Product Details:
Payment & Shipping Terms:
|
The 1794-IE12 is the twelve-channel analog input card: 16-bit resolution, 0...20 mA, 4...20 mA or +/-10V per channel, and 8.0 ms conversion for all twelve channels.
Twelve channels on one FLEX I/O slot is the density argument — a panel with a rack of transmitters fits one island, and the per-channel out-of-range flag removes the range checking from the program.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O analog input, 1794 terminal base |
Cat Num |
1794-IE12 |
Brand Name |
Rockwell |
Channels |
12, individually configurable, out-of-range per channel |
Input ranges |
0...20 mA, 4...20 mA, +/-10V DC |
Resolution |
16 bits unipolar, 15 bits plus sign bipolar; 0.641 uA/cnt, 320 uV/cnt |
Input resistance |
<100 Ohm current, >1 MOhm voltage |
Conversion rate |
8.0 ms all channels |
Accuracy |
0.1% of full scale at 25 deg C |
Overload |
30V continuous, 32 mA continuous, single channel |
Isolation |
850V DC type test for 60 s, field to system; no channel isolation |
External supply current |
30 mA at 24V DC, 45 mA at 10V DC |
Power dissipation |
1.2 W at 31.2V DC (4.1 BTU/hr) |
Operating temperature |
-20...60 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
0.641 uA per count on current and 320 uV per count on voltage is 16-bit unipolar resolution, with 15 bits plus sign in bipolar mode.
8.0 ms conversion for all twelve channels is a successive-approximation front end, so the update is fast but the line rejection is filter-dependent.
Out-of-range notification per channel is a bit in the input data, not a program comparison, which is what makes twelve channels manageable.
0.1% of full scale at 25 deg C is the published accuracy including offset, gain, non-linearity and repeatability.
Current input resistance below 100 Ohm keeps the loop burden low enough for a two-wire transmitter at the end of a long cable.
-3 dB at 0.05 Hz and -52 dB at 50 Hz in normal mode is a heavy filter: it rejects mains hum well and settles slowly.
Quick Step moves the corner to 1.5 Hz and the 50 Hz rejection to -29 dB, trading noise immunity for a 0.09 s step response instead of 1.3 s.
The choice is per module, not per channel, so a panel that needs both a fast pressure loop and a slow temperature reading uses two cards.
1.3 s to 63% of full scale is the normal-mode figure; in a level or temperature application that is invisible, in a fast loop it is the limiting factor.
30 mA at 24V DC and 1.2 W (4.1 BTU/hr) is the lowest heat per channel in the analog line: twelve channels for less dissipation than four isolated ones.
45 mA at 10V DC is the published figure at the bottom of the supply range, where the internal regulator works hardest.
The card does not power the loop; a two-wire transmitter needs its own supply, and the current input is a 100 Ohm burden on it.
-20...60 deg C operating range sits between the standard -20...55 deg C and the XT -20...70 deg C.
Single-ended inputs share a common return; a grounded transmitter plus a grounded panel reference is the classic ground-loop case this card cannot break.
Current and voltage on the same channel is a wiring error; the range is configured but the terminals accept one signal type.
Shielded pair, return at the module is the standard for a 4...20 mA loop, and the 30V/32 mA overload rating covers most miswiring during commissioning.
Keying and FlexBus insertion follow the same five steps as every 1794 module; the base holds the terminals so a card swap leaves the wiring.
Dense analog panels where twelve loops on one slot replaces three four-channel cards.
Slow process signals — level, temperature, flow — where the 1.3 s step response is irrelevant.
Not for isolated loops. Channels share a common; a panel with separate grounds needs the 1794-IF4I or 1794-IF8IH.
Not for HART. The HART modem lives in the 1794-IE8H, not in this card.
How many channels has the 1794-IE12?
Twelve individually configurable analog inputs.
What ranges are supported?
0...20 mA, 4...20 mA and +/-10V DC, selected per channel.
What is the resolution?
16 bits unipolar and 15 bits plus sign bipolar, 0.641 uA or 320 uV per count.
How fast does it convert?
8.0 ms for all twelve channels.
What is the step response?
1.3 s to 63% of full scale, or 0.09 s with Quick Step enabled.
What isolation does it provide?
850V DC type tested for 60 s, field to system; no isolation between channels.