Product Details:
Payment & Shipping Terms:
|
The 1794-ASB2 Series D is the small-island Remote I/O adapter: 2 modules only, where the 1794-ASB carries 8. Everything else — rates, power, isolation, footprint — is shared with the larger adapter.
That capacity limit is the whole point of the part. It is the right choice when a rack slot or two needs a Remote I/O node and an 8-module adapter would be wasted spend.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 15 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 15 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O Remote I/O adapter, 2 module |
Cat Num |
1794-ASB2 Series D |
Brand Name |
Rockwell |
I/O module capacity |
2 modules |
Input voltage range |
19.2...31.2V DC, 450 mA |
Output voltage |
5V DC, 640 mA |
Inrush current |
23 A at 24V DC for 2 ms |
Communication rate |
57.6, 115.2, 230.4 kbps |
Isolation |
50V continuous, tested 750V DC for 60 s |
Dimensions |
87 x 69 x 69 mm |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
2 I/O modules maximum, against 8 on the 1794-ASB Series E.
Same 640 mA of 5V Flexbus output, so a single module pair is never current-limited.
Same 57.6/115.2/230.4 kbps rates and switch-set rack numbering.
Same 87 x 69 x 69 mm body, so the rail footprint does not shrink with the capacity.
19.2...31.2V DC at 450 mA maximum input draw.
330 mA at 24V typical, 23 A inrush for 2 ms.
4.6 W dissipation and 1.7 BTU/hr at 31.2V DC.
Isolation 50V continuous, tested at 750V DC for 60 s.
Do not use with Classic PLC-5/15 or PLC-5/25, as with the 1794-ASB Series E.
European Zone 2 and North American hazardous location approved as Series D.
Belden 9463 cable, removable RIO connector, PRL reset button.
Termination at the last adapter on the link.
Small RIO nodes of one or two modules.
Cost-driven panels where a 2-module adapter replaces a full one.
Not a 8-module adapter; the capacity is fixed at 2.
Not for PLC-5/15 or PLC-5/25.
Sparse remote racks.
Legacy RIO systems with small drops.
Not EtherNet/IP migration — the AENT is that path.
Not ControlNet.
How many modules can the 1794-ASB2 carry?
2 FLEX I/O modules, against 8 on the 1794-ASB Series E.
What rates does it support?
57.6, 115.2 and 230.4 kbps.
Which processors must not use it?
Classic PLC-5/15 and PLC-5/25.
What is the isolation rating?
50V continuous, tested at 750V DC for 60 s.
What is the Flexbus output?
5V DC at 640 mA.
What is the inrush?
23 A at 24V DC for 2 ms.