The 1756-PA75R (also written 1756PA75R) is the AC member of the ControlLogix redundant power supply pair: a 120/240 V AC supply that puts 5.1 V DC at 13 A onto the backplane and is designed to share the chassis load with a second supply rather than to run alone. Rockwell describes it as a 85-265 V AC redundant supply with a 75 W maximum output across 0…60 °C, connected to the chassis through a 1756-CPR2 cable (1756-IN620).
The architecture is what separates it from a 1756-PA75. Two supplies are mounted remotely, both feed one passive 1756-PSCA2 chassis adapter, and the adapter funnels the combined power into the single power connector on the chassis backplane. If one supply fails, the remaining supply takes the whole chassis load without interrupting chassis activity. The published limitation is equally explicit: the redundancy is designed around the power supply itself, not around the adapter or the cables.
Electrical and physical data: 120/240 V AC nominal input with an 85 V minimum at 50 Hz and 60 Hz, 120 VA / 115 W maximum input power, 20 A maximum inrush, 5.1 V DC output at 13 A with 4 A available at 3.3 V DC, 75 W maximum power output, 1.45 kg, 175 mm high by 145 mm wide by 137 mm deep. Operating range 0…60 °C, 5…95% relative humidity non-condensing, 30 g operating shock and 2 g vibration at 10…500 Hz.
| 1756-PA75R | AC redundant supply, 120/240 V AC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PB75R | DC redundant supply, 24 V DC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PAXT | XT AC supply, 8 A at 5.1 V DC, 42 W at -25 to +70 C | IN STOCK |
| 1756-PBXT | XT DC supply, 10 A at 5.1 V DC, 52 W at -25 to +70 C | IN STOCK |
| 1756-PAXTR | XT AC redundant supply, 42 W, 0-60 C in a non-XT chassis | IN STOCK |
| 1756-PA75 | Non-redundant AC supply, single, 13 A at 5.1 V DC, 75 W | IN STOCK |
Application |
Chassis Power |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-PA75R |
Communication |
— |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Backplane, via 1756-PSCA2 |
Mounting |
Remote, cable-connected |
Number Of Channels |
— |
Standard |
CE, UL, RCM, EAC, Morocco DOC |
Sub Brand |
ControlLogix |
Type |
Redundant Power Supply |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN620 (redundant power supply instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Specify the pair where a process cannot stop for a power supply: a line controller running a continuous process, or a cell whose restart costs more than the second supply. Both supplies are remote-mounted, so the electrical enclosure can be laid out with the supplies on a DIN rail or a plate and only the adapter in the chassis slot.
The supply is AC (120/240 V AC), which makes it the usual choice in a plant with a 120 V or 240 V control bus. It carries no hazardous-location approval of its own — IN620 lists 1756-PA75R as ATEX “None" — so a classified-area installation depends on the rest of the assembly, in particular the 1756-PSCA2 adapter, which is certified Ex nA IIC T4 Gc (DEMKO13ATEX1325026X, IECEx UL 14.0008X).
Because the output is 75 W at 5.1 V DC, the design check is a power budget rather than a current guess: add the 5.1 V, 3.3 V, 1.2 V and 24 V draws of every module in the chassis, keep the total inside 75 W, and confirm the single-supply case still holds — that is the case the pair is bought for.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Cable seating | Verify both 1756-CPR2 connections at the adapter and at the supply. Power down first — an arc at an unmated redundant cable is a hazard in a classified area. |
| Check 3 | Load sharing | Compare the two supplies under load. Unequal sharing points at a cable, a connector or a failing supply rather than at the chassis. |
| Check 4 | Annunciator contacts | If the annunciator wiring is used, confirm it is within the 10 m (32.8 ft) limit and that it reports the loss of one supply, not just a chassis fault. |
| Check 5 | Fusing | Each ungrounded supply needs its own 15 A time-delay fuse. A shared fuse hides a single-supply failure and lets one supply carry everything silently. |
| Check 6 | Chassis compatibility | 1756-PA75R pairs into A4/B, A7/B, A10/B, A13/B and A17/B chassis. Check the chassis series before ordering: the redundant table is series-specific. |
Installation checks per Rockwell publication 1756-IN620, which covers adapter mounting, cable seating, load sharing, fusing and the chassis compatibility table and 1756-IN050.
The 1756-PA75R is an active catalogue item, so replacement is like for like. What changes in a retrofit is the chassis series: the redundant table in 1756-IN620 pairs PA75R with series B chassis and PB75R with series C chassis, and the XT redundant supplies with the XT chassis list.
If a redundant supply fails in service, replace the supply — not the adapter and not the cable, unless the connector is worn. Worn contacts at the redundant cable connector are called out in IN620 as a source of resistance that affects module operation, so a supply that fails repeatedly is a connector problem first.
For a new design the choice is between AC and DC input rather than between power classes: both 1756-PA75R and 1756-PB75R deliver 75 W at 5.1 V DC and 13 A, and the two can be mixed in one redundant pair — the published system allows an AC supply and a DC supply in tandem.
What is the difference between 1756-PA75R and 1756-PA75?
The redundant supply is built to run in a pair behind a 1756-PSCA2 chassis adapter, with two supplies sharing the chassis load; the 1756-PA75 is a single supply mounted in the chassis. Both are 75 W class with a 5.1 V DC output, and the redundant version lists 13 A at 5 V DC (1756-IN620, product records).
How does the pair actually work?
Two remotely mounted supplies share the current the chassis needs. If one fails, the remaining supply carries the whole chassis load without disrupting chassis activity. The 1756-PSCA2 adapter is passive and funnels power from one or two supplies into the single backplane power connector (1756-IN620).
Can an AC and a DC supply be mixed in one pair?
Yes. IN620 states that the AC supplies (1756-PA75R or 1756-PAXTR) and the DC supplies (1756-PB75R or 1756-PBXTR) can be mixed and matched when used in tandem.
Which chassis accept the 1756-PA75R?
1756-A4/B, 1756-A7/B, 1756-A10/B, 1756-A13/B and 1756-A17/B. The DC version 1756-PB75R lists the series C chassis instead — A4/C through A17/C — so the chassis series decides which redundant supply fits.
What cable and adapter are required?
One 1756-PSCA2 (or 1756-PSCA2XT) chassis adapter per chassis and one cable per supply: 1756-CPR2 at 0.91 m (3 ft), or 1756-CPR2D and 1756-CPR2U. The cable is not optional — it is how the remote supply reaches the adapter.
What are the input and output ratings?
Input 120/240 V AC nominal, 85 V minimum at 50 Hz and 60 Hz, 120 VA / 115 W maximum, 20 A maximum inrush. Output 5.1 V DC at 13 A and 4 A at 3.3 V DC, 75 W maximum at 0…60 °C.
Is the 1756-PA75R certified for hazardous locations?
IN620 lists the 1756-PA75R as ATEX “None" — no ATEX or IECEx protection type of its own. The 1756-PSCA2 adapter and the 1756-PB75R DC supply are the parts in that assembly carrying Ex nA IIC T4 Gc (DEMKO13ATEX1325026X, IECEx UL 14.0008X).
What wiring rules apply?
2.5 mm² (14 AWG) 90 °C copper wire with 1.2 mm maximum insulation, 0.565 N·m (5 lb·in) terminal torque, one conductor per terminal, and a 15 A time-delay fuse in every ungrounded supply. Annunciator wiring is limited to 10 m (32.8 ft), and the 1756-CPR2 connections are wire category 3.
What does redundancy not cover?
The published claim covers the power supply only. The chassis adapter and the power supply cables are excluded, so a failed adapter or a damaged CPR2 cable takes the chassis down even with two healthy supplies — cable and connector condition is part of the maintenance plan, not an accessory detail.
Data sources. Technical values on this page come from Rockwell publications 1756-IN620 (ControlLogix Redundant Power Supply, installation instructions), 1756-IN619 (ControlLogix Power Supply installation instructions) and 1756-TD005 (ControlLogix power supply technical data) and the manufacturer's product page for 1756-PA75R. Values re-checked 15 November 2026.