogix Power Supply installation instructions) and 1756-TD005 (ControlLogix power supply technical data) and the manufacturer's product page for 1756-PAR2. Values re-checked 15 November 2026.