Product Details:
Payment & Shipping Terms:
|
The 1794-TB3K is the conformally coated cage-clamp terminal base: 16 I/O terminals, 18 common and 18 +V, rated 10 A and -20...70 deg C.
The K suffix is the coating, and it is what pairs this base with the -XT extended-temperature modules on the same rail.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O terminal base, 1794 backplane |
Cat Num |
1794-TB3K |
Brand Name |
Rockwell |
Termination |
Cage clamp, 16 I/O, 18 common, 18 +V |
Wire size |
0.34...3.3 mm2 (22...12 AWG), 75 deg C or greater, 1.2 mm insulation max |
Current capacity |
10 A maximum |
Voltage |
Up to 132V AC / 156V DC |
Wiring category |
2 |
Dimensions |
94 x 94 x 69 mm |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
16 I/O, 18 common and 18 +V terminals in a cage clamp, so each field wire is held by a screw-driven clamp rather than a spring.
10 A maximum current capacity across the base, which is the number to check against a 16-point output card's total load.
24...12 AWG accepted, with 1.2 mm maximum insulation diameter.
Up to 132V AC / 156V DC on the terminals, and wiring category 2 for the routing plan.
Conformal coating is the only difference between the 1794-TB3K and the 1794-TB3.
-20...70 deg C operating range matches the XT modules, so a cold panel keeps one temperature statement across the base and the card.
94 x 94 x 69 mm is identical to the uncoated base, so the rail length and enclosure depth do not change.
The base plugs to the next base and forms the backplane; no separate wiring between bases is required.
The general-purpose 1794 base, described in the selection guide as intended for 3-wire input proximity switches and usable with output modules.
Three-wire sensors use the +V and common terminals, which is why the base carries 18 of each rather than a single pair.
Not the choice for temperature modules, which need the CJC sets of the 1794-TB3T.
Not the choice for 32-point cards, which need the 1794-TB32 terminal count.
35 x 7.5 mm DIN rail (Allen-Bradley 199-DR1, DIN 46277-3) with at least 25 mm of air space around the system.
A zinc-plated, yellow-chromated steel rail is required for grounding through the rail; aluminium or plastic rail gives intermittent grounding.
1794-NM1 panel-mount kit with 18 screws replaces the rail where direct mounting is needed.
1492-EA35 DIN rail locks are recommended in high-vibration or vertical installations.
Extended-temperature islands where every base should match the -XT cards.
Panels with condensation that the coating is specified for.
Not for thermocouples; the 1794-TB3T provides the two CJC sets.
Not for 32-point modules; use the 1794-TB32 or 1794-TB32S.
What does the K suffix mean on the 1794-TB3K?
It is the conformally coated version of the 1794-TB3 base.
How many terminals has it?
16 I/O, 18 common and 18 +V, in a cage clamp.
What current can it carry?
10 A maximum, with 24...12 AWG wire.
What is the operating temperature?
-20...70 deg C.
Does it need separate backplane wiring?
No, bases plug together to form the backplane.
What rail does it mount on?
35 x 7.5 mm DIN rail, or panel mount with the 1794-NM1 kit.