Product Details:
Payment & Shipping Terms:
|
The 1794-CJC2 supplies two cold junction compensation parts, the replaceable element on a FLEX I/O temperature base.
The temperature bases carry two CJC sets for the 1794-IT8 and 1794-IRT8, so this kit is a one-base replacement or a spares line for a maintenance crib.
| 1794-PS3 | 120/220V AC power supply, 24V DC 3.0 A | IN STOCK |
| 1794-PS13 | 120/220V AC power supply, 24V DC 1.3 A | IN STOCK |
| 1794-CE1 | 0.3 m (1 ft) extender cable for FLEX I/O | IN STOCK |
| 1794-CE3 | 0.9 m (3 ft) extender cable for FLEX I/O | IN STOCK |
| 1794-NM1 | panel mounting kit with 18 screws | IN STOCK |
| 1794-N2 | empty slot filler module, no electronics | IN STOCK |
| 1794-CJC2 | cold junction compensation kit, two parts | IN STOCK |
| 1794-LBL | label kit with die-cut sheet and five labels | IN STOCK |
Application |
Replacement cold junction compensation for FLEX I/O temperature bases |
Cat Num |
1794-CJC2 |
Brand Name |
Rockwell |
Contents |
Two cold junction compensation parts |
Fits |
1794-TB3T, 1794-TB3TK, 1794-TB3TS, 1794-TB3TSK |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Two cold junction compensation parts, the sensing element at the terminal block where the thermocouple wire lands.
Fits the temperature bases: 1794-TB3T, TB3TK, TB3TS and TB3TSK, each of which carries two sets.
Replaceable rather than soldered, so a drifted junction is a part swap.
The K suffix denotes the coated variant of the metal parts.
Cold junction compensation corrects for the terminal temperature, which is where the thermocouple actually terminates.
A drifted CJC reads as a temperature offset across every channel on the card, not as a random error.
Replacing both sets at once keeps the two halves of the base matched.
No recalibration of the module is implied by the accessory listing.
Spare parts for thermocouple islands, where a CJC failure stops a loop.
Base refurbishment when a coated base is reused.
Not a thermocouple; it does not include sensors or wire.
Not for the IR8; that module uses the ground terminals, not CJC sets.
One kit covers one base at two parts.
Count bases, not channels, when stocking spares.
1794-TB3T and 1794-TB3TK are cage clamp; the TS versions are spring.
Publication 1794-SG002 lists the kit in the accessory section.
Thermocouple and RTD islands with IT8 or IRT8 cards.
Maintenance cribs for plants with several temperature bases.
Not for analog voltage or current inputs; they do not use CJC.
Not for -XT upgrades on their own; the base and module coatings still matter.
What is in the 1794-CJC2 kit?
Two cold junction compensation parts.
Which bases does it fit?
1794-TB3T, 1794-TB3TK, 1794-TB3TS and 1794-TB3TSK.
How many sets does a temperature base carry?
Two.
Why replace a CJC?
A drifted junction offsets every channel on the card.
Is it used with the 1794-IR8?
No; the IR8 relies on the base ground terminals instead.
How many kits per base?
One kit, containing both parts.