Product Details:
Payment & Shipping Terms:
|
1783-BMS06SGA is a DIN rail managed switch designed to sit in the control cabinet on the same 24V dc bus as the controllers — 6 ports.
Gigabit fibre on a six port switch is the cheapest way to stop the inter-cabinet trunk becoming the bottleneck, and it keeps the copper side unchanged.
| 1783-BMS20CL | Stratix 5700, 20 ports, 16 copper + 2 combo + 2 SFP | IN STOCK |
| 1783-BMS20CGP | Stratix 5700, 20 ports, gigabit combo | IN STOCK |
| 1783-BMS20CGL | Stratix 5700, 20 ports, gigabit combo, Lite firmware | IN STOCK |
| 1783-BMS20CGPK | Stratix 5700, 20 ports, gigabit combo, kit | IN STOCK |
| 1783-BMS06TA | Stratix 5700, 6 copper ports | IN STOCK |
| 1783-BMS06TL | Stratix 5700, 6 copper ports, Lite firmware | IN STOCK |
| 1783-BMS06TGA | Stratix 5700, 4 copper + 2 gigabit copper | IN STOCK |
| 1783-BMS06SA | Stratix 5700, 4 copper + 2 SFP | IN STOCK |
| 1783-BMS06SL | Stratix 5700, 4 copper + 2 SFP, Lite firmware | IN STOCK |
| 1783-BMS06SGA | Stratix 5700, 4 copper + 2 gigabit SFP | IN STOCK |
| 1783-BMS06SGL | Stratix 5700, 4 copper + 2 gigabit SFP, Lite firmware | IN STOCK |
| 1783-MS06T | Stratix 8000, 6 port chassis | IN STOCK |
| 1783-MS10T | Stratix 8000, 10 port chassis | IN STOCK |
| 1783-RMS06T | Stratix 8300, 6 port layer 3 | IN STOCK |
| 1783-RMS10T | Stratix 8300, 10 port layer 3 | IN STOCK |
| 1783-EMS04T | Stratix 6000, 4 port managed | IN STOCK |
| 1783-MX08T | Stratix 8000 copper 8 port expansion | IN STOCK |
| 1783-MX08F | Stratix 8000 fibre 8 port expansion | IN STOCK |
| 1783-MCF | Stratix 8000 CompactFlash spare card | IN STOCK |
| 1783-RMCF | Stratix 8300 CompactFlash spare card | IN STOCK |
| 1783-ETAP | EtherNet/IP tap, 3 copper ports | IN STOCK |
| 1783-ETAP2F | EtherNet/IP tap, 1 copper + 2 fibre | IN STOCK |
| 1783-SFP100FX | 100FX multimode SFP, 2 km | IN STOCK |
| 1783-SFP100LX | 100LX singlemode SFP, 10 km | IN STOCK |
| 1783-SFP1GSX | 1000SX multimode SFP, 550 m | IN STOCK |
| 1783-SFP1GLX | 1000LX singlemode SFP, 10 km | IN STOCK |
| 1783-US8T | Stratix 2000, 8 copper ports, unmanaged | IN STOCK |
| 1783-US03T01F | Stratix 2000, 3 copper + 1 fibre, unmanaged | IN STOCK |
Catalog number |
1783-BMS06SGA |
Product family |
Stratix 5700 6 port managed switch |
Total ports |
6 ports |
Copper ports |
4 * 10/100 RJ45 |
SFP ports |
2 * 10/100/1000 SFP |
Combination ports |
None |
Power input |
12…48V dc, Class 2 / SELV, 0.5 A |
Power consumption |
15 W maximum, 9.5 W at 24V dc and 40 °C |
Weight |
1.11 kg |
Mounting |
DIN rail (top hat rail) |
Firmware type |
Full |
Lifecycle status |
Discontinued September 01, 2024 |
Replacement category |
Engineering Replacement |
Replacement product |
Not named on the product page |
Publication |
1783-UM011 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1783-UM011 (module specifications) and Rockwell literature library (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Copper: 4 * 10/100 RJ45. SFP: 2 * 10/100/1000 SFP. Combination: None.
A combination port accepts either an RJ45 module or a Mini-GBIC, so the copper count and the fibre count cannot both be taken at face value on a unit where both are populated.
12…48V dc, Class 2 / SELV, 0.5 A; 15 W maximum, 9.5 W at 24V dc and 40 °C; DIN rail (top hat rail).
An alarm relay rated 1 A at 30V dc switches a panel lamp or a PLC input when the switch loses a supply or a monitored condition. That contact is often the only thing an operator sees when the network fails. A wide 12…48V dc range is deliberate: the switch runs from the same supply as the controllers.
Four copper devices on the cell and two gigabit fibre links toward the backbone — a compact aggregation node.
Managed switching inside a panel is about segmentation and diagnostics, not throughput. A cell/zone layout with IGMP snooping is what stops multicast I/O traffic from flooding every port in the cabinet.
Discontinued September 01, 2024, replacement category Engineering Replacement; the product page names no specific replacement product for this catalog number.
Existing units stay in service for years after a switch is retired. The practical questions are spare hardware and configuration backup — a replacement switch with no saved configuration is not a spare.
Ask for the firmware revision, the configuration export and a photograph of the label. On a managed switch these three matter more than cosmetic condition.
A unit pulled from a working line with a documented configuration is worth more than an unconfigured identical unit, and should be priced that way.
How many ports does 1783-BMS06SGA have?
6 ports
What power does 1783-BMS06SGA need?
12…48V dc, Class 2 / SELV, 0.5 A
Is 1783-BMS06SGA still available from Rockwell?
No. Discontinued September 01, 2024; replacement category Engineering Replacement.
What replaces 1783-BMS06SGA?
The product page lists Engineering Replacement without naming a specific replacement product.
What is 1783-BMS06SGA used for?
Stratix 5700 6 port managed switch — a managed Ethernet switch for a control network.
1783-BMS06SGA is a Stratix industrial Ethernet switch from the Allen-Bradley range, specified here against the Rockwell technical data rather than a distributor summary, so the port count, the supply range and the temperature ceiling are the figures an integrator can build a cabinet around.
| Specification | Value |
|---|---|
| Port configuration | 4 Fast Ethernet RJ45 ports plus 2 Gigabit SFP slots |
| Firmware | Full firmware, the usual choice for a cell uplinked at Gigabit |
| Alarm relay | 1 A at 30V DC or 0.5 A at 48V DC |
| Power input | 12 to 48V DC, Class 2 or SELV, 0.5 to 3.0 A maximum depending on model |
| Power consumption | 9.5 to 21 W at 24V DC and 40 degrees C, 14 to 30 W maximum across the range |
| Ethernet rate | Fast Ethernet 10/100 Mbps on RJ45 ports, Gigabit on the GE ports and SFP slots |
| Cabling | RJ45 to IEC 60603-7, Category 5e minimum to TIA 568-B.1 or Category 5 to ISO/IEC 24702 |
| Wire size, power | 0.5 to 0.8 mm2 (20 to 18 AWG) copper rated 75 degrees C or higher, 1.2 mm insulation maximum |
| Operating temperature | -40 to 60 degrees C, surrounding air maximum 60 degrees C |
| Storage temperature | -40 to 85 degrees C |
| Humidity | 5 to 95 percent noncondensing |
| Shock and vibration | 30 g operating, 55 g nonoperating, 2 g at 10 to 500 Hz |
| Emissions | CISPR 11 Class A, ESD 8 kV contact and 15 kV air |
| Enclosure rating | IP30, open style |
| Source | 1783-TD002D-EN-P, May 2023 |
Read the suffix rather than the base number when specifying this unit. The same six port body is sold as T, S or SG and as L or A, and the difference between an L and an A part is whether the firmware carries the ring and time synchronisation features that a coordinated cell depends on. A Lite unit is a real product, not a crippled one, and it is the right choice where the cell only needs a transparent switch with diagnostics.
DIN rail mounting and panel mounting are both supported, and in this range the 20 port units are the ones usually chosen as the aggregation point of a line: sixteen copper drops cover a row of drives and I/O heads, two Gigabit SFP slots carry the uplink to the plant backbone, and the two remaining Fast Ethernet ports serve the local HMI or a diagnostics laptop.
Where a value in this table is a range rather than a single figure, it is a range because the Rockwell table publishes it that way across the model group; the individual unit is then fixed by its catalog suffix. Anything an engineer needs beyond this, including the certification file and the full EMC test list, is in the technical data publication named at the bottom of the table.
A switch that has been in a cabinet for eight years, 1783-BMS06SGA among them, is usually still electrically sound and functionally obsolete. The practical question at replacement time is whether the firmware can still be managed by the current tool, and a unit that cannot be reached by the engineering software is a unit that will be replaced on failure rather than on schedule.
A managed switch adds the diagnostics that make a network debuggable: port level counters, spanning tree, and in the Stratix range a Device Level Ring that survives a single cable break. The catalog suffix tells you whether that firmware is present, and a Lite unit is not upgradeable into a Full one by flashing it. For 1783-BMS06SGA the suffix is the only reliable statement of which firmware set ships.
Every one of these units, 1783-BMS06SGA included, is open style, which means it belongs in an enclosure with a pollution degree 2 environment. The IP30 rating protects against fingers and tools, not against water, and a switch mounted on an open panel in a wet area is a warranty claim waiting to happen.
Cybersecurity hardening starts at the switch, not at the firewall. Disabling unused ports, changing the default credentials, and keeping the management interface off the plant backbone are the three steps that close most findings in an industrial network assessment, and none of them require a licence.
Ethernet ports are rated for Category 5e cable at minimum, and the connector is the IEC 60603-7 RJ45 that every industrial patch cord already uses. Where a cabinet is wired with older Category 5 cable, the link will usually train at 100 Mbps but the error counters will climb, which is why the cable class is printed next to the port table.
For 1783-BMS06SGA the NAT variants exist for the machine builder who must hand over a cell with a fixed internal address scheme. A configurable NAT router lets the same internal IP plan be reused on every machine while the plant side sees a different address, which removes an entire class of commissioning arguments.
Spare parts strategy on a switch is driven by firmware, not by hardware. A Lite spare cannot replace a Full unit in a ring that depends on CIP Sync, so the stocking list should carry the suffix rather than the base number, and the label on the failed unit is the authority.
In a plant network the switch, 1783-BMS06SGA included, is usually the part that gets blamed last and fails first, because it sits between a drive that trips and a controller that logs nothing. Keeping the port count, the supply range and the temperature rating on the page means a maintenance engineer can replace a unit without opening a drawing set.
Device Level Ring is the reason many of these switches exist in a machine line. A ring built from two ports per device survives one open cable without dropping the cell, and the recovery time is a property of the ring rather than of any single switch, so a mixed vendor ring has to be checked as a whole.
The emission class is CISPR 11 Class A, which is an industrial environment statement. Mounting one of these in a light industrial or residential panel can require additional filtering, and that is a compliance question rather than a performance one, so it belongs in the quotation stage.
The distance an SFP reaches is a property of the optic and the fiber, not of the switch. Multimode runs to a few hundred meters, singlemode runs to kilometers, and the budget has to cover connectors and splices, so the link loss calculation belongs in the same document as the port list.
An unmanaged switch has no address and no configuration, so it either forwards frames or it does not. That is a feature in a machine cell where nobody wants a config file to restore after a controller swap, and it is a liability in a line where someone needs to know which port dropped a packet.
On 1783-BMS06SGA conformal coating is a suffix rather than a separate product, and it matters in washdown or sulfur bearing atmospheres. Where a cabinet sits in a food plant or near a rubber process, the coated variant is the one to quote, because condensation on an uncoated board is a failure that shows up months later.
Commissioning a switch takes an afternoon the first time and twenty minutes afterwards: address it, set the ring or the redundant path, confirm the port counters stay clean under load, and record the firmware revision on the as-built drawing. The failures that survive to production are almost always a duplicate address or a loop nobody documented.
Confirm the ring or uplink topology on the drawing before ordering, check the 60 degrees C surrounding air limit against the cabinet thermal calculation, and record the firmware suffix on the spare parts list.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley 1783 network switches category.