The 1794-OW8 provides eight Form A normally open relay outputs, each isolated from the others, rated 2 A at 250V AC or 2 A at 5...30V DC.
It is the card for loads a semiconductor output cannot switch: AC coils, mixed AC and DC circuits, and anything that needs a hard open contact rather than a solid-state drop.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O relay output, 1794 terminal base |
Cat Num |
1794-OW8 |
Brand Name |
Rockwell |
Outputs |
8, Form A normally open relay, isolated |
Contact rating |
2 A at 5...30V DC, 0.22 A at 125V DC, 2 A at 125V AC, 2 A at 250V AC |
Minimum load |
100 uA at 100 mV |
On/off delay |
10 ms |
Contact resistance |
30 mOhm |
Switching frequency |
0.3 Hz |
Bounce time |
1.2 ms |
Mechanical life |
100,000 operations |
Fuse |
3.0 A 250V slow-blow, Littelfuse 239003 |
Isolation |
250V basic relay to relay, backplane and power; 1500V AC 60 s, 3250V DC 60 s |
External supply current |
125 mA at 24V DC |
Power dissipation |
5.5 W at 31.2V DC (18.8 BTU/hr) |
Operating temperature |
-20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Eight Form A normally open contacts, each isolated from its neighbours and from the backplane.
2 A at 250V AC and 2 A at 125V AC; 2 A at 5...30V DC and 0.22 A at 125V DC — the DC rating falls sharply above 30V, which is the number that catches designs.
Minimum load 100 uA at 100 mV means the contact works with a dry-circuit input, but oxide build-up on a contact that never carries current is still a maintenance item.
Contact resistance is 30 mOhm and bounce time is 1.2 ms, so an input counting the contact sees the bounce unless it filters it.
On and off delay of 10 ms is the module's response, far slower than a solid-state output and the reason this card never drives a fast actuator.
Switching frequency 0.3 Hz — about one operation every three seconds — is the published mechanical limit, not a suggestion.
Mechanical life of 100,000 operations sets the maintenance interval on a contactor that cycles every minute: roughly 69 days of continuous cycling.
A 3.0 A 250V slow-blow fuse (Littelfuse 239003) protects each group, and the replacement part number belongs on the spares list.
250V basic isolation relay to relay, relay to backplane and relay to power, with 50V between power and backplane.
Type tests are 1500V AC for 60 s, 3250V DC for 60 s and 720V DC for 60 s across the three isolation paths.
1.0 mA leakage at 240V AC comes from the snubber across the contact and is what a sensitive input downstream may see as a partial on-state.
-20...55 deg C on the standard version; the 1794-OW8XT publishes -20...70 deg C.
125 mA at 24V DC, 19.2...31.2V range, 5.5 W (18.8 BTU/hr) is the module budget.
Mixed AC and DC loads on one card are allowed because the contacts are isolated; keep the AC and DC wiring in separate bundles anyway.
A snubber or RC network across an AC coil reduces contact erosion, and the 1.0 mA leakage it introduces has to be acceptable to the load's off-state.
Field terminals on the base, and the fuse is socketed on the module for replacement without disturbing the field wiring.
AC coils and mixed circuits that need a dry contact.
Low-frequency switching — 0.3 Hz, 100,000 operations.
Not for fast pulsing; a 10 ms delay and 0.3 Hz limit make a solid-state output the only choice.
Not for high DC voltage; 0.22 A at 125V DC is a small contact rating.
How many outputs has the 1794-OW8?
Eight Form A normally open relay outputs, isolated from each other.
What is the contact rating?
2 A at 250V AC, 2 A at 125V AC, 2 A at 5...30V DC and 0.22 A at 125V DC.
How fast does it switch?
10 ms on and off delay, with a 0.3 Hz switching frequency limit.
What fuse does it use?
A 3.0 A 250V slow-blow fuse, Littelfuse 239003.
What isolation does it provide?
250V basic relay to relay, backplane and power; tested at 1500V AC for 60 s and 3250V DC for 60 s.
What current does the module draw?
125 mA at 24V DC over a 19.2...31.2V range.