logo
Home ProductsAB Micro & Nano Systems

Allen Bradley Micro800 2085-IRT4 / 2085IRT4

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley Micro800 2085-IRT4 / 2085IRT4

China Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier
Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier Allen Bradley Micro800 2085-IRT4 / 2085IRT4 supplier

Large Image :  Allen Bradley Micro800 2085-IRT4 / 2085IRT4

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley Micro800 2085-IRT4 / 2085IRT4

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $279.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Paypal and Western Union.
Supply Ability: 5 PCS
Detailed Product Description

2085-IRT4 technical data PDF download 2085-IRT4 Rockwell Micro800 4 Channel RTD and Thermocouple Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: Micro800 2085 expansion I/O

2085-IRT4 is a 4-channel temperature input module in the Micro800 expansion line. It reads RTDs and thermocouples directly at 16 bits, which removes four transmitters and their loop supplies from a temperature panel.

Field wiring lands on the removable terminal block (RTB). The RTB can be unplugged with the wiring in place, which is the reason a failed module can be swapped without re-terminating a panel.

2085-IA8 8-point 120 V AC input IN STOCK
2085-IM8 8-point 240 V AC input IN STOCK
2085-OA8 8-point 120/240 V AC triac output IN STOCK
2085-IQ32T 32-point 12/24 V DC sink/source input IN STOCK
2085-OV16 16-point 12/24 V DC sink transistor output IN STOCK
2085-OB16 16-point 12/24 V DC source transistor output IN STOCK
2085-OW8 8-point AC/DC relay output IN STOCK
2085-OW16 16-point AC/DC relay output, 2 A IN STOCK
2085-IF4 4-channel 14-bit isolated analog input IN STOCK
2085-IF8 8-channel 14-bit isolated analog input IN STOCK
2085-OF4 4-channel 12-bit isolated analog output IN STOCK
2085-IRT4 4-channel 16-bit RTD and thermocouple input IN STOCK
2085-ECR 2085 expansion bus terminator IN STOCK

Product Specifications 2085-IRT4 (PDF)
 Catalog number
 2085-IRT4
 Product type
 4-channel temperature input module
 Points / channels
 4 channels
 Signal
 RTD and thermocouple, 16-bit
 Isolation
 Isolated, field wiring to controller
 Backplane current, 5 V DC
 Not published
 Dimensions, H x W x D
 Not published
 Temperature rating
 Not published
 Lifecycle status
 Active
 UPC
 Not published
 Country of origin
 Not published
 Terminal block
 Removable terminal block (RTB)

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-UM003 (module specifications) and Rockwell literature library (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

2085-IRT4 2085-IRT4 2085-IRT4 2085-IRT4 2085-IRT4 2085-IRT4 2085-IRT4

What the module adds to a Micro800 controller

2085-IRT4 is a 4-channel temperature input module in the Micro800 expansion line. It reads RTDs and thermocouples directly at 16 bits, which removes four transmitters and their loop supplies from a temperature panel.

It mounts to the right of a Micro810, Micro820, Micro830, Micro850 or Micro870 controller and is addressed by its position in the expansion chain, so the slot order in the project has to match the physical order.

Signal and channel count are fixed by the catalog number: 4 channels, RTD and thermocouple, 16-bit.

Wiring on the removable terminal block

Field wiring lands on the removable terminal block (RTB). The RTB can be unplugged with the wiring in place, which is the reason a failed module can be swapped without re-terminating a panel.

Sensor type is selected in software per channel, so the same card covers a Pt100 and a type J thermocouple on neighbouring zones.

Size the conductors and the torque to the module data sheet; the RTB screws are hand-tightened, not driven with a power tool.

Expansion bus, module order and power

Module order matters: the expansion chain is scanned in physical order, and the bus is ended with a terminator. Isolation is field to controller, not channel to channel, which matters when the sensors sit at different potentials.

Backplane draw is Not published. Add every module in the chain before deciding on the controller power budget.

Dimensions, ratings and lifecycle

Rockwell lists this catalog number as Active.

Dimensions are Not published and the rated ambient is Not published.

UPC is Not published, country of origin Not published.

Buying and swapping a module

Check that the module comes with its RTB. A module sold without the terminal block is not a drop-in swap, whatever the price difference.

Confirm the catalog number against the project: the 2085 line separates sink from source transistor outputs and AC input from DC input by catalog number only.

A temperature card is only as good as its cold junction and its wiring: check the terminal block for corrosion before trusting a used unit.

FAQ — 2085-IRT4

What does 2085-IRT4 do?

4-channel temperature input module: 4 channels, RTD and thermocouple, 16-bit.

Where does 2085-IRT4 mount?

To the right of a Micro800 controller, in the expansion chain, connected through the 2085 bus.

How much backplane current does 2085-IRT4 draw?

Not published.

What are the dimensions of 2085-IRT4?

Not published, rated Not published.

Is 2085-IRT4 a current Rockwell product?

Rockwell lists it as Active.


Data sources. Descriptions, channel counts and analog ranges come from the Micro800 expansion I/O manual 2080-UM003; the 120 V and 240 V input ranges, off-state limits, filter time and bus current come from 2085-IN005; physical and lifecycle data come from the Rockwell product page for the catalog number. Any attribute these publications do not print is marked Not published. Any attribute a publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

2085-IRT4: 4 channel thermocouple and RTD input module

2085-IRT4 is a 4 channel thermocouple and RTD input module in the 2085 expansion family for Micro850 controllers, and the specification rows below are the published values for this catalog number rather than a family average.

SpecificationValue
Catalog number2085-IRT4, 4 channel thermocouple and RTD input expansion module
Thermocouple typesB, C, E, J, K, TXK and XK (L), N, R, S, T
RTD types100 Ohm Pt alpha 0.00385, 200 Ohm Pt alpha 0.00385, 100 Ohm Pt alpha 0.003916 US, 200 Ohm Pt alpha 0.003916 US, 100 Ohm nickel 618, 200 Ohm nickel 618, 120 Ohm nickel 672, 10 Ohm copper 427
Other rangesMillivolt 0 to 100 mV; resistance 0 to 500 Ohm
Resolution16 bits
Channel update time12 to 500 ms per enabled channel, typical
Input impedanceOver 10 MOhm
Accuracy, thermocouplePlus or minus 0.5 to 3.0 degrees C, 0.9 to 5.4 degrees F
Accuracy, RTDPlus or minus 0.2 to 0.6 degrees C, 0.36 to 1.08 degrees F
Power dissipation2 W total
Isolation voltage50V continuous, reinforced insulation, channel to system; type tested at 720V DC for 60 s
Status indicators1 green health indicator
EnclosureOpen style
North American temperature codeT4
Source2080-TD001 Micro800 technical data, 2085-IRT4 specification

Two tenths of a degree on an RTD and half a degree on a thermocouple are the accuracies at the good end of the published ranges, and the range itself widens with the sensor type and the temperature. Quoting one number for a temperature module is where most specification errors start.

Twelve to five hundred milliseconds per enabled channel means a four channel module with all channels enabled can take two seconds to complete a cycle. A temperature control loop that needs faster feedback than that has to enable fewer channels or use a different module.

The figures on this page are published for this catalog number in the Micro800 technical data, including the isolation and temperature code rows. Where the source gives a range rather than a single value, the range is reproduced instead of a midpoint.

The point count on an expansion module is a bus load as well as a field count. Sixteen discrete inputs draw one hundred and seventy milliamps from the five volt bus and thirty two draw one hundred and ninety, which is the figure the controller power budget has to absorb for every module in the chain.

Derating curves are published for a reason, and they are the part of a data sheet that gets skipped. A sixteen point DC input module with a published curve will carry its full count at one ambient and a reduced count at another, and the cabinet temperature is the variable that decides which.

A green health indicator and no channel indicators is a deliberate diagnostic style on some analog modules. The module tells you it is alive and the channel value tells you the rest, which means the troubleshooting tool is the programming software rather than a lamp.

The Type 1 input designation is a real classification, not marketing. IEC Type 1 inputs are the slow, tolerant sensors, and a module published against that standard is the right choice for a limit switch and the wrong one for a registration mark.

Channel update time on a temperature module is measured per enabled channel, not per module. Twelve to five hundred milliseconds per channel means a module with all channels enabled updates slowly, and a control loop that assumes a fast scan will be wrong about when the value arrived.

An expansion module is a separate DIN rail device with its own terminal block, and that changes the wiring effort compared with a plug-in module. The 2085 family is what a Micro850 chassis accepts, up to four of them, and each one carries its own field terminals rather than borrowing the controller row.

Relay and transistor outputs on the same family look interchangeable on a drawing and are not interchangeable on a load. A relay at eight amps per module handles an inrush that a transistor output rated half an amp per point will not survive, and the load type decides which module is ordered.

Two hundred and twenty grams of shipping weight and an open style enclosure are the practical statements about these modules. They are panel mounted inside an enclosure, they are not field mounted, and the enclosure rating is the panel rating rather than the module rating.

Isolation on these modules is fifty volts continuous, reinforced insulation, channel to system, with a type test at seven hundred and fifteen volts DC for sixty seconds. That is a working isolation for a panel with a common reference, not a barrier for a hazardous area, and the two should not be confused.

Analog temperature modules carry an accuracy that depends on the sensor type. A thermocouple input specified within half a degree to three degrees and an RTD input within two tenths to six tenths of a degree are two very different measurement systems sharing one module.

Expansion modules share the controller supply and add to its consumption, so the power budget is cumulative. A controller published at eleven watts with no expansion and thirty three watts with plug-ins and expansion is telling the designer that the difference belongs to the modules that were added.

Forty four and a half millimetres of width is the physical unit of expansion planning. Five modules fit in a fraction of the rail space that five separate controllers would take, and the depth of eighty seven millimetres is what decides whether the panel is deep enough for the terminal cover.

The bus terminator is the part that makes the serial expansion bus electrically correct. It terminates the end of the chain, it is listed in the same technical data as the modules, and a chain without it is a chain that may work on the bench and fail in the panel.

Match the accuracy to the sensor type, count the channels against the update time, and do not quote one accuracy figure for the module.

The Allen-Bradley Micro and Nano systems category groups the other catalog numbers, options and spare parts in the same range.