The 1756-RMC3 (also written 1756RMC3) is the 3 m (9.84 ft) fiber-optic cable that links a pair of ControlLogix redundancy modules — 1756-RM2 or 1756-RM2XT — across the two chassis of a redundant system. It is a real order line, not an accessory included in the box: the module ships with its SFP transceivers installed but with no cable, so the cable is ordered separately with its own catalogue number (1756-IN087).
The assembly is 8.5/125 µm single-mode fiber with LC duplex connectors, specified as 1000BASE-LX: 1310 nm, 1000 Mbps transmission, one channel of transmit and receive fibre, and a published maximum link length of 10 km. The same cable family is offered in three lengths — 1756-RMC1 at 1 m, the 1756-RMC3 at 3 m and 1756-RMC10 at 10 m — and the SFP transceiver in the module is Rockwell part PN-91972, an LC duplex 1000BASE-LX device.
Two engineering details decide whether the cable works. First, the module carries a single-mode transmitter, so connecting it to a multimode port can damage multimode devices. Second, the modules sit at the bottom of the chassis facing down, and the space between the transmit and receive connectors is sized for an LC coupler — that coupler keeps the fibre from bending and lets the cable be connected or disconnected without pulling the module out of the chassis.
| 1756-RMC1 | Redundancy fiber-optic cable, 1 m (3.28 ft) | IN STOCK |
| 1756-RMC3 | Redundancy fiber-optic cable, 3 m (9.84 ft) | IN STOCK |
| 1756-RMC10 | Redundancy fiber-optic cable, 10 m (32.81 ft) | IN STOCK |
| 1756-RM2 | Redundancy module, standard temperature, 1.16 A at 5.1 V DC | IN STOCK |
| 1756-RM2XT | Redundancy module, XT, -25 to +70 C | IN STOCK |
| 1756-L61 | ControlLogix 5560 controller, 2 MB | IN STOCK |
Application |
Redundancy (ControlLogix) |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-RMC3 |
Communication |
Fiber-optic, 1000BASE-LX |
Display |
— |
Enclosure |
None (open-style) |
Interface |
LC duplex |
Mounting |
Between 1756-RM2 / RM2XT modules |
Number Of Channels |
1 (transmit and receive fibre) |
Standard |
— The UL, ATEX and IECEx listings are held by the 1756-RM2 / RM2XT module pair; no separate listing is published for the cable. |
Sub Brand |
ControlLogix |
Type |
Redundancy Fiber-optic Cable |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN087 (ControlLogix redundancy modules). Certification details, with certificate and file numbers, are listed in the FAQ below.
The cable is specified by the distance between the two chassis, not by the controller: a redundant ControlLogix system keeps one controller in each chassis, the two redundancy modules bridge the pair, and the controllers exchange control data and synchronise their operation across that bridge. One 1756-RMC3 therefore serves one module pair — that is the whole redundant link.
In a panel built as two adjacent enclosures the RMC3 is the length most often drawn, because it covers the gap between cabinets without leaving a coil of spare fibre inside a wireway. Where the chassis sit in the same enclosure the RMC1 is enough; where they are separated by a wall or a floor, the RMC10 is the published option.
Media redundancy is a separate layer from the redundancy module pair: to survive a cable fault you install modules with redundant ports and run a redundant fibre system, routing trunk A and trunk B apart so that one event cannot take both. Keep that separation in the drawing as well as in the panel — a single tray carrying both trunks defeats the design.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Field check 2 | Inspect the LC coupler | The coupler must be seated between the transmit and receive connectors; an unseated coupler is the usual cause of a link that works on the bench and fails in the panel. |
| Field check 3 | Check the bend radius | Any tight bend left in the route is permanent loss. Re-route rather than re-terminate: the assembly is factory-terminated single-mode fibre. |
| Field check 4 | Verify the fibre type | Single-mode 8.5/125 µm only. A multimode patch cord substituted on site can damage the module transmitter, not just lose the link. |
| Field check 5 | Check the module pair | 1756-RM2 modules pair only with 1756-RM2 modules, and 1756-RM2XT with 1756-RM2XT. A mixed pair is not a supported configuration. |
| Field check 6 | Check the chassis type | XT modules must be in an XT chassis. An XT redundancy module in a standard chassis is outside the published mounting configuration. |
Field checks assembled from Rockwell publication 1756-IN087, which covers the cable route, the LC coupler, the fibre type and the module-pair rules and 1756-IN050.
Treat the cable as a line item in the redundancy bill of materials. It is not interchangeable with a generic LC patch cord: the assembly is single-mode 8.5/125 µm with a factory LC duplex termination, and the module's transmitter is single-mode.
If a cable is damaged, replace the whole RMC3 assembly rather than splicing in the tray. The optical path is part of the validated redundancy design, and a splice in the trunk changes the loss budget without changing the drawing.
The redundancy modules themselves are the other half of the pair. Keep the same catalogue number, series and revision on both sides of the link — the redundant system is published as a matched pair of modules, not as two independent spares.
What does the 1756-RMC3 actually connect?
Two ControlLogix redundancy modules — 1756-RM2 or 1756-RM2XT — one in each chassis of a redundant pair. The redundant pair bridges the two chassis so that the controllers can exchange control data and synchronise their operation (1756-IN087).
Is the fiber cable included with the redundancy module?
No. The cable is not included with the module and is ordered separately. The module arrives with its SFP transceivers pre-installed; publication 1756-IN087 states explicitly that the 1756-RMCx cable must be ordered separately.
What lengths are available?
1756-RMC1 at 1 m (3.28 ft), 1756-RMC3 at 3 m (9.84 ft) and 1756-RMC10 at 10 m (32.81 ft). The published maximum link length for the module pair is 10 km, which is far beyond any of the three cable options.
What fibre and connector type is it?
8.5/125 µm single-mode fiber with LC-type connectors, one channel of transmit and receive fibre, 1000 Mbps transmission at 1310 nm, 1000BASE-LX compliant. The module's SFP is Rockwell part PN-91972 with an LC duplex connector (1756-IN087 specifications, with the corresponding data in 1756-TD001).
Can a multimode patch cord be used instead?
No. The redundancy module contains a single-mode transmitter, and connection to a multimode port can damage multimode devices. The published cable is single-mode 8.5/125 µm for that reason, not as a preference.
How should the two trunk cables be routed?
Route trunk A and trunk B separately so that damage to one cable does not damage the other. Redundant cabling tolerates one or more faults on a single channel; if both channels fault, network operation becomes unpredictable.
Why is there an LC coupler at the module?
The transmit and receive connectors are spaced so that an LC connector coupler can be used. The coupler keeps the fibre from bending and allows the cable to be connected and disconnected without removing the module from the chassis.
Which modules and chassis pair with this cable?
1756-RM2 with 1756-RM2, or 1756-RM2XT with 1756-RM2XT — the two types are not mixed. XT modules must be installed in a ControlLogix-XT chassis, and each module draws 1.16 A at 5.1 V DC and 3.4 mA at 24 V DC, dissipating up to 6 W (1756-TD001).
Does the cable need its own certification?
No separate listing is published for the cable. The UL, ATEX and IECEx approvals are held by the 1756-RM2 and 1756-RM2XT modules (ATEX certificate UL22ATEX2818X, UKEX UL22UKEX2604X, IECEx UL 22.0063X, type of protection Ex ec IIC T4 Gc), and the cable is part of that assembled system.
Data sources. Technical values on this page come from Rockwell publications 1756-IN087 (ControlLogix Redundancy Modules, installation instructions) and 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and the manufacturer's product page for 1756-RMC3. Values re-checked 15 November 2026.