Product Details:
Payment & Shipping Terms:
|
The 1794-IF2XOF2I is a two-in, two-out analog module with channel-to-channel isolation and a sigma-delta input converter at 16 bits, for loops where each channel sits at its own field reference.
Two isolated inputs and two isolated outputs in one slot is a narrow requirement, and it is the only card in the 1794 analog line that meets it with a 0.1% full-scale accuracy statement.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O isolated analog combination, 1794 terminal base |
Cat Num |
1794-IF2XOF2I |
Brand Name |
Rockwell |
Channels |
2 inputs and 2 outputs, channel-to-channel isolated |
Input ranges |
0...20 mA, +/-10V DC |
Input resolution |
16 bits; 0.156/0.313 mV, 0.320/0.640 uA |
Input conversion |
Sigma-delta, 2.5, 5.0 or 7.5 ms |
Input accuracy |
0.1% of full scale |
Input drift |
0.0038, 0.0028, 0.0025 or 0.0012 %FS per deg C, range dependent |
Output resolution |
15 bits plus sign; 0.656 uA, 0.320 mV |
Output conversion |
Digital-to-analog converter, 2.5 or 5.0 ms |
Load |
0...750 Ohm current; 3 mA maximum on voltage output |
Isolation |
120V continuous with TB3/TB3S/TB2/TB3T/TB3TS, 250V with TBN; 1500V AC 60 s, 2550V DC 1 s |
External supply current |
150 mA at 24V DC |
Power dissipation |
3.3 W at 31.2V DC (11 BTU/hr) |
Operating temperature |
-20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Channel-to-channel isolation at 120V continuous with a TB3, TB3S, TB2, TB3T or TB3TS base, and 250V continuous with a TBN base.
1500V AC for 60 s and 2550V DC for 1 s are the type tests, channel to channel and field to system.
The base is part of the rating, so a 250V circuit needs the TBN base, not just the module.
Two in, two out is a deliberate channel count: an isolated loop pair, not a dense island.
Sigma-delta conversion at 2.5, 5.0 or 7.5 ms selectable per module, trading update rate for rejection.
16 bits of resolution at 0.156 or 0.313 mV and 0.320 or 0.640 uA depending on the range.
0.1% of full scale accuracy with drift from 0.0038 down to 0.0012 %FS per deg C, the finer figure belonging to the slower filter setting.
The slower the conversion, the better the drift and noise figures — the three settings are a real engineering choice, not a formality.
15 bits plus sign at 0.656 uA or 0.320 mV per count.
Digital-to-analog conversion at 2.5 or 5.0 ms for both channels.
0...750 Ohm current load and 3 mA maximum on voltage output are the same limits as the other 1794 output cards.
The outputs are isolated channel to channel , which is why a two-loop valve station can share one slot.
150 mA at 24V DC and 3.3 W (11 BTU/hr) at 31.2V DC is a modest budget for four isolated channels.
-20...55 deg C on the standard version; the 1794-IF2XOF2IXT publishes -20...70 deg C and a 75 mm deep body.
Terminal base selection drives both the isolation rating and the wiring plan, and it is decided before the module is ordered.
One signal type per channel, as everywhere in this family; the isolation does not make a mis-wired channel work.
Two isolated loops — a transmitter at one reference and a valve at another, in one slot.
Mixed signal cabinets where a barrier is undesirable and isolation in the module is preferred.
Not for density; the 1794-IE8XOE4 fits twelve channels in the same slot without isolation.
Not for HART; HART variants exist separately on both sides.
How many channels has the 1794-IF2XOF2I?
Two isolated analog inputs and two isolated analog outputs.
What isolation does it provide?
120V continuous with TB3/TB3S/TB2/TB3T/TB3TS bases or 250V with TBN; type tested at 1500V AC for 60 s.
What resolution does the input offer?
16 bits, with sigma-delta conversion at 2.5, 5.0 or 7.5 ms.
What accuracy does it achieve?
0.1% of full scale on the input, with 0.0038 to 0.0012 %FS per deg C drift depending on the filter setting.
What load can the outputs drive?
0...750 Ohm on current output and 3 mA maximum on voltage output.
What current does the module draw?
150 mA at 24V DC, dissipating 3.3 W at 31.2V DC.