Product Details:
Payment & Shipping Terms:
|
The 1794-OF4I is the isolated four-channel analog output: channel-to-channel isolation, six output ranges, 15-bit resolution and a step response under 25 us.
The sub-25 us response is what separates it from the PWM cards: a fast drive reference or a proportional valve that has to follow a step can be driven from this output, not from a 24 ms card.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O isolated analog output, 1794 terminal base |
Cat Num |
1794-OF4I |
Brand Name |
Rockwell |
Channels |
4, channel-to-channel isolated, individually configurable |
Output ranges |
4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC, +/-5V DC, 0...5V DC |
Resolution |
15 bits plus sign; 0.656 uA/cnt, 0.320 mV/cnt |
Conversion |
Digital-to-analog converter, 2.5 or 5.0 ms |
Step response |
Under 25 us to 63% of full scale |
Accuracy |
0.1% of full scale at 25 deg C |
Load |
0...750 Ohm current; 3 mA maximum on voltage output |
Isolation |
120V continuous with TB2/TB3/TB3S/TB3T, 250V with TBN; 1500V AC for 60 s channel to channel |
External supply current |
210 mA at 24V DC |
Power dissipation |
4.7 W at 31.2V DC (16 BTU/hr) |
Operating temperature |
-20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Channel-to-channel isolation at 120V continuous with TB2, TB3, TB3S, TB3T or TB3TS bases, and 250V continuous with a TBN base.
1500V AC for 60 s and 2550V DC for 1 s type tests between channel and channel and I/O to system are the published isolation figures.
Six ranges: 4...20 mA, 0...20 mA, +/-10V, 0...10V, +/-5V and 0...5V, configurable per channel.
15 bits plus sign at 0.656 uA and 0.320 mV per count is finer than the non-isolated four-channel card.
0.1% of full scale at 25 deg C with 0.0025% per deg C on current and 0.0012% on voltage drift.
Under 25 us to 63% of full scale is the fastest analog output response in the FLEX I/O analog line.
Digital-to-analog conversion at 2.5 or 5.0 ms for all channels; the update rate does not limit the step itself.
0...750 Ohm resistive load on current and 3 mA on voltage output, unchanged from the non-isolated card.
Factory calibrated, so there is no trim procedure, and the isolation is not compromised by a field adjustment.
210 mA at 24V DC is the module consumption, higher than the 1794-OE4 because of four isolated output stages.
4.7 W at 31.2V DC (16 BTU/hr) is the heat to add to the enclosure calculation.
-20...55 deg C on the standard version; the 1794-OF4IXT publishes -20...70 deg C with a 75 mm deep body.
Wire category 2 on signal ports and 3 on power ports is stated in the publication, which is worth checking against the panel's routing plan.
Each output has its own return, which is the point of the card: four devices at four different ground references can be driven from one slot.
250V continuous isolation only with a TBN base is a base-dependent rating, not a module-only one, and it belongs on the drawing.
Shielded pair per loop with the shield at the panel is the practice; isolation breaks ground loops, it does not remove induced noise.
One signal type per channel, and a voltage device on a current-configured channel reads zero without any diagnostic bit.
Fast analog references — drive speed references, proportional valves that follow a ramp.
Mixed ground references across four field devices in the same panel.
Not for HART. The 1794-OF8IH carries the HART modem and eight isolated outputs.
Not for density. Four isolated outputs cost a slot that a non-isolated card would fill with twelve.
How many outputs has the 1794-OF4I?
Four isolated analog outputs with individual range configuration.
What isolation does it provide?
Channel-to-channel at 120V continuous with TB2/TB3/TB3S/TB3T bases, 250V with TBN; type tested at 1500V AC for 60 s.
What ranges are available?
4...20 mA, 0...20 mA, +/-10V, 0...10V, +/-5V and 0...5V.
How fast does it respond?
Under 25 us to 63% of full scale, with 2.5 or 5.0 ms conversion for all channels.
What accuracy does it achieve?
0.1% of full scale at 25 deg C, factory calibrated.
What current does the module draw?
210 mA at 24V DC.
| Catalog number | Channels | Output ranges | Resolution | Accuracy | Load |
|---|---|---|---|---|---|
| 1794-OE4 | 4, non-isolated, individually configurable | 4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC | 12 bits plus sign; 2.56 mV/cnt, 5.13 uA/cnt | 0.425% of full scale current, 0.133% voltage, at 25 deg C | 15...750 Ohm current; 3 mA maximum on voltage output |
| 1794-OE4XT | 4, non-isolated, individually configurable | 4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC | 12 bits plus sign; 0.156 mV/cnt, 0.320 uA/cnt | 0.425% of full scale current, 0.133% voltage, at 25 deg C | 15...750 Ohm current; 3 mA maximum on voltage output |
| 1794-OE12 | 12, individually configurable, out-of-range bit per channel | 0...20 mA, 4...20 mA, +/-10V DC | 320 uV/cnt, 0.641 uA/cnt | 0.1% of full scale at 25 deg C, current and voltage | 0...750 Ohm current; 3 mA maximum on voltage output |
| 1794-OF4I | 4, channel-to-channel isolated, individually configurable | 4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC, +/-5V DC, 0...5V DC | 15 bits plus sign; 0.656 uA/cnt, 0.320 mV/cnt | 0.1% of full scale at 25 deg C | 0...750 Ohm current; 3 mA maximum on voltage output |
A single module can carry four or twelve outputs on the same base width, so the load per channel matters more than the count once the panel is already built.
For 1794-OF4I the published row reads 4, channel-to-channel isolated, individually configurable channels over 4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC, +/-5V DC, 0...5V DC, at 15 bits plus sign; 0.656 uA/cnt, 0.320 mV/cnt resolution and 0.1% of full scale at 25 deg C accuracy, driving 0...750 Ohm current; 3 mA maximum on voltage output; the module draws 210 mA at 24V DC from the external supply and dissipates 4.7 W at 31.2V DC (16 BTU/hr).
An accuracy figure quoted at a single temperature is a room-temperature promise; the drift and temperature rows on the page above are what the loop sees in a cabinet that runs warm.
Conversion is published as Digital-to-analog converter, 2.5 or 5.0 ms and the step response as Under 25 us to 63% of full scale, so a loop that needs a fast move should be checked against the second figure before the resolution.
This part sits in the Allen-Bradley Flex I/O 1794 modules category, with the other models and spare parts listed alongside it.