The 1794-IC16 reads 16 sinking 48V DC inputs — the 48V DC variant of the 1794-IB16, for panels that run a 48V control rail instead of 24V.
One module covers a full 16-point group at 5 mA per point, so the field supply carries about 82 mA at nominal voltage on top of the device currents.
| 1794-IB8 | 8-point 24V DC sinking input module | IN STOCK |
| 1794-IB16 | 16-point 24V DC sinking input module | IN STOCK |
| 1794-IB32 | 32-point 24V DC sinking input module | IN STOCK |
| 1794-IB10XOB6 | 10 inputs / 6 sourcing outputs, 24V DC combo module | IN STOCK |
| 1794-IB16XOB16P | 16 inputs / 16 protected sourcing outputs combo module | IN STOCK |
| 1794-IB16D | 16-point diagnostic sinking input module | IN STOCK |
| 1794-IB16XT | 16-point 24V DC sinking input, extended temperature | IN STOCK |
| 1794-IB10XOB6XT | 10 inputs / 6 sourcing outputs, extended temperature | IN STOCK |
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IC16 | 16-point 48V DC sinking input module | IN STOCK |
| 1794-IG16 | 16-point 5V DC TTL input module | IN STOCK |
| 1794-IH16 | 16-point 125V DC sinking input module | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-IV16 | 16-point 24V DC sourcing input module | IN STOCK |
| 1794-IV32 | 32-point 24V DC sourcing input module | IN STOCK |
Application |
FLEX I/O digital input, 48V DC |
Cat Num |
1794-IC16 |
Brand Name |
Rockwell |
Number of inputs |
16, nonisolated, sinking |
On-state voltage |
30V DC min, 48V DC nom, 60V DC max |
On-state current |
2.0 mA @ 30V, 5.0 mA @ 48V, 7.0 mA @ 60V |
Off-state voltage, max |
10V DC |
Input impedance |
11 k ohm nominal |
External supply |
48V DC nominal, 30...60V DC range |
Supply current |
51 mA @ 30V, 82 mA @ 48V, 107 mA @ 60V |
Terminal base |
1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
On-state 30...60V DC, 5.0 mA at 48V nominal, with 2.0 mA at the 30V threshold and 7.0 mA at 60V.
Off-state below 10V DC, 11 k ohm nominal input impedance, which sets the leakage a two-wire device may pass without being read as On.
16 sinking inputs, nonisolated, one group, with 16 yellow status indicators on the field side.
Keyswitch position 1 on the terminal base, as set out in publication 1794-IN105.
Inputs land on terminals A-0...A-15, with the 48V supply on C-35...C-50 and commons on B-17...B-32.
C-34...C-51 are internally connected, so the supply can be brought in once and distributed across the base.
3-wire devices also need the common terminal, 2-wire devices use input and supply only.
Daisy chain to the next base by jumpering C-51 to C-34 and B-33 to B-16.
51 mA at 30V, 82 mA at 48V, 107 mA at 60V is the module's own draw from the field supply.
The field devices add to that, and the base is limited to 10 A total through its terminals.
The 48V rail is not generated by the adapter, so a 48V supply is part of the panel design.
Fusing is external; the module has none.
48V DC control circuits carried over from older machine designs.
Longer cable runs where 48V tolerates more voltage drop than 24V.
Not a substitute for 125V DC; the 1794-IH16 covers that range.
Not isolated; the 1794-IA8I style isolated AC parts are a different family.
Retrofit panels with an existing 48V rail.
Machines mixing 24V logic and 48V field devices.
Not for 24V islands; the 1794-IB16 is the equivalent at 24V.
Not for extended temperature; 0...55 deg C only.
How many inputs has the 1794-IC16?
16 nonisolated sinking inputs.
What voltage range does it accept?
30...60V DC, with 48V DC nominal.
What is the on-state current?
5.0 mA at 48V DC, 2.0 mA at 30V and 7.0 mA at 60V.
Which terminal bases are used?
1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
What is the operating temperature?
0...55 deg C.
Does the module supply the 48V rail?
No; a separate 48V supply feeds C-34 and the module draws 51 to 107 mA from it.