logo
Home ProductsAB FlexLogix I/O 1794

Allen Bradley PLC 1794-OB8EP / 1794-OB8EP

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1794-OB8EP / 1794-OB8EP

China Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier
Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier Allen Bradley PLC 1794-OB8EP / 1794-OB8EP supplier

Large Image :  Allen Bradley PLC 1794-OB8EP / 1794-OB8EP

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-OB8EP / 1794-OB8EP

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $158.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-OB8EP technical data PDF download FLEX I/O 1794-OB8EP / 1794OB8EP 8-Point 2 A Fused Output

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-OB8EP is the 8-point electronically fused output: when a channel faults, the module opens that output instead of blowing a fuse, and reports the condition to the processor.

The fuse resets by push button, by software or by cycling the input power, which is the difference a maintenance team notices first.

1794-OB8 8-point 24V DC sourcing output module IN STOCK
1794-OB8EP 8-point 2 A electronically fused sourcing output module IN STOCK
1794-OB16 16-point 24V DC sourcing output module IN STOCK
1794-OB16P 16-point protected sourcing output module IN STOCK
1794-OB16D 16-point diagnostic 24V DC output module IN STOCK
1794-OB32P 32-point protected sourcing output module IN STOCK
1794-OB16PXT 16-point protected sourcing output, extended temperature IN STOCK
1794-OB8EPXT 8-point 2 A electronically fused output, extended temperature IN STOCK
1794-OV16 16-point sinking output module IN STOCK
1794-OV16P 16-point protected sinking output module IN STOCK
1794-OV32 32-point sinking output module IN STOCK
1794-OC16 16-point 48V DC sourcing output module IN STOCK
1794-OG16 16-point 5V DC sourcing output module IN STOCK
1794-OW8 8-point isolated relay output module IN STOCK

Product Specifications 1794-OB8EP (PDF)
 Application
 FLEX I/O electronically fused sourcing output
 Cat Num
 1794-OB8EP
 Brand Name
 Rockwell
 Number of outputs
 8, sourcing, electronically fused
 Output voltage
 19.2...31.2V DC
 Output current
 2 A per output
 Flexbus current
 73 mA at 5V DC
 External supply
 24V DC, 80 mA
 Enclosure rating
 Ex nA IIC T4 Gc
 Operating temperature
 -20...55 deg C
 Terminal base
 1794-TB2, 1794-TB3, 1794-TB3S

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-OB8EP original product photograph, wide view 1794-OB8EP original product photograph, wide view 1794-OB8EP original product photograph, wide view

How the electronic fuse works

The EP suffix means electronically fused: the output opens on an over-current event and stays open until reset.

Reset is by push button, by software command, or by cycling input power, as the family description states.

Fault status is provided to the processor, so the fault appears in the ladder program rather than only at the panel.

No fuse to replace, which removes a spare-part line from the maintenance list.

Electrical data

2 A per output on 19.2...31.2V DC, with 73 mA Flexbus current and 80 mA from the external 24V supply.

Eight sourcing outputs, driving valves, contactors and lamps directly.

Ex nA IIC T4 Gc protection method with a -20...55 deg C rating, per the 1794-DU001 ratings table.

Base options are 1794-TB2, TB3 and TB3S, the standard 16-terminal patterns.

Comparison with the XT part

The 1794-OB8EPXT covers -20...70 deg C with conformal coating, while this module stops at 55 deg C.

The XT version draws 80 mA Flexbus and 55 mA supply, against 73 mA and 80 mA here.

Both are 2 A per output with electronic fusing, so the choice is the temperature and coating rating.

Pick the standard part unless the enclosure needs the extended range.

Application

Outputs that must recover without a fuse change.

Unattended cells where a fault should self-report and then wait for a commanded reset.

Not where per-channel current must be set below 2 A; the 1794-OB16P gives 500 mA at 16 points.

Not for AC loads.

Where it fits

Fused-output islands in standard-temperature panels.

Panels with a maintenance burden on fuses.

Not the 16-point density.

Not 48V DC; the 1794-OC16 covers that rail.

FAQ — 1794-OB8EP

What does EP mean on the 1794-OB8EP?

Electronically fused: the output opens on fault and reports status to the processor.

How is the fuse reset?

By push button, by software, or by cycling the input power.

What current does each output carry?

2 A on 19.2...31.2V DC.

What are the supply figures?

80 mA from the external 24V supply and 73 mA from the 5V Flexbus.

What is the temperature rating?

-20...55 deg C, Ex nA IIC T4 Gc.

Which bases are used?

1794-TB2, 1794-TB3 and 1794-TB3S.


Data sources. Technical values on this page come from Rockwell publication 1794-DU001 (FLEX I/O and FLEX I/O-XT Modules, protection method and electrical ratings). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Where the 1794-OB8EP sits in the FLEX I/O range

1794-OB8EP is a protected digital DC output with 8 outputs in the FLEX I/O range, rated for 24V DC, non-isolated, protected. It mounts on the 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.

AttributeValue
Catalog number1794-OB8EP
Module typeprotected digital DC output
Points8 outputs
Electrical range24V DC, non-isolated, protected
Terminal base unit1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK
Protection behaviourThe output opens on a fault and the electronic fuse is reset by a push button, by software, or by cycling the input power
Fault reportingFault status is reported to the processor, which is the difference between the EP and the P suffix

FLEX I/O is a backplane-free architecture: the terminal base unit snaps onto the DIN rail to the right of the adapter and the bases plug together to form the backplane. The module then sits on top of the base, so the base is chosen for the field wiring and the module for the signal, and the two are ordered separately.

Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.

One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.

Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.

The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.

Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.