Product Details:
Payment & Shipping Terms:
|
The 1794-OG16 gives 16 TTL outputs at 24 mA per channel, for driving logic-level inputs, solid-state relays and instrument gates.
Like the input card of the same family, the logic is inverted: On is 0...0.4V DC, Off is 4.5...5.5V DC.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O TTL digital output |
Cat Num |
1794-OG16 |
Brand Name |
Rockwell |
Number of outputs |
16, TTL |
Output voltage |
0V DC min, 0V DC nom, 0.4V DC max |
Output current |
0.15 mA min, 24 mA max per channel |
Off-state leakage |
1 mA max |
Isolation |
50V continuous, type tested 707V DC for 60 s |
Signal delay |
0.5 ms Off-to-On, 1.0 ms On-to-Off |
Flexbus current |
80 mA at 5V DC |
External supply |
4.5...5.5V DC, 100 mA at 5V DC |
Terminal base |
1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
On = 1 = logic low = 0...0.4V DC; Off = 0 = logic high = 4.5...5.5V DC, as printed in the publication.
A NOT instruction restores conventional polarity in the ladder program.
24 mA per channel maximum, 0.15 mA minimum, which is enough for a TTL input or an SSR gate.
1 mA off-state leakage will hold a sensitive input low, so check the driven device.
0.5 ms Off-to-On and 1.0 ms On-to-Off, the values the datasheet gives rather than a range.
4.5...5.5V DC external supply, 100 mA at 5V, supplied from the same rail as the driven logic.
80 mA from the Flexbus, higher than the input card because each channel is driven.
0.8 W dissipation and 3.41 BTU/hr, negligible in a panel thermal budget.
Driving TTL inputs, SSRs and small interface boards.
Test rigs that emulate logic-level signals.
Not for 24V devices; the 1794-OB16 is the 24V sourcing card.
Not for long cable runs; the 10 m cable limit applies to this family.
Capacitors of 0.01 uF, 2000V minimum, across the output wiring per the publication drawing.
I/O cable under 10 m, shielded per the wiring recommendation.
<Keyswitch position 4A, set on the terminal base before the module is seated.
16 yellow status indicators show each output state.
TTL-level interface islands.
Machine panels passing signals to a vision or measurement system.
Not for inductive 24V loads.
Not for AC.
How many outputs has the 1794-OG16?
16 TTL outputs.
What is the maximum output current?
24 mA per channel.
Is the logic inverted?
Yes; On is 0...0.4V DC and Off is 4.5...5.5V DC.
What is the output delay?
0.5 ms Off-to-On and 1.0 ms On-to-Off.
What supply does it need?
4.5...5.5V DC, drawing 100 mA at 5V.
Which terminal bases are used?
1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
1794-OG16 is a digital DC output with 16 outputs in the FLEX I/O range, rated for 5V DC, non-isolated. It mounts on the 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-OG16 |
| Module type | digital DC output |
| Points | 16 outputs |
| Electrical range | 5V DC, non-isolated |
| Terminal base unit | 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
The wiring category matters as much as the gauge: category 2 bases are the general field wiring class, while grounded bases in the 1794-TB3G family carry 10 chassis ground terminals for analog and temperature modules where a separate signal common is needed.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Conformal coating on a K suffix base is applied to the assembled board and not to the terminals, so the coating protects the electronics against condensation while the field terminals remain serviceable. That is the point of ordering the coated base instead of sealing the whole enclosure.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
The Allen-Bradley Flex I/O 1794 modules category lists the related catalog numbers, options and accessories for this range.