Product Details:
Payment & Shipping Terms:
|
The 2080-LC20-20AWBR is the same 20-point AC-input Micro820 as the 20AWB, built with removable terminal blocks.
Removable blocks matter on a machine that is serviced in the field: a controller can be swapped without rewiring, and the blocks travel with the harness.
| 2080-LC10-12AWA | Micro810, 8 AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QWB | Micro810, 8 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QBB | Micro810, 8 DC/AC in / 4 DC source out | IN STOCK |
| 2080-LC10-12DWD | Micro810, 8 12V DC in / 4 relay out | IN STOCK |
| 2080-LC20-20AWB | Micro820, 12 AC in / 8 relay out | IN STOCK |
| 2080-LC20-20QWB | Micro820, 12 DC in / 8 relay out | IN STOCK |
| 2080-LC20-20QBB | Micro820, 12 DC in / 8 DC source out | IN STOCK |
| 2080-LC20-20AWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QBBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC30-10QWB | Micro830, 6 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC30-10QVB | Micro830, 6 DC/AC in / 4 DC sink out | IN STOCK |
| 2080-LC30-16AWB | Micro830, 10 AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QWB | Micro830, 10 DC/AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QVB | Micro830, 10 DC/AC in / 6 DC sink out | IN STOCK |
| 2080-LC30-24QWB | Micro830, 14 DC/AC in / 10 relay out | IN STOCK |
| 2080-LC30-24QVB | Micro830, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC30-24QBB | Micro830, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC30-48AWB | Micro830, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QWB | Micro830, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QVB | Micro830, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-24AWB | Micro850, 14 AC in / 10 relay out | IN STOCK |
| 2080-LC50-24QVB | Micro850, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC50-24QBB | Micro850, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC50-48AWB | Micro850, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QWB | Micro850, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QVB | Micro850, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-48QBB | Micro850, 28 DC/AC in / 20 DC source out | IN STOCK |
Catalog number |
2080-LC20-20AWBR |
Family |
Micro820 20-point Ethernet controller |
I/O points |
20 (12 inputs, 8 relay outputs) |
Inputs |
12 inputs, 120 V AC on inputs 4 to 11; inputs 0 to 3 are 24 V DC |
Outputs |
8 relay outputs, 2 A at 240 V AC and 1 A at 24 V DC |
Supply |
24 V DC Class 2, 20.4 to 26.4 V DC |
Communication |
USB 2.0 (USB-C on the 2080-L20E), 10/100 Base-T Ethernet RJ45, RS-232/RS-485 non-isolated combo serial, microSD slot for data logging and recipes |
Plug-in modules |
2 plug-in slots |
Dimensions, H x W x D |
90 x 104 x 75 mm |
Shipping weight |
0.38 kg |
Temperature rating |
-20 to 65 C (-4 to 149 F) |
Power consumption, max |
5.62 W without plug-ins, 8.5 W with |
Lifecycle |
Active |
Removable terminal blocks |
Removable terminal blocks |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-TD001 (module specifications) and 2080-TD001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 2080-LC20-20AWBR is the same 20-point AC-input Micro820 as the 20AWB, built with removable terminal blocks.
Removable blocks matter on a machine that is serviced in the field: a controller can be swapped without rewiring, and the blocks travel with the harness.
Everything else matches the 20AWB: Ethernet, serial, microSD and two plug-in slots.
The terminal blocks unplug, so the wiring schedule should be labelled per block rather than per controller.
Input circuit is 120 V AC on inputs 4 to 11; inputs 0 to 3 are 24 V DC.
Relay output rating is 2 A at 240 V AC and 1 A at 24 V DC.
Communication and capacity. USB 2.0 (USB-C on the 2080-L20E), 10/100 Base-T Ethernet RJ45, RS-232/RS-485 non-isolated combo serial, microSD slot for data logging and recipes
2 plug-in slots plug-in modules can be fitted, each drawing about 1.44 W of the controller's internal budget.
Connected Components Workbench is the programming environment for the whole family, so a project built for one Micro800 controller converts to another with the I/O reassigned.
Mounting is DIN rail or panel, 90 x 104 x 75 mm, shipping 0.38 kg.
Rated ambient -20 to 65 C (-4 to 149 F), maximum consumption 5.62 W without plug-ins, 8.5 W with.
Lifecycle. Active
Twenty points, two plug-in slots, Ethernet and serial on the base unit.
Rockwell lists it as Active.
The R suffix is the whole difference from 2080-LC20-20AWB, and it is worth paying for on a machine that will be serviced.
How many I/O points does 2080-LC20-20AWBR have?
Micro820 20-point Ethernet controller: 20 (12 inputs, 8 relay outputs).
What is the input type on 2080-LC20-20AWBR?
12 inputs, 120 V AC on inputs 4 to 11; inputs 0 to 3 are 24 V DC.
What does 2080-LC20-20AWBR use for communication?
USB 2.0 (USB-C on the 2080-L20E), 10/100 Base-T Ethernet RJ45, RS-232/RS-485 non-isolated combo serial, microSD slot for data logging and recipes.
What are the dimensions of 2080-LC20-20AWBR?
90 x 104 x 75 mm, 0.38 kg.
What is the lifecycle status of 2080-LC20-20AWBR?
Active.