Product Details:
Payment & Shipping Terms:
|
The 1794-OF4I is the isolated four-channel analog output: channel-to-channel isolation, six output ranges, 15-bit resolution and a step response under 25 us.
The sub-25 us response is what separates it from the PWM cards: a fast drive reference or a proportional valve that has to follow a step can be driven from this output, not from a 24 ms card.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O isolated analog output, 1794 terminal base |
Cat Num |
1794-OF4I |
Brand Name |
Rockwell |
Channels |
4, channel-to-channel isolated, individually configurable |
Output ranges |
4...20 mA, 0...20 mA, +/-10V DC, 0...10V DC, +/-5V DC, 0...5V DC |
Resolution |
15 bits plus sign; 0.656 uA/cnt, 0.320 mV/cnt |
Conversion |
Digital-to-analog converter, 2.5 or 5.0 ms |
Step response |
Under 25 us to 63% of full scale |
Accuracy |
0.1% of full scale at 25 deg C |
Load |
0...750 Ohm current; 3 mA maximum on voltage output |
Isolation |
120V continuous with TB2/TB3/TB3S/TB3T, 250V with TBN; 1500V AC for 60 s channel to channel |
External supply current |
210 mA at 24V DC |
Power dissipation |
4.7 W at 31.2V DC (16 BTU/hr) |
Operating temperature |
-20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Channel-to-channel isolation at 120V continuous with TB2, TB3, TB3S, TB3T or TB3TS bases, and 250V continuous with a TBN base.
1500V AC for 60 s and 2550V DC for 1 s type tests between channel and channel and I/O to system are the published isolation figures.
Six ranges: 4...20 mA, 0...20 mA, +/-10V, 0...10V, +/-5V and 0...5V, configurable per channel.
15 bits plus sign at 0.656 uA and 0.320 mV per count is finer than the non-isolated four-channel card.
0.1% of full scale at 25 deg C with 0.0025% per deg C on current and 0.0012% on voltage drift.
Under 25 us to 63% of full scale is the fastest analog output response in the FLEX I/O analog line.
Digital-to-analog conversion at 2.5 or 5.0 ms for all channels; the update rate does not limit the step itself.
0...750 Ohm resistive load on current and 3 mA on voltage output, unchanged from the non-isolated card.
Factory calibrated, so there is no trim procedure, and the isolation is not compromised by a field adjustment.
210 mA at 24V DC is the module consumption, higher than the 1794-OE4 because of four isolated output stages.
4.7 W at 31.2V DC (16 BTU/hr) is the heat to add to the enclosure calculation.
-20...55 deg C on the standard version; the 1794-OF4IXT publishes -20...70 deg C with a 75 mm deep body.
Wire category 2 on signal ports and 3 on power ports is stated in the publication, which is worth checking against the panel's routing plan.
Each output has its own return, which is the point of the card: four devices at four different ground references can be driven from one slot.
250V continuous isolation only with a TBN base is a base-dependent rating, not a module-only one, and it belongs on the drawing.
Shielded pair per loop with the shield at the panel is the practice; isolation breaks ground loops, it does not remove induced noise.
One signal type per channel, and a voltage device on a current-configured channel reads zero without any diagnostic bit.
Fast analog references — drive speed references, proportional valves that follow a ramp.
Mixed ground references across four field devices in the same panel.
Not for HART. The 1794-OF8IH carries the HART modem and eight isolated outputs.
Not for density. Four isolated outputs cost a slot that a non-isolated card would fill with twelve.
How many outputs has the 1794-OF4I?
Four isolated analog outputs with individual range configuration.
What isolation does it provide?
Channel-to-channel at 120V continuous with TB2/TB3/TB3S/TB3T bases, 250V with TBN; type tested at 1500V AC for 60 s.
What ranges are available?
4...20 mA, 0...20 mA, +/-10V, 0...10V, +/-5V and 0...5V.
How fast does it respond?
Under 25 us to 63% of full scale, with 2.5 or 5.0 ms conversion for all channels.
What accuracy does it achieve?
0.1% of full scale at 25 deg C, factory calibrated.
What current does the module draw?
210 mA at 24V DC.