The 1794-OM8 drives eight 240V AC loads at 500 mA per channel and 4.0 A for the module, with 2.5 mA leakage, 1.5V drop and 5 W dissipation.
It is the 240V counterpart of the 120V AC output card: same point count, same current class, a different load voltage window and a different isolation statement in the publication.
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA8I | 8-point 120V AC input module, 1240V isolation | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IA16K | 16-point 120V AC input module, conformal coated | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-OA8 | 8-point 120V AC output module | IN STOCK |
| 1794-OA8I | 8-point 120V AC isolated output module | IN STOCK |
| 1794-OA8K | 8-point 120V AC output module, conformal coated | IN STOCK |
| 1794-OA16 | 16-point 220V AC output module | IN STOCK |
| 1794-OA16K | 16-point 220V AC output module, conformal coated | IN STOCK |
| 1794-OM8 | 8-point 240V AC output module | IN STOCK |
| 1794-OM16 | 16-point 240V AC output module | IN STOCK |
Application |
FLEX I/O digital output, 1794 terminal base |
Cat Num |
1794-OM8 |
Brand Name |
Rockwell |
Outputs |
8, AC |
Output current |
500 mA per channel; 4.0 A per module |
Off-state leakage |
2.5 mA maximum |
On-state voltage drop |
1.5V at 0.5 A |
Surge current |
7 A for 40 ms |
Isolation |
250V basic; 1250V AC for 60 s |
Power dissipation |
5 W (17.1 BTU/hr) |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Eight AC outputs, 500 mA per channel, 4.0 A per module, with 2.5 mA maximum off-state leakage and 1.5V drop at 0.5 A.
7 A surge for 40 ms covers the inrush of a 240V solenoid or a small contactor coil.
5 W (17.1 BTU/hr) is the module heat, higher than the 120V card's 4.1 W because of the higher blocking voltage in the output stage.
2.5 mA leakage at 240V is a larger volt-ampere product than at 120V, so the bleeder calculation matters more, not less.
Because the card publishes 250V basic insulation, the 240V statement in the panel drawing and the card's rating have to agree before the load is landed.
An eight-point 240V card and an eight-point 120V card are indistinguishable from the front, so the base label carries the information that prevents a wrong substitution.
The fused base turns a blown output into a fuse change, which is a five-minute job rather than a card swap and a re-termination of eight conductors.
Field failures on 240V outputs are usually leakage or an unsuppressed coil, and both are resolved at the load rather than at the card.
250V basic insulation, tested at 1250V AC for 60 s is what the publication states for this card.
Read that against the load voltage: 240V AC on a 250V basic insulation rating is a control-circuit product, not a distribution product.
The isolation is field to system; channels share a common, as on every card in the AC output line.
Type tested, not routine tested. Nobody proves the barrier on the bench before shipping; the certificate covers the design.
Minimum load and leakage are the two limits that produce most field complaints: a 240V relay that buzzes or fails to release is usually seeing leakage rather than a failed output.
A bleeder resistor across the coil fixes both the minimum-load and the leakage problem for a few watts of standing loss.
Suppression at the coil is still required; the triac does not enjoy switching an unsuppressed inductor at 240V.
0...55 deg C operating range and 5 W of module heat belong in the enclosure calculation alongside the adapter.
Field terminals on the 1794 base, with the fused variants where the panel requires protection at the terminal.
Keying first, FlexBus connector fully left, pins inspected, groove aligned, latch locked — the five steps from 1794-IN093.
Keep 240V conductors separated from the FlexBus and network cabling, and from analog signals, in their own duct.
Label the load voltage on the base, because a 240V card and a 120V card look identical from the front and only the label prevents a wrong substitution.
240V panels with eight loads — solenoid valves, contactor coils, fan starters and 240V lamps.
Retrofit work. An existing 240V relay panel comes out and the loads land on one card with no new power supply.
Not for 120V circuits. The isolation and load voltage statements are for the 240V class; use 1794-OA8 for 120V.
How many outputs has the 1794-OM8?
Eight 240V AC outputs at 500 mA per channel and 4.0 A per module.
What isolation is published?
250V basic insulation, tested at 1250V AC for 60 s field to system.
What is the off-state leakage?
2.5 mA maximum, so a light relay coil may need a bleeder resistor to release.
What surge can it carry?
7 A for 40 ms.
What is the module dissipation?
5 W, equal to 17.1 BTU/hr.
What temperature range applies?
0...55 deg C operating.
1794-OM8 is the eight-channel AC member of the four AC and relay output modules on this site, and it is the one whose record prints the fewest of the rows the others carry. The two tables below hold the four side by side, with the absent rows left as absent rather than filled in.
| Catalog number | Outputs | Load window as printed | Per-channel and module current | Isolation as printed | Fuse as printed |
|---|---|---|---|---|---|
| 1794-OA8I | 8, AC | 85 V AC to 132 V AC | 5 mA minimum; 500 mA per channel at 55 C and 750 mA at 35 C; 4.0 A per module | 2150 V DC for 1 s; 1250 V AC for 60 s | 1.6 A 250 V slow-blow |
| 1794-OA16 | 16, AC | 159 V AC to 264 V AC | 500 mA per channel at 55 C; 4.0 A per module, printed as 16 x 250 mA | 2600 V DC for 1 s | 2.5 A 150 V M02 |
| 1794-OM8 | 8, AC | not printed on the record | 500 mA per channel; 4.0 A per module | 250 V basic; 1250 V AC for 60 s | not printed on the record |
| 1794-OW8 | 8, Form A normally open relay, isolated | 2 A at 5 to 30 V DC, 0.22 A at 125 V DC, 2 A at 125 V AC, 2 A at 250 V AC | a contact rating rather than a channel current | 250 V basic relay to relay, to backplane and to power; 1500 V AC 60 s, 3250 V DC 60 s | 3.0 A 250 V slow-blow |
| Catalog number | Operating temperature as printed | Power dissipation | Leakage or off-state | Surge as printed |
|---|---|---|---|---|
| 1794-OA8I | -20 to 55 C | 4.1 W (14.0 BTU/hr) | 2.25 mA maximum | 7 A for 45 ms, repeatable every 8 s |
| 1794-OA16 | 0 to 55 C | 4.7 W (16.1 BTU/hr) | 2.5 mA maximum | 7 A for 40 ms, repeatable every 8 s |
| 1794-OM8 | 0 to 55 C | 5 W (17.1 BTU/hr) | 2.5 mA maximum | 7 A for 40 ms |
| 1794-OW8 | -20 to 55 C | 5.5 W at 31.2 V DC (18.8 BTU/hr) | 100 uA at 100 mV minimum load | 10 ms on and off delay, 1.2 ms bounce |
The record prints no load-voltage window and no fuse, which between them decide whether the module can be ordered at all: eight AC outputs at 500 mA each with a 4.0 A ceiling is the same arithmetic as the OA8I, but without a voltage window there is no way to tell from this page whether the module belongs on a 120 V system or a 230 V one.
The four cold-temperature floors do not agree inside one family: the OA8I and the OW8 print -20 to 55 C while the OA16 and the OM8 print 0 to 55 C. An unheated cabinet that drops to -10 C can take the first pair and not the second, so the floor has to be checked per module rather than assumed from the 1794 name. The dissipation rows run from 4.1 W to 5.5 W across the same four, which is a second, quieter reason the enclosure size changes when the output type changes.
What the four records do not settle between them: no terminal base compatibility row on any of them, no backplane current draw, no wiring diagram, no statement of which of them can share a base with which adapter, no lifecycle field on any of the four, and no fuse rating at all on the OM8. The load window on the OM8 and the 150 V fuse on the OA16 are the two rows to query before an order rather than after.
Source: the published rows of 1794-OA8I, 1794-OA16, 1794-OM8 and 1794-OW8 as printed on this site - output counts and types, load windows, per-channel and per-module currents, contact ratings, minimum load, on and off delay, bounce, contact resistance, switching frequency, mechanical life, fuses, isolation strings, external supply current, power dissipation, leakage, surge, and operating temperature. Rows a record does not print are marked as not printed rather than filled in; the 93 hour figure for the relay is the published 100,000 operations divided by the published 0.3 Hz.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.