Product Details:
Payment & Shipping Terms:
|
The 1756-DNB (also written 1756DNB) is the ControlLogix DeviceNet scanner: one DeviceNet port in a single-slot module, up to 64 nodes on the segment, and 125/250/500 Kbps at 500/250/100 m maximum cable length.
Published figures are 400 mA at 5.1 V DC and 0 mA at 24 V DC from the backplane, a separate 60 mA at 24 V DC on the DeviceNet side, 11…25 V DC Class 2/SELV network voltage, 3.5 W power dissipation and 11.9 BTU/hr thermal dissipation. Isolation is 50 V continuous basic between the DeviceNet network and the backplane, type tested at 853 V AC for 60 s, with no isolation between USB and the backplane. The module fits 1756-A4, A7, A10, A13 and A17 chassis and runs from the standard 1756-PA72/C, PA75/B, PB72/C, PB75/B, PC75/B or PH75/B supply, or the redundant 1756-PA75R / PB75R pair with a 1756-PSCA2 adapter (1756-TD003).
1756-DNB |
DeviceNet scanner, 64 nodes, 400 mA at 5.1 V DC, 3.5 W |
In stock |
1756-DNBK |
Conformal-coated 1756-DNB, same electrical specification |
In stock |
1756-CN2R |
Redundant ControlNet bridge, where the segment is remote |
In stock |
1756-EN2T |
EtherNet/IP bridge, for gateway-based DeviceNet access |
In stock |
1756-DHRIO |
DH+ and remote I/O scanner, a different network |
In stock |
Application |
DeviceNet scanner |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-DNB |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-DNB |
Mounting |
Chassis |
Number Of Channels |
1756-DNB |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
A DeviceNet segment is a field network, so the scanner's job is to stand between the rack and devices that were installed years before the ControlLogix upgrade. That is the case the 1756-DNB is usually bought for: a line with DeviceNet valves, drives or photoeyes that has to be brought into a Logix controller without rewiring the segment.
One slot and 3.5 W is a small footprint for 64 nodes. The constraint is rarely rack space; it is the segment itself, where every device has an address, a baud rate and a supply of its own, and where the scanner is the only element that sees all three at once.
Where the devices are already Ethernet-capable, a gateway off an existing 1756-EN2T costs no scanner slot and no second network to maintain; where the segment is large and its devices are not replaceable, the dedicated scanner remains the cleaner engineering answer.
A scanner has no status display that can be read from a drawing; its limits are the numbers that decide whether a segment will run. Every row below is quoted from the module specification 1756-TD003.
| Indicator | State | Meaning and first action |
| Data rate and cable length | 125 Kbps / 500 m; 250 Kbps / 250 m; 500 Kbps / 100 m | Rate and distance are one decision, not two; the published maximum applies to the trunk length of the segment. |
| Current at 5.1 V DC | 400 mA | Backplane draw of the scanner itself. Sum it with the rest of the rack against the chassis 5.1 V budget. |
| Current at 24 V DC | 0 mA | The scanner takes no 24 V from the backplane. |
| DeviceNet current at 24 V DC | 60 mA | Drawn from the DeviceNet network supply, which must stay inside 11…25 V DC Class 2/SELV. |
| Power dissipation | 3.5 W | 11.9 BTU/hr; part of the enclosure thermal load. |
| Isolation | 50 V continuous, basic; DeviceNet to backplane | Type tested at 853 V AC for 60 s; no isolation between USB and the backplane. |
| Slot and chassis | 1 slot; 1756-A4 / A7 / A10 / A13 / A17 | Any chassis in the standard range; the XT chassis use the XT communication modules instead. |
| Power supply | 1756-PA72/C, PA75/B, PB72/C, PB75/B, PC75/B, PH75/B | Redundant option: 1756-PA75R / PB75R with the 1756-PSCA2 chassis adapter. |
Node count, data rates, current draw, dissipation and isolation per Rockwell publication 1756-TD003 (1756 ControlLogix Communication Modules Specifications), Table 10 and 1756-IN050.
The 1756-DNB has no direct ControlLogix successor for every case: a DeviceNet segment either keeps a scanner in the rack or is migrated device by device to EtherNet/IP. The practical replacement question is therefore whether the segment stays.
If it stays, the scanner is replaced like for like and the configuration is restored from the project; if it migrates, the rack needs a 1756-EN2T or 1756-EN2TR and the devices need Ethernet interfaces, which is a field change, not a rack change.
The 1756-DNBK is the same module with conformal coating, for panels where condensation or corrosive atmosphere is the reason the rack is coated in the first place.
How many DeviceNet nodes can the 1756-DNB handle?
Up to 64 nodes on the segment (1756-TD003).
What data rates and cable lengths are supported?
125 Kbps at 500 m maximum, 250 Kbps at 250 m, and 500 Kbps at 100 m.
How much backplane current does it draw?
400 mA at 5.1 V DC and 0 mA at 24 V DC; a separate 60 mA at 24 V DC comes from the DeviceNet network supply.
What DeviceNet supply voltage is required?
11…25 V DC, Class 2 or SELV, at the segment.
What is the power and thermal dissipation?
3.5 W and 11.9 BTU/hr maximum.
What isolation is specified?
50 V continuous basic insulation between the DeviceNet network and the backplane, type tested at 853 V AC for 60 s; there is no isolation between USB and the backplane.
Which chassis and power supplies are listed?
1756-A4, A7, A10, A13 and A17 chassis with the 1756-PA72/C, PA75/B, PB72/C, PB75/B, PC75/B or PH75/B supply, or the redundant 1756-PA75R / PB75R pair with a 1756-PSCA2 adapter.
Can it be used in an XT rack?
Not directly: the XT chassis publish their own XT module list in 1756-TD003, and the standard 1756-DNB is listed against the standard 1756-A4…A17 chassis only.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (1756 ControlLogix Communication Modules Specifications) and the manufacturer's product page for 1756-DNB. Values re-checked 16 November 2026.