This page documents catalog number 1738-ADN18, a DeviceNet adapter with M18 connectors in the ArmorPoint I/O family. The adapter is the network node of a backplane: it carries the MAC ID, the baud rate and the mapping, and the figures below are the system specifications published for the ArmorPoint DeviceNet adapters.
| Field | Value |
| Catalog number | 1738-ADN18 |
| Family | 1738 ArmorPoint I/O, DeviceNet adapter |
| Connectors | M18 for the DeviceNet drop and the field-power feed |
| Dimensions | 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| Operating temperature | 20 to 60 degrees C (68 to 140 degrees F) |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz |
| Maximum modules on a backplane | 63, reachable with additional 1738-EP24DC power modules |
The 18-millimetre shell is the middle size in this family and is chosen when the drop cable is heavier than an M12 body accommodates but the space does not take an M23 flange.
A backplane is limited to 63 modules, and the limit is reached in practice with 1738-EP24DC power modules inserted to keep the field-power budget inside the segment rather than with an adapter that runs out of addresses. Each digital or analog module draws 75 mA at 5 V dc from PointBus, the 1738-SSIM23 draws 110 mA, and that sum is the number that decides how many modules fit before another power module is needed.
Field power is a separate budget at 10 to 28.8 V dc, and it is the one that fails first on a segment full of sensors: the adapter and the power modules feed the field side, the PointBus feeds the logic side, and a segment planned on one of the two is a segment that trips on the other.
The adapter holds the MAC ID for the drop and the baud rate for the network, and autobaud is a setting rather than a default that can be relied on. On the 1738-ADNX the adapter also runs a subnet behind itself, which is the architecture that lets modules not on the backplane keep their own baud rate and MAC ID; the adapter then builds a scanlist from what it finds and maps the data along byte, word or double-word boundaries.
Auto Start Mode is the convenience that is easy to misread: while it runs, the adapter reports an auto-start state and refuses I/O allocation from a scanner, and the parameter is meant to be returned to a do-nothing value afterwards. A segment left in auto start is a segment a scanner cannot allocate.
| Parameter | Value |
| Dimensions with base | 120 H x 72 W x 42 D mm (4.72 x 2.83 x 1.65 in.) for I/O modules; 112 H x 72 W x 65 D mm (4.41 x 2.83 x 2.56 in.) for the DeviceNet adapters |
| Enclosure rating | Meets IP65/66/67 when marked; the sealed housing needs no cabinet, though a plant with washdown or corrosive atmosphere can still require one |
| Operating temperature | -20 to 60 degrees C (-4 to 140 degrees F), IEC 60068-2-1 cold, 60068-2-2 dry heat and 60068-2-14 thermal shock |
| Storage temperature | -40 to 85 degrees C (-40 to 185 degrees F) |
| Relative humidity | 5 to 95 percent non-condensing, IEC 60068-2-30 damp heat |
| Shock and vibration | Operating 30 g, non-operating 50 g; 5 g at 10-500 Hz operating |
| Isolation | 50 V rms continuous withstand, tested at 1,250 V ac rms for 60 s |
| ESD and RF immunity | 6 kV contact and 8 kV air discharge, 10 V/m radiated RF from 30 MHz to 2,000 MHz, 10 Vrms conducted RF from 150 kHz to 80 MHz |
| Transient immunity | Plus or minus 3 kV at 5 kHz EFT on signal ports, plus or minus 1 kV line-to-line and plus or minus 2 kV line-to-earth surge |
| Emissions | CISPR 11 Group 1 Class A |
| Mounting | Mounted on a grounded metal plate with #8 (M4) screws; base torque 7.5 in-lb in aluminium and 16 in-lb in steel; the ground lug is also a mounting hole |
| Weight | 0.29 kg (0.64 lb) with base |
| Field power bus | 24 V dc nominal, 10 to 28.8 V dc range |
| PointBus current | 75 mA at 5 V dc for digital and analog modules, 110 mA for 1738-SSIM23 |
The environmental claims in this family are stated per module and per connector: IP65/66/67 applies when the connector caps are tightened, and the installation instructions repeat the attention note that all connectors and caps have to be securely tightened to keep the seal. That single step is where most field failures on sealed I/O originate, and it is a mechanical check rather than a network check.
The sealed housing is the reason this family exists. An IP67 module on a machine frame removes the cabinet from the field side of the design, and the price of that is that every environmental claim is made per module rather than per enclosure.
What this page does not claim matters as much as what it does. It does not state a module count, a cable length, a cycle time or a network baud rate for this catalog number, because those are properties of the segment and the adapter rather than of the module, and a figure of that kind copied into a page becomes a specification nobody can trace back to a publication. Where the source publications do fix a value - the channel count, the connector shell, the current limit, the isolation rating, the temperature window, the data size - it is on this page with the publication named.
No lifecycle statement and no price is implied. The electrical, environmental and data-map figures are quoted from the ArmorPoint installation instructions and the DeviceNet adapter user manual; a figure not printed here is one the source publication does not state for this catalog number.