Product Details:
Payment & Shipping Terms:
|
The 2080-LC10-12AWA is the AC-supplied 12-point Micro810: eight 120/240 V AC inputs and four relay outputs that switch the load directly, so a small panel needs no interposing relays.
Rockwell positions the Micro810 as a smart relay with the programming capability of a micro PLC: delay ON/OFF timers, time of day, time of week and time of year function blocks are built in for lighting and timer work.
| 2080-LC10-12AWA | Micro810, 8 AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QWB | Micro810, 8 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QBB | Micro810, 8 DC/AC in / 4 DC source out | IN STOCK |
| 2080-LC10-12DWD | Micro810, 8 12V DC in / 4 relay out | IN STOCK |
| 2080-LC20-20AWB | Micro820, 12 AC in / 8 relay out | IN STOCK |
| 2080-LC20-20QWB | Micro820, 12 DC in / 8 relay out | IN STOCK |
| 2080-LC20-20QBB | Micro820, 12 DC in / 8 DC source out | IN STOCK |
| 2080-LC20-20AWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QBBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC30-10QWB | Micro830, 6 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC30-10QVB | Micro830, 6 DC/AC in / 4 DC sink out | IN STOCK |
| 2080-LC30-16AWB | Micro830, 10 AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QWB | Micro830, 10 DC/AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QVB | Micro830, 10 DC/AC in / 6 DC sink out | IN STOCK |
| 2080-LC30-24QWB | Micro830, 14 DC/AC in / 10 relay out | IN STOCK |
| 2080-LC30-24QVB | Micro830, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC30-24QBB | Micro830, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC30-48AWB | Micro830, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QWB | Micro830, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QVB | Micro830, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-24AWB | Micro850, 14 AC in / 10 relay out | IN STOCK |
| 2080-LC50-24QVB | Micro850, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC50-24QBB | Micro850, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC50-48AWB | Micro850, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QWB | Micro850, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QVB | Micro850, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-48QBB | Micro850, 28 DC/AC in / 20 DC source out | IN STOCK |
Catalog number |
2080-LC10-12AWA |
Family |
Micro810 12-point smart relay controller |
I/O points |
12 (8 inputs, 4 relay outputs) |
Inputs |
8 inputs, 120/240 V AC; four of them can be reconfigured as 0 to 10 V analog inputs |
Outputs |
4 relay outputs, two rated 8 A and two rated 4 A |
Supply |
100 to 240 V AC, 50/60 Hz, 85 to 263 V range, 5 VA maximum |
Communication |
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port |
Plug-in modules |
None; the Micro810 has no plug-in slots, only the LCD and USB accessories |
Dimensions, H x W x D |
91 x 75 x 59 mm |
Shipping weight |
0.203 kg |
Temperature rating |
0 to 55 C (32 to 131 F) |
Power consumption, max |
5 VA |
Lifecycle |
Active |
Relay output rating |
Two outputs at 8 A, two at 4 A |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-TD001 (module specifications) and 2080-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 2080-LC10-12AWA is the AC-supplied 12-point Micro810: eight 120/240 V AC inputs and four relay outputs that switch the load directly, so a small panel needs no interposing relays.
Rockwell positions the Micro810 as a smart relay with the programming capability of a micro PLC: delay ON/OFF timers, time of day, time of week and time of year function blocks are built in for lighting and timer work.
It is the controller to specify when the machine is a pump, a fan, a gate or a lighting circuit rather than a motion axis.
Inputs and outputs are on fixed screw terminals with 7 mm stripping length and 0.5 to 0.6 Nm torque.
The relay contacts are the reason this model exists: 8 A and 4 A ratings mean a contactor coil or a small heater can be wired straight to the controller.
Four of the eight inputs are analog/digital configurable, so a 0 to 10 V sensor can share the same terminal strip as the discrete switches.
Communication and capacity. USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port
None; the Micro810 has no plug-in slots, only the LCD and USB accessories plug-in modules can be fitted, each drawing about 1.44 W of the controller's internal budget.
Connected Components Workbench is the programming environment for the whole family, so a project built for one Micro800 controller converts to another with the I/O reassigned.
Mounting is DIN rail or panel, 91 x 75 x 59 mm, shipping 0.203 kg.
Rated ambient 0 to 55 C (32 to 131 F), maximum consumption 5 VA.
Lifecycle. Active
Eight inputs and four outputs is the whole I/O count: there is no expansion and no plug-in slot, so the application has to fit in twelve points.
The USB programming port is reached through the 2080-USBADAPTER, and the 2080-LCD gives local configuration without a PC.
Rockwell lists it as Active, and it is still the cheapest way into the Micro800 programming environment.
How many I/O points does 2080-LC10-12AWA have?
Micro810 12-point smart relay controller: 12 (8 inputs, 4 relay outputs).
What is the input type on 2080-LC10-12AWA?
8 inputs, 120/240 V AC; four of them can be reconfigured as 0 to 10 V analog inputs.
What does 2080-LC10-12AWA use for communication?
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port.
What are the dimensions of 2080-LC10-12AWA?
91 x 75 x 59 mm, 0.203 kg.
What is the lifecycle status of 2080-LC10-12AWA?
Active.