Product Details:
Payment & Shipping Terms:
|
The 1794-APBDPV1 is the DP-V1 PROFIBUS adapter: it speaks the newer protocol generation instead of DP-0, adds Identification & Maintenance records, and runs any rate up to 12.0 Mbit/s.
The electrical profile is leaner than the APB — 385 mA maximum and 4.2 W dissipation against 450 mA and 7.68 W — so the same enclosure carries more islands for the same heat budget.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 15 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 15 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O PROFIBUS DP-V1 adapter |
Cat Num |
1794-APBDPV1 |
Brand Name |
Rockwell |
I/O module capacity |
8 modules |
Input voltage |
24V DC nom, 19.2...31.2V DC |
Input current, max |
385 mA, 309 mA at 24V DC |
Inrush current |
23 A for 2 ms |
Communication rate |
Up to 12.0 Mbit/s |
Flexbus |
640 mA at 5V DC |
Power dissipation |
4.2 W at 19.2V DC |
Operating temperature |
0...55 deg C, T4 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
DP-V1 instead of DP-0: the APB uses first-generation PROFIBUS DP, this adapter uses the newer protocol.
I&M functions are implemented, which store device identification and maintenance data for acyclic access.
Supports newer HART modules that the APB does not.
Acyclic services are available on top of the cyclic I/O exchange.
Physical address range 1...99, logical range 1...126.
Thumbwheels set to 00 allow software configuration to assign 1...125; changes take effect only after a power cycle.
Maximum 32 stations on one network.
9-pin SUB-D connector and standard PROFIBUS drop cable.
19.2...31.2V DC, 385 mA maximum and 309 mA at 24V DC.
23 A inrush for 2 ms, 640 mA at 5V DC on the Flexbus.
Routine tested at 850V DC for 1 s, type tested at 850V AC for 60 s across PROFIBUS, backplane and power.
4.2 W and 14 BTU/hr at 19.2V DC, roughly half the APB's heat.
87 x 69 x 69 mm, T4 temperature code.
22...12 AWG power conductors rated 115 deg C, 0.8 N*m torque.
Up to 8 terminal base units forming an eight-slot island.
Status and PROFIBUS diagnostic indicators on the front panel.
DP-V1 masters and networks using acyclic parameter access.
Panels using HART I/O on FLEX I/O.
Not DP-0 compatibility replacement where the master is DP-0 only — check the master.
Not EtherNet/IP or ControlNet.
What protocol does the 1794-APBDPV1 use?
PROFIBUS DP-V1, whereas the 1794-APB uses DP-0.
What is the maximum rate?
Up to 12.0 Mbit/s.
How many modules can it carry?
8 modules, on up to eight terminal base units.
What is the input current?
385 mA maximum, 309 mA at 24V DC, 23 A inrush for 2 ms.
What is the isolation test?
Routine tested at 850V DC for 1 s, type tested at 850V AC for 60 s.
How is the node address set?