logo
Home ProductsAB PLC-5 Systems

Allen Bradley PLC 1771-IBN / 1771IBN

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1771-IBN / 1771IBN

China Allen Bradley PLC 1771-IBN / 1771IBN supplier
Allen Bradley PLC 1771-IBN / 1771IBN supplier Allen Bradley PLC 1771-IBN / 1771IBN supplier Allen Bradley PLC 1771-IBN / 1771IBN supplier Allen Bradley PLC 1771-IBN / 1771IBN supplier Allen Bradley PLC 1771-IBN / 1771IBN supplier

Large Image :  Allen Bradley PLC 1771-IBN / 1771IBN

Product Details:

Place of Origin: Made in USA
Brand Name: PLC Module
Certification: All goods we supply with 1 year warranty!
Model Number: Allen Bradley PLC 1771-IBN / 1771IBN

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $610.00 (USD/PCS)
Packaging Details: 100% New packaging
Delivery Time: IN STOCK; 2-4 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 2 PCS
Detailed Product Description

1771-IBN technical data PDF download 1771-IBN Rockwell 32 Point DC Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: Bulletin 1771 · PLC-5 input modules

1771-IBN is a 32-point DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. The 32-point series C card is the highest density input in the family and the most restricted in placement: the published table marks it restricted under 1-slot addressing and not compatible under 2-slot.

Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.


Product Specifications 1771-IBN (PDF)
 Catalog number
 1771-IBN
 Product type
 32-point DC input module
 Number of inputs
 32
 Input signal
 Not published
 Module series
 C
 1771 chassis compatibility
 Series B chassis, 1-slot restricted, 2-slot not compatible
 Lifecycle status
 Discontinued
 Discontinued date
 31 December 2013
 Replacement category
 Engineering Replacement
 UPC
 Not published
 Country of origin
 Not published
 Field wiring arm
 1771-WA, 10 terminal

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publication 1771-TD180 (module specifications) and the Rockwell literature library (installation instructions).

1771-IBN 1771-IBN

What the module does in a 1771 rack

1771-IBN is a 32-point DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. The 32-point series C card is the highest density input in the family and the most restricted in placement: the published table marks it restricted under 1-slot addressing and not compatible under 2-slot.

The slot it occupies is one 1771 slot, and the input image it claims is fixed by the module series: 32. That number decides how much of the processor input table the rack consumes, not how many wires the panel brings in.

Signal level is Not published. Nothing in the module is software configurable, so the field device has to match the printed range before the module is ordered.

Wiring, keying and the 1771-WA arm

Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.

Keying bands in the chassis connector must line up with the slots on the module board. 1771 chassis are keyed per module type precisely so a 120 V AC module cannot be pushed into a slot wired for a 24 V DC module.

Backplane current comes from the chassis supply, so the load of every module in the rack has to be added up before a rack is repopulated with these cards.

Because of those restrictions it is usually found in racks that were designed around it from the start, not in racks repopulated later.

Chassis compatibility and addressing

Chassis compatibility is published per module series: Series B chassis, 1-slot restricted, 2-slot not compatible. Series A modules fit the superseded 1771-A1, -A2 and -A4 chassis as well as the current A1B to A4B and AM1/AM2 chassis.

Some 32-point and isolated cards can only be placed under 1-slot or 2-slot addressing rules, so the addressing mode of the chassis has to be confirmed before a mixed rack is built.

Lifecycle and replacement

Rockwell lists 1771-IBN as Discontinued, replacement category Engineering Replacement.

The published discontinued date is 31 December 2013.

The family replacement path is a 1756 or 1794 migration, which means the field wiring, the wiring arms and the addressing scheme all change. Buying the same catalog number is usually cheaper than re-terminating a panel.

Plan a replacement rack for fewer points per card: the 1756 equivalents do not map one-to-one onto a 32-point 1771 slot.

Buying a used module

Ask for a photo of the label side and the wiring arm. A module removed without its arm has to be re-keyed and re-wired, which is where most of the cost of a used card actually sits.

Check the module series letter against the chassis series: an A-series card in an A1B chassis works, but the reverse combination is what produces "module not recognised" faults.

These are static-sensitive cards. A unit shipped loose without conductive foam is a risk, whatever the price.

FAQ — 1771-IBN

How many inputs does 1771-IBN have?

32, on the published 1771 data sheet.

What input signal does 1771-IBN accept?

Not published.

Which 1771 chassis will accept 1771-IBN?

Series B chassis, 1-slot restricted, 2-slot not compatible.

Is 1771-IBN still available from Rockwell?

No. It is listed as Discontinued with replacement category Engineering Replacement.

What is the discontinued date of 1771-IBN?

31 December 2013.


Data sources. Point counts, input signal ranges and chassis codes come from the 1771 technical data sheets (1771-TD180 for DC, 1771-TD041 and 1771-IN082 for the 24 V AC module, 1771-IN046 and 1771-IN051 for analog); lifecycle dates, UPC and country of origin come from the Rockwell product page for the catalog number. Where Rockwell has withdrawn the catalog page, the field is marked Not published rather than guessed. Any attribute a publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Where this 1771 module sits in the family: signal class, point count, one slot each

Forty-one 1771 input catalogues resolve into nine signal classes, and the class decides more than the part number does: it fixes which field voltages are possible, which module can be isolated, and - with the point count - how much of the processor input image the rack spends. The table below is the class view rather than a list of forty-one part numbers.

Signal classCatalogues and point counts in this classRange printed for the class
120 V AC / AC-DC1771-IA (8), 1771-IAD (16), 1771-ID (6, isolated), 1771-ID16 (16, isolated)IA 87...138 V AC and 97...138 V DC; IAD and ID16 120 V AC; ID accepts 120 V AC or 120 V DC
24 V DC, standard1771-IB (8), 1771-IBD (16), 1771-IBN (32), 1771-IQ16 (16, isolated), 1771-IQ (8, selectable)IB 10...27 V DC (12...24 V nominal); IBD 10...30 V DC; IQ 5...30 V DC selectable; IQ16 24 V DC isolated
24...48 V DC wide range1771-IH (8)24...48 V DC on one module
48 V DC1771-IC (8)42...56 V DC, 48 V DC nominal
24 V AC1771-IN (8), 1771-IND (16)IN 24 V AC at 47...63 Hz, 12...28 V AC on-state
TTL1771-IG (8), 1771-IGD (16)TTL level DC
Analog voltage / current1771-IFE, 1771-IFF (16 single-ended / 8 differential), 1771-IFMS (8), 1771-IL (8 fully isolated)IFE voltage or current set per input by configuration jumper; IFF +1...5 / 0...5 / -10...10 V DC; IL adds +4...20 mA and 0...20 mA ranges with full isolation
Temperature1771-IR (6 RTD, 3-wire), 1771-IXE (8 TC/mV), 1771-IXHR (8 TC/mV high resolution)RTD 3-wire; thermocouple and millivolt
Controller / driver logic1771-LC3B loop controller, 1771-IV driver logicAnalog loop control in one slot; driver logic level input

Where this page sits: 1771-IBN is the 32-point 24 V DC input in the 24 V DC, standard class, with 32 points at 24 V DC. Reading the class table under this paragraph is what stops a wrong order: the class decides which field voltages are possible at all, and the point count then decides how much of the input image the rack spends. Only two catalogues reach 32 points on one slot, 1771-IBN (24 V DC) and 1771-IAN, and the signal range of the second is not printed in the source used here - the module is sold as a 32-point input, not as a documented 24 V DC one. Isolation inside the class is confined to 1771-IQ16 and 1771-IQ, which is what a panel mixing separate field supplies has to look for before ordering.

Three mechanical facts apply to every module in the table. Each occupies one 1771 slot in a PLC-5 or PLC-2 chassis, so the module count and the slot count are the same number. Field wiring lands on the 1771-WA 10-terminal wiring arm, which swings up to the module so the arm can stay wired while a module is swapped - that is the feature that makes a failed input module a five-minute replacement rather than a re-termination. And keying bands in the chassis connector must be set to match the module, because the chassis connector is the same shape for modules of different signal classes and only the keying stops a 120 V AC module being plugged into a slot wired for 24 V DC.

Two limits of the published data are left as gaps rather than filled. The withdrawn variant catalogues (1771-IA2, 1771-IADK, 1771-IBDK, 1771-IDK, 1771-IM and 1771-IXEK) no longer have a Rockwell catalog page, so their own point count and signal range are not published and this table quotes the base part instead. And the number of input-image words a module consumes is printed per module series in 1771-TD180 rather than in this summary, so the image budget for a rack has to be added up from that publication, not from the point counts here.

Product type, point count and signal range per the 1771 technical data sheets (1771-TD180 for DC, 1771-TD041 and 1771-IN082 for 24 V AC, 1771-IN046 and 1771-IN051 for analog) and 1785-SG001, as transcribed on this page.

Related numbers

Related models, options and spare parts for this range are listed in the Allen-Bradley PLC-5 systems and 1771 I/O category.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)