Product Details:
Payment & Shipping Terms:
|
The 1794-IE4XOE2XT is the extended-temperature version of the four-in/two-out analog module, rated -20...70 deg C and conformally coated, with the same 256 us input conversion.
The electrical behaviour is unchanged from the standard card; what changes is the operating window and the coating, which is what an outdoor or unheated panel actually needs.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O analog combination, 1794 terminal base |
Cat Num |
1794-IE4XOE2XT |
Brand Name |
Rockwell |
Channels |
4 inputs and 2 outputs, individually configurable |
Input ranges |
0...20 mA, +/-10V DC |
Input conversion |
256 us for all channels |
Input step response |
18.2 ms current, 9.4 ms voltage |
Input impedance |
238 Ohm current, 100 kOhm voltage |
Output resolution |
12 bits plus sign |
Output conversion |
Pulse-width modulation, 1.024 ms |
Output step response |
24 ms to 63% of full scale |
Accuracy |
0.20% input, 0.425% current output, 0.133% voltage output, at 25 deg C |
External supply current |
70 mA at 24V DC |
Power dissipation |
4.0 W at 31.2V DC (13.6 BTU/hr) |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
-20...70 deg C operating range is the entire difference that matters at the specification stage; the standard card stops at 55 deg C.
Conformal coating protects the board through condensation cycles at cold start, which is the failure mode the standard card does not cover.
Four inputs at 256 us conversion — the fastest analog input in the line, at either temperature rating.
Two outputs at 12 bits plus sign, PWM at 1.024 ms, 24 ms step response carry over unchanged.
0.20% input and 0.425%/0.133% output accuracy at 25 deg C are the same published figures.
0...20 mA or +/-10V inputs, individually configured, with 238 Ohm current impedance and 100 kOhm on voltage.
Normal mode rejection at -15.3 dB on current and -10 dB on voltage at 50 Hz is modest; keep the input wiring away from drive feeders.
15...750 Ohm on the current output and 3 mA maximum on voltage remain the output load limits.
Input drift of 0.0407% and 0.0428% per deg C is the larger term over a 90 deg C span — at the top of the range it is the dominant error.
70 mA at 24V DC is the consumption, unchanged from the standard card.
4.0 W at 31.2V DC (13.6 BTU/hr) is the heat, and an unheated enclosure has to shed it without a fan.
Storage -40...85 deg C and 5...95% RH non-condensing are the general environmental limits.
75 mm body depth is shared with the standard module, so the base and rail do not change.
Non-isolated channels — input and output commons are separate from each other but not from channel to channel.
Cold-start checks belong in the commissioning sheet: verify each input reading against a known source before the first production run.
Shield at the panel and one signal type per channel, as on every analog card in this family.
Field power removed before insertion, following the FlexBus steps in 1794-IN093.
Outdoor and unheated cabinets where -20 deg C start and +70 deg C internal temperature both occur.
Washdown-adjacent panels that benefit from the conformal coating.
Not for isolated circuits; the 1794-IF2XOF2IXT is the isolated extended-temperature alternative.
Not for low-level sensors; temperature inputs have their own cards.
How does the 1794-IE4XOE2XT differ from the standard card?
It is rated -20...70 deg C and conformally coated; the electrical specifications are the same.
How fast are the inputs?
256 us conversion for all channels, with an 18.2 ms or 9.4 ms step response.
What current does it draw?
70 mA at 24V DC, dissipating 4.0 W at 31.2V DC.
What is the input impedance?
238 Ohm on current and 100 kOhm on voltage.
What load can the outputs drive?
15...750 Ohm on current output and 3 mA maximum on voltage output.
Is it isolated?
No; inputs and outputs share a common with the system.